All the vulnerabilites related to Rockwell Automation - ControlLogix® 5570 redundant
cve-2024-21916
Vulnerability from cvelistv5
Published
2024-01-31 18:28
Modified
2024-08-01 22:35
Summary
Rockwell Automation Denial-of-service Vulnerability in ICE1 Controller
Show details on NVD website


{
  "containers": {
    "adp": [
      {
        "affected": [
          {
            "cpes": [
              "cpe:2.3:o:rockwellautomation:controllogix_5570_controller_firmware:20.011:*:*:*:*:*:*:*"
            ],
            "defaultStatus": "unknown",
            "product": "controllogix_5570_controller_firmware",
            "vendor": "rockwellautomation",
            "versions": [
              {
                "status": "affected",
                "version": "20.011"
              }
            ]
          },
          {
            "cpes": [
              "cpe:2.3:o:rockwellautomation:guardlogix_5570_controller_firmware:20.011:*:*:*:*:*:*:*"
            ],
            "defaultStatus": "unknown",
            "product": "guardlogix_5570_controller_firmware",
            "vendor": "rockwellautomation",
            "versions": [
              {
                "status": "affected",
                "version": "20.011"
              }
            ]
          },
          {
            "cpes": [
              "cpe:2.3:o:rockwellautomation:controllogix_5570_redundant_controller_firmware:20.054_kit1:*:*:*:*:*:*:*"
            ],
            "defaultStatus": "unknown",
            "product": "controllogix_5570_redundant_controller_firmware",
            "vendor": "rockwellautomation",
            "versions": [
              {
                "status": "affected",
                "version": "20.054_kit1"
              }
            ]
          }
        ],
        "metrics": [
          {
            "other": {
              "content": {
                "id": "CVE-2024-21916",
                "options": [
                  {
                    "Exploitation": "none"
                  },
                  {
                    "Automatable": "yes"
                  },
                  {
                    "Technical Impact": "partial"
                  }
                ],
                "role": "CISA Coordinator",
                "timestamp": "2024-02-06T05:00:32.025684Z",
                "version": "2.0.3"
              },
              "type": "ssvc"
            }
          }
        ],
        "providerMetadata": {
          "dateUpdated": "2024-07-01T19:54:41.466Z",
          "orgId": "134c704f-9b21-4f2e-91b3-4a467353bcc0",
          "shortName": "CISA-ADP"
        },
        "title": "CISA ADP Vulnrichment"
      },
      {
        "providerMetadata": {
          "dateUpdated": "2024-08-01T22:35:34.618Z",
          "orgId": "af854a3a-2127-422b-91ae-364da2661108",
          "shortName": "CVE"
        },
        "references": [
          {
            "tags": [
              "x_transferred"
            ],
            "url": "https://www.rockwellautomation.com/en-us/support/advisory.SD1661.html"
          }
        ],
        "title": "CVE Program Container"
      }
    ],
    "cna": {
      "affected": [
        {
          "defaultStatus": "unaffected",
          "product": "ControlLogix\u00ae 5570",
          "vendor": "Rockwell Automation",
          "versions": [
            {
              "status": "affected",
              "version": "20.011"
            }
          ]
        },
        {
          "defaultStatus": "unaffected",
          "product": "GuardLogix\u00ae 5570",
          "vendor": "Rockwell Automation",
          "versions": [
            {
              "status": "affected",
              "version": "20.011"
            }
          ]
        },
        {
          "defaultStatus": "unaffected",
          "product": "ControlLogix\u00ae 5570 redundant",
          "vendor": "Rockwell Automation",
          "versions": [
            {
              "status": "affected",
              "version": "20.054_kit1"
            }
          ]
        }
      ],
      "datePublic": "2024-01-30T14:00:00.000Z",
      "descriptions": [
        {
          "lang": "en",
          "supportingMedia": [
            {
              "base64": false,
              "type": "text/html",
              "value": "\n\n\u003cspan style=\"background-color: rgb(255, 255, 255);\"\u003eA denial-of-service vulnerability exists in specific Rockwell Automation ControlLogix ang GuardLogix controllers. If exploited, the product could potentially experience a major nonrecoverable fault (MNRF). The device will restart itself to recover from the \u003c/span\u003e\u003ca target=\"_blank\" rel=\"nofollow\"\u003eMNRF.\u003c/a\u003e"
            }
          ],
          "value": "\nA denial-of-service vulnerability exists in specific Rockwell Automation ControlLogix ang GuardLogix controllers. If exploited, the product could potentially experience a major nonrecoverable fault (MNRF). The device will restart itself to recover from the MNRF."
        }
      ],
      "impacts": [
        {
          "capecId": "CAPEC-100",
          "descriptions": [
            {
              "lang": "en",
              "value": "CAPEC-100 Overflow Buffers"
            }
          ]
        }
      ],
      "metrics": [
        {
          "cvssV3_1": {
            "attackComplexity": "LOW",
            "attackVector": "NETWORK",
            "availabilityImpact": "HIGH",
            "baseScore": 8.6,
            "baseSeverity": "HIGH",
            "confidentialityImpact": "NONE",
            "integrityImpact": "NONE",
            "privilegesRequired": "NONE",
            "scope": "CHANGED",
            "userInteraction": "NONE",
            "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:C/C:N/I:N/A:H",
            "version": "3.1"
          },
          "format": "CVSS",
          "scenarios": [
            {
              "lang": "en",
              "value": "GENERAL"
            }
          ]
        }
      ],
      "problemTypes": [
        {
          "descriptions": [
            {
              "cweId": "CWE-119",
              "description": "CWE-119 Improper Restriction of Operations within the Bounds of a Memory Buffer",
              "lang": "en",
              "type": "CWE"
            }
          ]
        }
      ],
      "providerMetadata": {
        "dateUpdated": "2024-01-31T18:28:59.715Z",
        "orgId": "b73dd486-f505-4403-b634-40b078b177f0",
        "shortName": "Rockwell"
      },
      "references": [
        {
          "url": "https://www.rockwellautomation.com/en-us/support/advisory.SD1661.html"
        }
      ],
      "solutions": [
        {
          "lang": "en",
          "supportingMedia": [
            {
              "base64": false,
              "type": "text/html",
              "value": "\n\n\u003cul\u003e\u003cli\u003eUpdate to corrected Firmware.\u0026nbsp;\u003c/li\u003e\u003c/ul\u003e\n\n\u003ctable\u003e\u003ctbody\u003e\u003ctr\u003e\u003ctd\u003e\u003cp\u003e\u003ca target=\"_blank\" rel=\"nofollow\"\u003eAffected Product\u003c/a\u003e\u003c/p\u003e\u003c/td\u003e\u003ctd\u003e\u003cp\u003e\u003ca target=\"_blank\" rel=\"nofollow\"\u003eFirst Known in Firmware\u003c/a\u003e\u003c/p\u003e\u003c/td\u003e\u003ctd\u003e\u003cp\u003eCorrected in Firmware\u003c/p\u003e\u003c/td\u003e\u003c/tr\u003e\u003ctr\u003e\u003ctd\u003e\u003cp\u003eControlLogix\u00ae 5570\u003c/p\u003e\u003c/td\u003e\u003ctd\u003e\u003cp\u003e20.011\u003c/p\u003e\u003c/td\u003e\u003ctd\u003e\u003cp\u003ev33.016, 34.013, 35.012, 36.011 and later\u003c/p\u003e\u003c/td\u003e\u003c/tr\u003e\u003ctr\u003e\u003ctd\u003e\u003cp\u003eGuardLogix\u00ae 5570\u003cb\u003e\u003c/b\u003e\u003c/p\u003e\u003c/td\u003e\u003ctd\u003e\u003cp\u003e20.011\u003c/p\u003e\u003c/td\u003e\u003ctd\u003e\u003cp\u003ev33.016, 34.013, 35.012, 36.011 and later\u003c/p\u003e\u003c/td\u003e\u003c/tr\u003e\u003ctr\u003e\u003ctd\u003e\u003cp\u003eControlLogix\u00ae 5570 redundant\u003cb\u003e\u003c/b\u003e\u003c/p\u003e\u003c/td\u003e\u003ctd\u003e\u003cp\u003e20.054_kit1\u003c/p\u003e\u003c/td\u003e\u003ctd\u003e\u003cp\u003ev33.053_kit1, 34.052_kit1, 35.052_kit1, 36.051_kit1 and late\u003c/p\u003e\u003c/td\u003e\u003c/tr\u003e\u003c/tbody\u003e\u003c/table\u003e\n\n\u003cbr\u003e\n\n"
            }
          ],
          "value": "\n  *  Update to corrected Firmware.\u00a0\n\n\n\n\nAffected Product\n\nFirst Known in Firmware\n\nCorrected in Firmware\n\nControlLogix\u00ae 5570\n\n20.011\n\nv33.016, 34.013, 35.012, 36.011 and later\n\nGuardLogix\u00ae 5570\n\n20.011\n\nv33.016, 34.013, 35.012, 36.011 and later\n\nControlLogix\u00ae 5570 redundant\n\n20.054_kit1\n\nv33.053_kit1, 34.052_kit1, 35.052_kit1, 36.051_kit1 and late\n\n\n\n\n\n\n"
        }
      ],
      "source": {
        "discovery": "UNKNOWN"
      },
      "title": "Rockwell Automation Denial-of-service Vulnerability in ICE1 Controller",
      "x_generator": {
        "engine": "Vulnogram 0.1.0-dev"
      }
    }
  },
  "cveMetadata": {
    "assignerOrgId": "b73dd486-f505-4403-b634-40b078b177f0",
    "assignerShortName": "Rockwell",
    "cveId": "CVE-2024-21916",
    "datePublished": "2024-01-31T18:28:59.715Z",
    "dateReserved": "2024-01-03T16:40:50.367Z",
    "dateUpdated": "2024-08-01T22:35:34.618Z",
    "state": "PUBLISHED"
  },
  "dataType": "CVE_RECORD",
  "dataVersion": "5.1"
}