Search

Find a vulnerability

Search criteria Use this form to refine search results.
Full-text search supports keyword queries with ranking and filtering.
You can combine vendor, product, and sources to narrow results.
Enable “Apply ordering” to sort by date instead of relevance.

    4 vulnerabilities found for DirectLOGIC D0-06 series CPUs by AutomationDirect

    CVE-2022-2004 (GCVE-0-2022-2004)

    Vulnerability from nvd – Published: 2022-08-31 15:59 – Updated: 2025-04-16 16:11
    VLAI
    Title
    AutomationDirect DirectLOGIC with Ethernet Communication Uncontrolled Resource Consumption
    Summary
    AutomationDirect DirectLOGIC is vulnerable to a a specially crafted packet can be sent continuously to the PLC to prevent access from DirectSoft and other devices, causing a denial-of-service condition. This issue affects: AutomationDirect DirectLOGIC D0-06 series CPUs D0-06DD1 versions prior to 2.72; D0-06DD2 versions prior to 2.72; D0-06DR versions prior to 2.72; D0-06DA versions prior to 2.72; D0-06AR versions prior to 2.72; D0-06AA versions prior to 2.72; D0-06DD1-D versions prior to 2.72; D0-06DD2-D versions prior to 2.72; D0-06DR-D versions prior to 2.72;
    SSVC
    Exploitation: none Automatable: yes Technical Impact: partial
    CISA Coordinator (v2.0.3)
    CWE
    • CWE-400 - Uncontrolled Resource Consumption
    Assigner
    References
    Impacted products
    Vendor Product Version
    AutomationDirect DirectLOGIC D0-06 series CPUs Affected: D0-06DD1 , < 2.72 (custom)
    Affected: D0-06DD2 , < 2.72 (custom)
    Affected: D0-06DR , < 2.72 (custom)
    Affected: D0-06DA , < 2.72 (custom)
    Affected: D0-06AR , < 2.72 (custom)
    Affected: D0-06AA , < 2.72 (custom)
    Affected: D0-06DD1-D , < 2.72 (custom)
    Affected: D0-06DD2-D , < 2.72 (custom)
    Affected: D0-06DR-D , < 2.72 (custom)
    Create a notification for this product.
    Date Public
    2022-06-16 00:00
    Credits
    Sam Hanson of Dragos reported this vulnerability to CISA.
    Show details on NVD website

    {
      "containers": {
        "adp": [
          {
            "providerMetadata": {
              "dateUpdated": "2024-08-03T00:24:43.769Z",
              "orgId": "af854a3a-2127-422b-91ae-364da2661108",
              "shortName": "CVE"
            },
            "references": [
              {
                "tags": [
                  "x_refsource_CONFIRM",
                  "x_transferred"
                ],
                "url": "https://www.cisa.gov/uscert/ics/advisories/icsa-22-167-03"
              }
            ],
            "title": "CVE Program Container"
          },
          {
            "metrics": [
              {
                "other": {
                  "content": {
                    "id": "CVE-2022-2004",
                    "options": [
                      {
                        "Exploitation": "none"
                      },
                      {
                        "Automatable": "yes"
                      },
                      {
                        "Technical Impact": "partial"
                      }
                    ],
                    "role": "CISA Coordinator",
                    "timestamp": "2025-04-16T15:54:35.593506Z",
                    "version": "2.0.3"
                  },
                  "type": "ssvc"
                }
              }
            ],
            "providerMetadata": {
              "dateUpdated": "2025-04-16T16:11:14.677Z",
              "orgId": "134c704f-9b21-4f2e-91b3-4a467353bcc0",
              "shortName": "CISA-ADP"
            },
            "title": "CISA ADP Vulnrichment"
          }
        ],
        "cna": {
          "affected": [
            {
              "product": "DirectLOGIC D0-06 series CPUs",
              "vendor": "AutomationDirect",
              "versions": [
                {
                  "lessThan": "2.72",
                  "status": "affected",
                  "version": "D0-06DD1",
                  "versionType": "custom"
                },
                {
                  "lessThan": "2.72",
                  "status": "affected",
                  "version": "D0-06DD2",
                  "versionType": "custom"
                },
                {
                  "lessThan": "2.72",
                  "status": "affected",
                  "version": "D0-06DR",
                  "versionType": "custom"
                },
                {
                  "lessThan": "2.72",
                  "status": "affected",
                  "version": "D0-06DA",
                  "versionType": "custom"
                },
                {
                  "lessThan": "2.72",
                  "status": "affected",
                  "version": "D0-06AR",
                  "versionType": "custom"
                },
                {
                  "lessThan": "2.72",
                  "status": "affected",
                  "version": "D0-06AA",
                  "versionType": "custom"
                },
                {
                  "lessThan": "2.72",
                  "status": "affected",
                  "version": "D0-06DD1-D",
                  "versionType": "custom"
                },
                {
                  "lessThan": "2.72",
                  "status": "affected",
                  "version": "D0-06DD2-D",
                  "versionType": "custom"
                },
                {
                  "lessThan": "2.72",
                  "status": "affected",
                  "version": "D0-06DR-D",
                  "versionType": "custom"
                }
              ]
            }
          ],
          "credits": [
            {
              "lang": "en",
              "value": "Sam Hanson of Dragos reported this vulnerability to CISA."
            }
          ],
          "datePublic": "2022-06-16T00:00:00.000Z",
          "descriptions": [
            {
              "lang": "en",
              "value": "AutomationDirect DirectLOGIC is vulnerable to a a specially crafted packet can be sent continuously to the PLC to prevent access from DirectSoft and other devices, causing a denial-of-service condition. This issue affects: AutomationDirect DirectLOGIC D0-06 series CPUs D0-06DD1 versions prior to 2.72; D0-06DD2 versions prior to 2.72; D0-06DR versions prior to 2.72; D0-06DA versions prior to 2.72; D0-06AR versions prior to 2.72; D0-06AA versions prior to 2.72; D0-06DD1-D versions prior to 2.72; D0-06DD2-D versions prior to 2.72; D0-06DR-D versions prior to 2.72;"
            }
          ],
          "metrics": [
            {
              "cvssV3_1": {
                "attackComplexity": "LOW",
                "attackVector": "NETWORK",
                "availabilityImpact": "HIGH",
                "baseScore": 7.5,
                "baseSeverity": "HIGH",
                "confidentialityImpact": "NONE",
                "integrityImpact": "NONE",
                "privilegesRequired": "NONE",
                "scope": "UNCHANGED",
                "userInteraction": "NONE",
                "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H",
                "version": "3.1"
              }
            }
          ],
          "problemTypes": [
            {
              "descriptions": [
                {
                  "cweId": "CWE-400",
                  "description": "CWE-400 Uncontrolled Resource Consumption",
                  "lang": "en",
                  "type": "CWE"
                }
              ]
            }
          ],
          "providerMetadata": {
            "dateUpdated": "2022-08-31T15:59:33.000Z",
            "orgId": "7d14cffa-0d7d-4270-9dc0-52cabd5a23a6",
            "shortName": "icscert"
          },
          "references": [
            {
              "tags": [
                "x_refsource_CONFIRM"
              ],
              "url": "https://www.cisa.gov/uscert/ics/advisories/icsa-22-167-03"
            }
          ],
          "solutions": [
            {
              "lang": "en",
              "value": "AutomationDirect recommends users upgrade to firmware Version 2.72 or later for all DL06 CPUs for CVE-2022-2002.\n\nAdditional brute force mitigation for password access has also been added. Three incorrect password entries will result in a three hour lock out of password entry. Power cycle will allow subsequent password attempts.\n\nPlease see the security network practices below for CVE-2022-2004.\nWhile automation networks and systems have built-in password protection schemes, this is only one step in securing the affected systems. Automation control system networks must incorporate data protection and security measures at least as robust as a typical business computer system. AutomationDirect recommends users of PLCs, HMI products, and other SCADA system products perform independent network security analysis to determine the proper level of security required for the application.\n\nAutomationDirect has identified the specific mitigation actions listed below:\n\nSecure physical access.\nIsolate and air gap networks when possible.\nConsider some of the AutomationDirect newer PLC families."
            }
          ],
          "source": {
            "discovery": "UNKNOWN"
          },
          "title": "AutomationDirect DirectLOGIC with Ethernet Communication Uncontrolled Resource Consumption",
          "x_generator": {
            "engine": "Vulnogram 0.0.9"
          },
          "x_legacyV4Record": {
            "CVE_data_meta": {
              "ASSIGNER": "ics-cert@hq.dhs.gov",
              "DATE_PUBLIC": "2022-06-16T17:00:00.000Z",
              "ID": "CVE-2022-2004",
              "STATE": "PUBLIC",
              "TITLE": "AutomationDirect DirectLOGIC with Ethernet Communication Uncontrolled Resource Consumption"
            },
            "affects": {
              "vendor": {
                "vendor_data": [
                  {
                    "product": {
                      "product_data": [
                        {
                          "product_name": "DirectLOGIC D0-06 series CPUs",
                          "version": {
                            "version_data": [
                              {
                                "version_affected": "\u003c",
                                "version_name": "D0-06DD1",
                                "version_value": "2.72"
                              },
                              {
                                "version_affected": "\u003c",
                                "version_name": "D0-06DD2",
                                "version_value": "2.72"
                              },
                              {
                                "version_affected": "\u003c",
                                "version_name": "D0-06DR",
                                "version_value": "2.72"
                              },
                              {
                                "version_affected": "\u003c",
                                "version_name": "D0-06DA",
                                "version_value": "2.72"
                              },
                              {
                                "version_affected": "\u003c",
                                "version_name": "D0-06AR",
                                "version_value": "2.72"
                              },
                              {
                                "version_affected": "\u003c",
                                "version_name": "D0-06AA",
                                "version_value": "2.72"
                              },
                              {
                                "version_affected": "\u003c",
                                "version_name": "D0-06DD1-D",
                                "version_value": "2.72"
                              },
                              {
                                "version_affected": "\u003c",
                                "version_name": "D0-06DD2-D",
                                "version_value": "2.72"
                              },
                              {
                                "version_affected": "\u003c",
                                "version_name": "D0-06DR-D",
                                "version_value": "2.72"
                              }
                            ]
                          }
                        }
                      ]
                    },
                    "vendor_name": "AutomationDirect"
                  }
                ]
              }
            },
            "credit": [
              {
                "lang": "eng",
                "value": "Sam Hanson of Dragos reported this vulnerability to CISA."
              }
            ],
            "data_format": "MITRE",
            "data_type": "CVE",
            "data_version": "4.0",
            "description": {
              "description_data": [
                {
                  "lang": "eng",
                  "value": "AutomationDirect DirectLOGIC is vulnerable to a a specially crafted packet can be sent continuously to the PLC to prevent access from DirectSoft and other devices, causing a denial-of-service condition. This issue affects: AutomationDirect DirectLOGIC D0-06 series CPUs D0-06DD1 versions prior to 2.72; D0-06DD2 versions prior to 2.72; D0-06DR versions prior to 2.72; D0-06DA versions prior to 2.72; D0-06AR versions prior to 2.72; D0-06AA versions prior to 2.72; D0-06DD1-D versions prior to 2.72; D0-06DD2-D versions prior to 2.72; D0-06DR-D versions prior to 2.72;"
                }
              ]
            },
            "generator": {
              "engine": "Vulnogram 0.0.9"
            },
            "impact": {
              "cvss": {
                "attackComplexity": "LOW",
                "attackVector": "NETWORK",
                "availabilityImpact": "HIGH",
                "baseScore": 7.5,
                "baseSeverity": "HIGH",
                "confidentialityImpact": "NONE",
                "integrityImpact": "NONE",
                "privilegesRequired": "NONE",
                "scope": "UNCHANGED",
                "userInteraction": "NONE",
                "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H",
                "version": "3.1"
              }
            },
            "problemtype": {
              "problemtype_data": [
                {
                  "description": [
                    {
                      "lang": "eng",
                      "value": "CWE-400 Uncontrolled Resource Consumption"
                    }
                  ]
                }
              ]
            },
            "references": {
              "reference_data": [
                {
                  "name": "https://www.cisa.gov/uscert/ics/advisories/icsa-22-167-03",
                  "refsource": "CONFIRM",
                  "url": "https://www.cisa.gov/uscert/ics/advisories/icsa-22-167-03"
                }
              ]
            },
            "solution": [
              {
                "lang": "en",
                "value": "AutomationDirect recommends users upgrade to firmware Version 2.72 or later for all DL06 CPUs for CVE-2022-2002.\n\nAdditional brute force mitigation for password access has also been added. Three incorrect password entries will result in a three hour lock out of password entry. Power cycle will allow subsequent password attempts.\n\nPlease see the security network practices below for CVE-2022-2004.\nWhile automation networks and systems have built-in password protection schemes, this is only one step in securing the affected systems. Automation control system networks must incorporate data protection and security measures at least as robust as a typical business computer system. AutomationDirect recommends users of PLCs, HMI products, and other SCADA system products perform independent network security analysis to determine the proper level of security required for the application.\n\nAutomationDirect has identified the specific mitigation actions listed below:\n\nSecure physical access.\nIsolate and air gap networks when possible.\nConsider some of the AutomationDirect newer PLC families."
              }
            ],
            "source": {
              "discovery": "UNKNOWN"
            }
          }
        }
      },
      "cveMetadata": {
        "assignerOrgId": "7d14cffa-0d7d-4270-9dc0-52cabd5a23a6",
        "assignerShortName": "icscert",
        "cveId": "CVE-2022-2004",
        "datePublished": "2022-08-31T15:59:33.591Z",
        "dateReserved": "2022-06-06T00:00:00.000Z",
        "dateUpdated": "2025-04-16T16:11:14.677Z",
        "state": "PUBLISHED"
      },
      "dataType": "CVE_RECORD",
      "dataVersion": "5.1"
    }

    CVE-2022-2003 (GCVE-0-2022-2003)

    Vulnerability from nvd – Published: 2022-08-31 15:59 – Updated: 2025-04-16 17:49
    VLAI
    Title
    AutomationDirect DirectLOGIC with Serial Communication Cleartext Transmission
    Summary
    AutomationDirect DirectLOGIC is vulnerable to a specifically crafted serial message to the CPU serial port that will cause the PLC to respond with the PLC password in cleartext. This could allow an attacker to access and make unauthorized changes. This issue affects: AutomationDirect DirectLOGIC D0-06 series CPUs D0-06DD1 versions prior to 2.72; D0-06DD2 versions prior to 2.72; D0-06DR versions prior to 2.72; D0-06DA versions prior to 2.72; D0-06AR versions prior to 2.72; D0-06AA versions prior to 2.72; D0-06DD1-D versions prior to 2.72; D0-06DD2-D versions prior to 2.72; D0-06DR-D versions prior to 2.72;
    SSVC
    Exploitation: none Automatable: no Technical Impact: total
    CISA Coordinator (v2.0.3)
    CWE
    • CWE-319 - Cleartext Transmission of Sensitive Information
    Assigner
    References
    Impacted products
    Vendor Product Version
    AutomationDirect DirectLOGIC D0-06 series CPUs Affected: D0-06DD1 , < 2.72 (custom)
    Affected: D0-06DD2 , < 2.72 (custom)
    Affected: D0-06DR , < 2.72 (custom)
    Affected: D0-06DA , < 2.72 (custom)
    Affected: D0-06AR , < 2.72 (custom)
    Affected: D0-06AA , < 2.72 (custom)
    Affected: D0-06DD1-D , < 2.72 (custom)
    Affected: D0-06DD2-D , < 2.72 (custom)
    Affected: D0-06DR-D , < 2.72 (custom)
    Create a notification for this product.
    Date Public
    2022-06-16 00:00
    Credits
    Sam Hanson of Dragos reported this vulnerability to CISA.
    Show details on NVD website

    {
      "containers": {
        "adp": [
          {
            "providerMetadata": {
              "dateUpdated": "2024-08-03T00:24:44.055Z",
              "orgId": "af854a3a-2127-422b-91ae-364da2661108",
              "shortName": "CVE"
            },
            "references": [
              {
                "tags": [
                  "x_refsource_CONFIRM",
                  "x_transferred"
                ],
                "url": "https://www.cisa.gov/uscert/ics/advisories/icsa-22-167-02"
              },
              {
                "tags": [
                  "x_refsource_CONFIRM",
                  "x_transferred"
                ],
                "url": "https://www.cisa.gov/uscert/ics/advisories/icsa-22-167-03"
              }
            ],
            "title": "CVE Program Container"
          },
          {
            "metrics": [
              {
                "other": {
                  "content": {
                    "id": "CVE-2022-2003",
                    "options": [
                      {
                        "Exploitation": "none"
                      },
                      {
                        "Automatable": "no"
                      },
                      {
                        "Technical Impact": "total"
                      }
                    ],
                    "role": "CISA Coordinator",
                    "timestamp": "2025-04-16T17:27:42.525536Z",
                    "version": "2.0.3"
                  },
                  "type": "ssvc"
                }
              }
            ],
            "providerMetadata": {
              "dateUpdated": "2025-04-16T17:49:17.171Z",
              "orgId": "134c704f-9b21-4f2e-91b3-4a467353bcc0",
              "shortName": "CISA-ADP"
            },
            "title": "CISA ADP Vulnrichment"
          }
        ],
        "cna": {
          "affected": [
            {
              "product": "DirectLOGIC D0-06 series CPUs",
              "vendor": "AutomationDirect",
              "versions": [
                {
                  "lessThan": "2.72",
                  "status": "affected",
                  "version": "D0-06DD1",
                  "versionType": "custom"
                },
                {
                  "lessThan": "2.72",
                  "status": "affected",
                  "version": "D0-06DD2",
                  "versionType": "custom"
                },
                {
                  "lessThan": "2.72",
                  "status": "affected",
                  "version": "D0-06DR",
                  "versionType": "custom"
                },
                {
                  "lessThan": "2.72",
                  "status": "affected",
                  "version": "D0-06DA",
                  "versionType": "custom"
                },
                {
                  "lessThan": "2.72",
                  "status": "affected",
                  "version": "D0-06AR",
                  "versionType": "custom"
                },
                {
                  "lessThan": "2.72",
                  "status": "affected",
                  "version": "D0-06AA",
                  "versionType": "custom"
                },
                {
                  "lessThan": "2.72",
                  "status": "affected",
                  "version": "D0-06DD1-D",
                  "versionType": "custom"
                },
                {
                  "lessThan": "2.72",
                  "status": "affected",
                  "version": "D0-06DD2-D",
                  "versionType": "custom"
                },
                {
                  "lessThan": "2.72",
                  "status": "affected",
                  "version": "D0-06DR-D",
                  "versionType": "custom"
                }
              ]
            }
          ],
          "credits": [
            {
              "lang": "en",
              "value": "Sam Hanson of Dragos reported this vulnerability to CISA."
            }
          ],
          "datePublic": "2022-06-16T00:00:00.000Z",
          "descriptions": [
            {
              "lang": "en",
              "value": "AutomationDirect DirectLOGIC is vulnerable to a specifically crafted serial message to the CPU serial port that will cause the PLC to respond with the PLC password in cleartext. This could allow an attacker to access and make unauthorized changes. This issue affects: AutomationDirect DirectLOGIC D0-06 series CPUs D0-06DD1 versions prior to 2.72; D0-06DD2 versions prior to 2.72; D0-06DR versions prior to 2.72; D0-06DA versions prior to 2.72; D0-06AR versions prior to 2.72; D0-06AA versions prior to 2.72; D0-06DD1-D versions prior to 2.72; D0-06DD2-D versions prior to 2.72; D0-06DR-D versions prior to 2.72;"
            }
          ],
          "metrics": [
            {
              "cvssV3_1": {
                "attackComplexity": "LOW",
                "attackVector": "LOCAL",
                "availabilityImpact": "NONE",
                "baseScore": 7.7,
                "baseSeverity": "HIGH",
                "confidentialityImpact": "HIGH",
                "integrityImpact": "HIGH",
                "privilegesRequired": "NONE",
                "scope": "UNCHANGED",
                "userInteraction": "NONE",
                "vectorString": "CVSS:3.1/AV:L/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:N",
                "version": "3.1"
              }
            }
          ],
          "problemTypes": [
            {
              "descriptions": [
                {
                  "cweId": "CWE-319",
                  "description": "CWE-319 Cleartext Transmission of Sensitive Information",
                  "lang": "en",
                  "type": "CWE"
                }
              ]
            }
          ],
          "providerMetadata": {
            "dateUpdated": "2022-08-31T15:59:33.000Z",
            "orgId": "7d14cffa-0d7d-4270-9dc0-52cabd5a23a6",
            "shortName": "icscert"
          },
          "references": [
            {
              "tags": [
                "x_refsource_CONFIRM"
              ],
              "url": "https://www.cisa.gov/uscert/ics/advisories/icsa-22-167-02"
            },
            {
              "tags": [
                "x_refsource_CONFIRM"
              ],
              "url": "https://www.cisa.gov/uscert/ics/advisories/icsa-22-167-03"
            }
          ],
          "solutions": [
            {
              "lang": "en",
              "value": "AutomationDirect recommends users upgrade to firmware Version 2.72 or later, which will no longer respond with the password when requested with the specially crafted message.\n\nAdditional mitigation for brute force password access has also been added. Three incorrect password entries will result in a 3-hour lock out of password entry. Power cycle will allow subsequent password attempts.\n\nWhile automation networks and systems have built-in password protection schemes, this is only one step in securing the affected systems. Automation control system networks must incorporate data protection and security measures at least as robust as a typical business computer system. AutomationDirect recommends users of PLCs, HMI products, and other SCADA system products perform independent network security analysis to determine the proper level of security required for the application.\n\nAutomationDirect has identified the specific mitigation actions listed below:\n\nSecure physical access.\nIsolate and air gap networks when possible.\nConsider some of the AutomationDirect newer PLC families."
            }
          ],
          "source": {
            "discovery": "UNKNOWN"
          },
          "title": "AutomationDirect DirectLOGIC with Serial Communication Cleartext Transmission",
          "x_generator": {
            "engine": "Vulnogram 0.0.9"
          },
          "x_legacyV4Record": {
            "CVE_data_meta": {
              "ASSIGNER": "ics-cert@hq.dhs.gov",
              "DATE_PUBLIC": "2022-06-16T17:00:00.000Z",
              "ID": "CVE-2022-2003",
              "STATE": "PUBLIC",
              "TITLE": "AutomationDirect DirectLOGIC with Serial Communication Cleartext Transmission"
            },
            "affects": {
              "vendor": {
                "vendor_data": [
                  {
                    "product": {
                      "product_data": [
                        {
                          "product_name": "DirectLOGIC D0-06 series CPUs",
                          "version": {
                            "version_data": [
                              {
                                "version_affected": "\u003c",
                                "version_name": "D0-06DD1",
                                "version_value": "2.72"
                              },
                              {
                                "version_affected": "\u003c",
                                "version_name": "D0-06DD2",
                                "version_value": "2.72"
                              },
                              {
                                "version_affected": "\u003c",
                                "version_name": "D0-06DR",
                                "version_value": "2.72"
                              },
                              {
                                "version_affected": "\u003c",
                                "version_name": "D0-06DA",
                                "version_value": "2.72"
                              },
                              {
                                "version_affected": "\u003c",
                                "version_name": "D0-06AR",
                                "version_value": "2.72"
                              },
                              {
                                "version_affected": "\u003c",
                                "version_name": "D0-06AA",
                                "version_value": "2.72"
                              },
                              {
                                "version_affected": "\u003c",
                                "version_name": "D0-06DD1-D",
                                "version_value": "2.72"
                              },
                              {
                                "version_affected": "\u003c",
                                "version_name": "D0-06DD2-D",
                                "version_value": "2.72"
                              },
                              {
                                "version_affected": "\u003c",
                                "version_name": "D0-06DR-D",
                                "version_value": "2.72"
                              }
                            ]
                          }
                        }
                      ]
                    },
                    "vendor_name": "AutomationDirect"
                  }
                ]
              }
            },
            "credit": [
              {
                "lang": "eng",
                "value": "Sam Hanson of Dragos reported this vulnerability to CISA."
              }
            ],
            "data_format": "MITRE",
            "data_type": "CVE",
            "data_version": "4.0",
            "description": {
              "description_data": [
                {
                  "lang": "eng",
                  "value": "AutomationDirect DirectLOGIC is vulnerable to a specifically crafted serial message to the CPU serial port that will cause the PLC to respond with the PLC password in cleartext. This could allow an attacker to access and make unauthorized changes. This issue affects: AutomationDirect DirectLOGIC D0-06 series CPUs D0-06DD1 versions prior to 2.72; D0-06DD2 versions prior to 2.72; D0-06DR versions prior to 2.72; D0-06DA versions prior to 2.72; D0-06AR versions prior to 2.72; D0-06AA versions prior to 2.72; D0-06DD1-D versions prior to 2.72; D0-06DD2-D versions prior to 2.72; D0-06DR-D versions prior to 2.72;"
                }
              ]
            },
            "generator": {
              "engine": "Vulnogram 0.0.9"
            },
            "impact": {
              "cvss": {
                "attackComplexity": "LOW",
                "attackVector": "LOCAL",
                "availabilityImpact": "NONE",
                "baseScore": 7.7,
                "baseSeverity": "HIGH",
                "confidentialityImpact": "HIGH",
                "integrityImpact": "HIGH",
                "privilegesRequired": "NONE",
                "scope": "UNCHANGED",
                "userInteraction": "NONE",
                "vectorString": "CVSS:3.1/AV:L/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:N",
                "version": "3.1"
              }
            },
            "problemtype": {
              "problemtype_data": [
                {
                  "description": [
                    {
                      "lang": "eng",
                      "value": "CWE-319 Cleartext Transmission of Sensitive Information"
                    }
                  ]
                }
              ]
            },
            "references": {
              "reference_data": [
                {
                  "name": "https://www.cisa.gov/uscert/ics/advisories/icsa-22-167-02",
                  "refsource": "CONFIRM",
                  "url": "https://www.cisa.gov/uscert/ics/advisories/icsa-22-167-02"
                },
                {
                  "name": "https://www.cisa.gov/uscert/ics/advisories/icsa-22-167-03",
                  "refsource": "CONFIRM",
                  "url": "https://www.cisa.gov/uscert/ics/advisories/icsa-22-167-03"
                }
              ]
            },
            "solution": [
              {
                "lang": "en",
                "value": "AutomationDirect recommends users upgrade to firmware Version 2.72 or later, which will no longer respond with the password when requested with the specially crafted message.\n\nAdditional mitigation for brute force password access has also been added. Three incorrect password entries will result in a 3-hour lock out of password entry. Power cycle will allow subsequent password attempts.\n\nWhile automation networks and systems have built-in password protection schemes, this is only one step in securing the affected systems. Automation control system networks must incorporate data protection and security measures at least as robust as a typical business computer system. AutomationDirect recommends users of PLCs, HMI products, and other SCADA system products perform independent network security analysis to determine the proper level of security required for the application.\n\nAutomationDirect has identified the specific mitigation actions listed below:\n\nSecure physical access.\nIsolate and air gap networks when possible.\nConsider some of the AutomationDirect newer PLC families."
              }
            ],
            "source": {
              "discovery": "UNKNOWN"
            }
          }
        }
      },
      "cveMetadata": {
        "assignerOrgId": "7d14cffa-0d7d-4270-9dc0-52cabd5a23a6",
        "assignerShortName": "icscert",
        "cveId": "CVE-2022-2003",
        "datePublished": "2022-08-31T15:59:33.369Z",
        "dateReserved": "2022-06-06T00:00:00.000Z",
        "dateUpdated": "2025-04-16T17:49:17.171Z",
        "state": "PUBLISHED"
      },
      "dataType": "CVE_RECORD",
      "dataVersion": "5.1"
    }

    CVE-2022-2004 (GCVE-0-2022-2004)

    Vulnerability from cvelistv5 – Published: 2022-08-31 15:59 – Updated: 2025-04-16 16:11
    VLAI
    Title
    AutomationDirect DirectLOGIC with Ethernet Communication Uncontrolled Resource Consumption
    Summary
    AutomationDirect DirectLOGIC is vulnerable to a a specially crafted packet can be sent continuously to the PLC to prevent access from DirectSoft and other devices, causing a denial-of-service condition. This issue affects: AutomationDirect DirectLOGIC D0-06 series CPUs D0-06DD1 versions prior to 2.72; D0-06DD2 versions prior to 2.72; D0-06DR versions prior to 2.72; D0-06DA versions prior to 2.72; D0-06AR versions prior to 2.72; D0-06AA versions prior to 2.72; D0-06DD1-D versions prior to 2.72; D0-06DD2-D versions prior to 2.72; D0-06DR-D versions prior to 2.72;
    SSVC
    Exploitation: none Automatable: yes Technical Impact: partial
    CISA Coordinator (v2.0.3)
    CWE
    • CWE-400 - Uncontrolled Resource Consumption
    Assigner
    References
    Impacted products
    Vendor Product Version
    AutomationDirect DirectLOGIC D0-06 series CPUs Affected: D0-06DD1 , < 2.72 (custom)
    Affected: D0-06DD2 , < 2.72 (custom)
    Affected: D0-06DR , < 2.72 (custom)
    Affected: D0-06DA , < 2.72 (custom)
    Affected: D0-06AR , < 2.72 (custom)
    Affected: D0-06AA , < 2.72 (custom)
    Affected: D0-06DD1-D , < 2.72 (custom)
    Affected: D0-06DD2-D , < 2.72 (custom)
    Affected: D0-06DR-D , < 2.72 (custom)
    Create a notification for this product.
    Date Public
    2022-06-16 00:00
    Credits
    Sam Hanson of Dragos reported this vulnerability to CISA.
    Show details on NVD website

    {
      "containers": {
        "adp": [
          {
            "providerMetadata": {
              "dateUpdated": "2024-08-03T00:24:43.769Z",
              "orgId": "af854a3a-2127-422b-91ae-364da2661108",
              "shortName": "CVE"
            },
            "references": [
              {
                "tags": [
                  "x_refsource_CONFIRM",
                  "x_transferred"
                ],
                "url": "https://www.cisa.gov/uscert/ics/advisories/icsa-22-167-03"
              }
            ],
            "title": "CVE Program Container"
          },
          {
            "metrics": [
              {
                "other": {
                  "content": {
                    "id": "CVE-2022-2004",
                    "options": [
                      {
                        "Exploitation": "none"
                      },
                      {
                        "Automatable": "yes"
                      },
                      {
                        "Technical Impact": "partial"
                      }
                    ],
                    "role": "CISA Coordinator",
                    "timestamp": "2025-04-16T15:54:35.593506Z",
                    "version": "2.0.3"
                  },
                  "type": "ssvc"
                }
              }
            ],
            "providerMetadata": {
              "dateUpdated": "2025-04-16T16:11:14.677Z",
              "orgId": "134c704f-9b21-4f2e-91b3-4a467353bcc0",
              "shortName": "CISA-ADP"
            },
            "title": "CISA ADP Vulnrichment"
          }
        ],
        "cna": {
          "affected": [
            {
              "product": "DirectLOGIC D0-06 series CPUs",
              "vendor": "AutomationDirect",
              "versions": [
                {
                  "lessThan": "2.72",
                  "status": "affected",
                  "version": "D0-06DD1",
                  "versionType": "custom"
                },
                {
                  "lessThan": "2.72",
                  "status": "affected",
                  "version": "D0-06DD2",
                  "versionType": "custom"
                },
                {
                  "lessThan": "2.72",
                  "status": "affected",
                  "version": "D0-06DR",
                  "versionType": "custom"
                },
                {
                  "lessThan": "2.72",
                  "status": "affected",
                  "version": "D0-06DA",
                  "versionType": "custom"
                },
                {
                  "lessThan": "2.72",
                  "status": "affected",
                  "version": "D0-06AR",
                  "versionType": "custom"
                },
                {
                  "lessThan": "2.72",
                  "status": "affected",
                  "version": "D0-06AA",
                  "versionType": "custom"
                },
                {
                  "lessThan": "2.72",
                  "status": "affected",
                  "version": "D0-06DD1-D",
                  "versionType": "custom"
                },
                {
                  "lessThan": "2.72",
                  "status": "affected",
                  "version": "D0-06DD2-D",
                  "versionType": "custom"
                },
                {
                  "lessThan": "2.72",
                  "status": "affected",
                  "version": "D0-06DR-D",
                  "versionType": "custom"
                }
              ]
            }
          ],
          "credits": [
            {
              "lang": "en",
              "value": "Sam Hanson of Dragos reported this vulnerability to CISA."
            }
          ],
          "datePublic": "2022-06-16T00:00:00.000Z",
          "descriptions": [
            {
              "lang": "en",
              "value": "AutomationDirect DirectLOGIC is vulnerable to a a specially crafted packet can be sent continuously to the PLC to prevent access from DirectSoft and other devices, causing a denial-of-service condition. This issue affects: AutomationDirect DirectLOGIC D0-06 series CPUs D0-06DD1 versions prior to 2.72; D0-06DD2 versions prior to 2.72; D0-06DR versions prior to 2.72; D0-06DA versions prior to 2.72; D0-06AR versions prior to 2.72; D0-06AA versions prior to 2.72; D0-06DD1-D versions prior to 2.72; D0-06DD2-D versions prior to 2.72; D0-06DR-D versions prior to 2.72;"
            }
          ],
          "metrics": [
            {
              "cvssV3_1": {
                "attackComplexity": "LOW",
                "attackVector": "NETWORK",
                "availabilityImpact": "HIGH",
                "baseScore": 7.5,
                "baseSeverity": "HIGH",
                "confidentialityImpact": "NONE",
                "integrityImpact": "NONE",
                "privilegesRequired": "NONE",
                "scope": "UNCHANGED",
                "userInteraction": "NONE",
                "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H",
                "version": "3.1"
              }
            }
          ],
          "problemTypes": [
            {
              "descriptions": [
                {
                  "cweId": "CWE-400",
                  "description": "CWE-400 Uncontrolled Resource Consumption",
                  "lang": "en",
                  "type": "CWE"
                }
              ]
            }
          ],
          "providerMetadata": {
            "dateUpdated": "2022-08-31T15:59:33.000Z",
            "orgId": "7d14cffa-0d7d-4270-9dc0-52cabd5a23a6",
            "shortName": "icscert"
          },
          "references": [
            {
              "tags": [
                "x_refsource_CONFIRM"
              ],
              "url": "https://www.cisa.gov/uscert/ics/advisories/icsa-22-167-03"
            }
          ],
          "solutions": [
            {
              "lang": "en",
              "value": "AutomationDirect recommends users upgrade to firmware Version 2.72 or later for all DL06 CPUs for CVE-2022-2002.\n\nAdditional brute force mitigation for password access has also been added. Three incorrect password entries will result in a three hour lock out of password entry. Power cycle will allow subsequent password attempts.\n\nPlease see the security network practices below for CVE-2022-2004.\nWhile automation networks and systems have built-in password protection schemes, this is only one step in securing the affected systems. Automation control system networks must incorporate data protection and security measures at least as robust as a typical business computer system. AutomationDirect recommends users of PLCs, HMI products, and other SCADA system products perform independent network security analysis to determine the proper level of security required for the application.\n\nAutomationDirect has identified the specific mitigation actions listed below:\n\nSecure physical access.\nIsolate and air gap networks when possible.\nConsider some of the AutomationDirect newer PLC families."
            }
          ],
          "source": {
            "discovery": "UNKNOWN"
          },
          "title": "AutomationDirect DirectLOGIC with Ethernet Communication Uncontrolled Resource Consumption",
          "x_generator": {
            "engine": "Vulnogram 0.0.9"
          },
          "x_legacyV4Record": {
            "CVE_data_meta": {
              "ASSIGNER": "ics-cert@hq.dhs.gov",
              "DATE_PUBLIC": "2022-06-16T17:00:00.000Z",
              "ID": "CVE-2022-2004",
              "STATE": "PUBLIC",
              "TITLE": "AutomationDirect DirectLOGIC with Ethernet Communication Uncontrolled Resource Consumption"
            },
            "affects": {
              "vendor": {
                "vendor_data": [
                  {
                    "product": {
                      "product_data": [
                        {
                          "product_name": "DirectLOGIC D0-06 series CPUs",
                          "version": {
                            "version_data": [
                              {
                                "version_affected": "\u003c",
                                "version_name": "D0-06DD1",
                                "version_value": "2.72"
                              },
                              {
                                "version_affected": "\u003c",
                                "version_name": "D0-06DD2",
                                "version_value": "2.72"
                              },
                              {
                                "version_affected": "\u003c",
                                "version_name": "D0-06DR",
                                "version_value": "2.72"
                              },
                              {
                                "version_affected": "\u003c",
                                "version_name": "D0-06DA",
                                "version_value": "2.72"
                              },
                              {
                                "version_affected": "\u003c",
                                "version_name": "D0-06AR",
                                "version_value": "2.72"
                              },
                              {
                                "version_affected": "\u003c",
                                "version_name": "D0-06AA",
                                "version_value": "2.72"
                              },
                              {
                                "version_affected": "\u003c",
                                "version_name": "D0-06DD1-D",
                                "version_value": "2.72"
                              },
                              {
                                "version_affected": "\u003c",
                                "version_name": "D0-06DD2-D",
                                "version_value": "2.72"
                              },
                              {
                                "version_affected": "\u003c",
                                "version_name": "D0-06DR-D",
                                "version_value": "2.72"
                              }
                            ]
                          }
                        }
                      ]
                    },
                    "vendor_name": "AutomationDirect"
                  }
                ]
              }
            },
            "credit": [
              {
                "lang": "eng",
                "value": "Sam Hanson of Dragos reported this vulnerability to CISA."
              }
            ],
            "data_format": "MITRE",
            "data_type": "CVE",
            "data_version": "4.0",
            "description": {
              "description_data": [
                {
                  "lang": "eng",
                  "value": "AutomationDirect DirectLOGIC is vulnerable to a a specially crafted packet can be sent continuously to the PLC to prevent access from DirectSoft and other devices, causing a denial-of-service condition. This issue affects: AutomationDirect DirectLOGIC D0-06 series CPUs D0-06DD1 versions prior to 2.72; D0-06DD2 versions prior to 2.72; D0-06DR versions prior to 2.72; D0-06DA versions prior to 2.72; D0-06AR versions prior to 2.72; D0-06AA versions prior to 2.72; D0-06DD1-D versions prior to 2.72; D0-06DD2-D versions prior to 2.72; D0-06DR-D versions prior to 2.72;"
                }
              ]
            },
            "generator": {
              "engine": "Vulnogram 0.0.9"
            },
            "impact": {
              "cvss": {
                "attackComplexity": "LOW",
                "attackVector": "NETWORK",
                "availabilityImpact": "HIGH",
                "baseScore": 7.5,
                "baseSeverity": "HIGH",
                "confidentialityImpact": "NONE",
                "integrityImpact": "NONE",
                "privilegesRequired": "NONE",
                "scope": "UNCHANGED",
                "userInteraction": "NONE",
                "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H",
                "version": "3.1"
              }
            },
            "problemtype": {
              "problemtype_data": [
                {
                  "description": [
                    {
                      "lang": "eng",
                      "value": "CWE-400 Uncontrolled Resource Consumption"
                    }
                  ]
                }
              ]
            },
            "references": {
              "reference_data": [
                {
                  "name": "https://www.cisa.gov/uscert/ics/advisories/icsa-22-167-03",
                  "refsource": "CONFIRM",
                  "url": "https://www.cisa.gov/uscert/ics/advisories/icsa-22-167-03"
                }
              ]
            },
            "solution": [
              {
                "lang": "en",
                "value": "AutomationDirect recommends users upgrade to firmware Version 2.72 or later for all DL06 CPUs for CVE-2022-2002.\n\nAdditional brute force mitigation for password access has also been added. Three incorrect password entries will result in a three hour lock out of password entry. Power cycle will allow subsequent password attempts.\n\nPlease see the security network practices below for CVE-2022-2004.\nWhile automation networks and systems have built-in password protection schemes, this is only one step in securing the affected systems. Automation control system networks must incorporate data protection and security measures at least as robust as a typical business computer system. AutomationDirect recommends users of PLCs, HMI products, and other SCADA system products perform independent network security analysis to determine the proper level of security required for the application.\n\nAutomationDirect has identified the specific mitigation actions listed below:\n\nSecure physical access.\nIsolate and air gap networks when possible.\nConsider some of the AutomationDirect newer PLC families."
              }
            ],
            "source": {
              "discovery": "UNKNOWN"
            }
          }
        }
      },
      "cveMetadata": {
        "assignerOrgId": "7d14cffa-0d7d-4270-9dc0-52cabd5a23a6",
        "assignerShortName": "icscert",
        "cveId": "CVE-2022-2004",
        "datePublished": "2022-08-31T15:59:33.591Z",
        "dateReserved": "2022-06-06T00:00:00.000Z",
        "dateUpdated": "2025-04-16T16:11:14.677Z",
        "state": "PUBLISHED"
      },
      "dataType": "CVE_RECORD",
      "dataVersion": "5.1"
    }

    CVE-2022-2003 (GCVE-0-2022-2003)

    Vulnerability from cvelistv5 – Published: 2022-08-31 15:59 – Updated: 2025-04-16 17:49
    VLAI
    Title
    AutomationDirect DirectLOGIC with Serial Communication Cleartext Transmission
    Summary
    AutomationDirect DirectLOGIC is vulnerable to a specifically crafted serial message to the CPU serial port that will cause the PLC to respond with the PLC password in cleartext. This could allow an attacker to access and make unauthorized changes. This issue affects: AutomationDirect DirectLOGIC D0-06 series CPUs D0-06DD1 versions prior to 2.72; D0-06DD2 versions prior to 2.72; D0-06DR versions prior to 2.72; D0-06DA versions prior to 2.72; D0-06AR versions prior to 2.72; D0-06AA versions prior to 2.72; D0-06DD1-D versions prior to 2.72; D0-06DD2-D versions prior to 2.72; D0-06DR-D versions prior to 2.72;
    SSVC
    Exploitation: none Automatable: no Technical Impact: total
    CISA Coordinator (v2.0.3)
    CWE
    • CWE-319 - Cleartext Transmission of Sensitive Information
    Assigner
    References
    Impacted products
    Vendor Product Version
    AutomationDirect DirectLOGIC D0-06 series CPUs Affected: D0-06DD1 , < 2.72 (custom)
    Affected: D0-06DD2 , < 2.72 (custom)
    Affected: D0-06DR , < 2.72 (custom)
    Affected: D0-06DA , < 2.72 (custom)
    Affected: D0-06AR , < 2.72 (custom)
    Affected: D0-06AA , < 2.72 (custom)
    Affected: D0-06DD1-D , < 2.72 (custom)
    Affected: D0-06DD2-D , < 2.72 (custom)
    Affected: D0-06DR-D , < 2.72 (custom)
    Create a notification for this product.
    Date Public
    2022-06-16 00:00
    Credits
    Sam Hanson of Dragos reported this vulnerability to CISA.
    Show details on NVD website

    {
      "containers": {
        "adp": [
          {
            "providerMetadata": {
              "dateUpdated": "2024-08-03T00:24:44.055Z",
              "orgId": "af854a3a-2127-422b-91ae-364da2661108",
              "shortName": "CVE"
            },
            "references": [
              {
                "tags": [
                  "x_refsource_CONFIRM",
                  "x_transferred"
                ],
                "url": "https://www.cisa.gov/uscert/ics/advisories/icsa-22-167-02"
              },
              {
                "tags": [
                  "x_refsource_CONFIRM",
                  "x_transferred"
                ],
                "url": "https://www.cisa.gov/uscert/ics/advisories/icsa-22-167-03"
              }
            ],
            "title": "CVE Program Container"
          },
          {
            "metrics": [
              {
                "other": {
                  "content": {
                    "id": "CVE-2022-2003",
                    "options": [
                      {
                        "Exploitation": "none"
                      },
                      {
                        "Automatable": "no"
                      },
                      {
                        "Technical Impact": "total"
                      }
                    ],
                    "role": "CISA Coordinator",
                    "timestamp": "2025-04-16T17:27:42.525536Z",
                    "version": "2.0.3"
                  },
                  "type": "ssvc"
                }
              }
            ],
            "providerMetadata": {
              "dateUpdated": "2025-04-16T17:49:17.171Z",
              "orgId": "134c704f-9b21-4f2e-91b3-4a467353bcc0",
              "shortName": "CISA-ADP"
            },
            "title": "CISA ADP Vulnrichment"
          }
        ],
        "cna": {
          "affected": [
            {
              "product": "DirectLOGIC D0-06 series CPUs",
              "vendor": "AutomationDirect",
              "versions": [
                {
                  "lessThan": "2.72",
                  "status": "affected",
                  "version": "D0-06DD1",
                  "versionType": "custom"
                },
                {
                  "lessThan": "2.72",
                  "status": "affected",
                  "version": "D0-06DD2",
                  "versionType": "custom"
                },
                {
                  "lessThan": "2.72",
                  "status": "affected",
                  "version": "D0-06DR",
                  "versionType": "custom"
                },
                {
                  "lessThan": "2.72",
                  "status": "affected",
                  "version": "D0-06DA",
                  "versionType": "custom"
                },
                {
                  "lessThan": "2.72",
                  "status": "affected",
                  "version": "D0-06AR",
                  "versionType": "custom"
                },
                {
                  "lessThan": "2.72",
                  "status": "affected",
                  "version": "D0-06AA",
                  "versionType": "custom"
                },
                {
                  "lessThan": "2.72",
                  "status": "affected",
                  "version": "D0-06DD1-D",
                  "versionType": "custom"
                },
                {
                  "lessThan": "2.72",
                  "status": "affected",
                  "version": "D0-06DD2-D",
                  "versionType": "custom"
                },
                {
                  "lessThan": "2.72",
                  "status": "affected",
                  "version": "D0-06DR-D",
                  "versionType": "custom"
                }
              ]
            }
          ],
          "credits": [
            {
              "lang": "en",
              "value": "Sam Hanson of Dragos reported this vulnerability to CISA."
            }
          ],
          "datePublic": "2022-06-16T00:00:00.000Z",
          "descriptions": [
            {
              "lang": "en",
              "value": "AutomationDirect DirectLOGIC is vulnerable to a specifically crafted serial message to the CPU serial port that will cause the PLC to respond with the PLC password in cleartext. This could allow an attacker to access and make unauthorized changes. This issue affects: AutomationDirect DirectLOGIC D0-06 series CPUs D0-06DD1 versions prior to 2.72; D0-06DD2 versions prior to 2.72; D0-06DR versions prior to 2.72; D0-06DA versions prior to 2.72; D0-06AR versions prior to 2.72; D0-06AA versions prior to 2.72; D0-06DD1-D versions prior to 2.72; D0-06DD2-D versions prior to 2.72; D0-06DR-D versions prior to 2.72;"
            }
          ],
          "metrics": [
            {
              "cvssV3_1": {
                "attackComplexity": "LOW",
                "attackVector": "LOCAL",
                "availabilityImpact": "NONE",
                "baseScore": 7.7,
                "baseSeverity": "HIGH",
                "confidentialityImpact": "HIGH",
                "integrityImpact": "HIGH",
                "privilegesRequired": "NONE",
                "scope": "UNCHANGED",
                "userInteraction": "NONE",
                "vectorString": "CVSS:3.1/AV:L/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:N",
                "version": "3.1"
              }
            }
          ],
          "problemTypes": [
            {
              "descriptions": [
                {
                  "cweId": "CWE-319",
                  "description": "CWE-319 Cleartext Transmission of Sensitive Information",
                  "lang": "en",
                  "type": "CWE"
                }
              ]
            }
          ],
          "providerMetadata": {
            "dateUpdated": "2022-08-31T15:59:33.000Z",
            "orgId": "7d14cffa-0d7d-4270-9dc0-52cabd5a23a6",
            "shortName": "icscert"
          },
          "references": [
            {
              "tags": [
                "x_refsource_CONFIRM"
              ],
              "url": "https://www.cisa.gov/uscert/ics/advisories/icsa-22-167-02"
            },
            {
              "tags": [
                "x_refsource_CONFIRM"
              ],
              "url": "https://www.cisa.gov/uscert/ics/advisories/icsa-22-167-03"
            }
          ],
          "solutions": [
            {
              "lang": "en",
              "value": "AutomationDirect recommends users upgrade to firmware Version 2.72 or later, which will no longer respond with the password when requested with the specially crafted message.\n\nAdditional mitigation for brute force password access has also been added. Three incorrect password entries will result in a 3-hour lock out of password entry. Power cycle will allow subsequent password attempts.\n\nWhile automation networks and systems have built-in password protection schemes, this is only one step in securing the affected systems. Automation control system networks must incorporate data protection and security measures at least as robust as a typical business computer system. AutomationDirect recommends users of PLCs, HMI products, and other SCADA system products perform independent network security analysis to determine the proper level of security required for the application.\n\nAutomationDirect has identified the specific mitigation actions listed below:\n\nSecure physical access.\nIsolate and air gap networks when possible.\nConsider some of the AutomationDirect newer PLC families."
            }
          ],
          "source": {
            "discovery": "UNKNOWN"
          },
          "title": "AutomationDirect DirectLOGIC with Serial Communication Cleartext Transmission",
          "x_generator": {
            "engine": "Vulnogram 0.0.9"
          },
          "x_legacyV4Record": {
            "CVE_data_meta": {
              "ASSIGNER": "ics-cert@hq.dhs.gov",
              "DATE_PUBLIC": "2022-06-16T17:00:00.000Z",
              "ID": "CVE-2022-2003",
              "STATE": "PUBLIC",
              "TITLE": "AutomationDirect DirectLOGIC with Serial Communication Cleartext Transmission"
            },
            "affects": {
              "vendor": {
                "vendor_data": [
                  {
                    "product": {
                      "product_data": [
                        {
                          "product_name": "DirectLOGIC D0-06 series CPUs",
                          "version": {
                            "version_data": [
                              {
                                "version_affected": "\u003c",
                                "version_name": "D0-06DD1",
                                "version_value": "2.72"
                              },
                              {
                                "version_affected": "\u003c",
                                "version_name": "D0-06DD2",
                                "version_value": "2.72"
                              },
                              {
                                "version_affected": "\u003c",
                                "version_name": "D0-06DR",
                                "version_value": "2.72"
                              },
                              {
                                "version_affected": "\u003c",
                                "version_name": "D0-06DA",
                                "version_value": "2.72"
                              },
                              {
                                "version_affected": "\u003c",
                                "version_name": "D0-06AR",
                                "version_value": "2.72"
                              },
                              {
                                "version_affected": "\u003c",
                                "version_name": "D0-06AA",
                                "version_value": "2.72"
                              },
                              {
                                "version_affected": "\u003c",
                                "version_name": "D0-06DD1-D",
                                "version_value": "2.72"
                              },
                              {
                                "version_affected": "\u003c",
                                "version_name": "D0-06DD2-D",
                                "version_value": "2.72"
                              },
                              {
                                "version_affected": "\u003c",
                                "version_name": "D0-06DR-D",
                                "version_value": "2.72"
                              }
                            ]
                          }
                        }
                      ]
                    },
                    "vendor_name": "AutomationDirect"
                  }
                ]
              }
            },
            "credit": [
              {
                "lang": "eng",
                "value": "Sam Hanson of Dragos reported this vulnerability to CISA."
              }
            ],
            "data_format": "MITRE",
            "data_type": "CVE",
            "data_version": "4.0",
            "description": {
              "description_data": [
                {
                  "lang": "eng",
                  "value": "AutomationDirect DirectLOGIC is vulnerable to a specifically crafted serial message to the CPU serial port that will cause the PLC to respond with the PLC password in cleartext. This could allow an attacker to access and make unauthorized changes. This issue affects: AutomationDirect DirectLOGIC D0-06 series CPUs D0-06DD1 versions prior to 2.72; D0-06DD2 versions prior to 2.72; D0-06DR versions prior to 2.72; D0-06DA versions prior to 2.72; D0-06AR versions prior to 2.72; D0-06AA versions prior to 2.72; D0-06DD1-D versions prior to 2.72; D0-06DD2-D versions prior to 2.72; D0-06DR-D versions prior to 2.72;"
                }
              ]
            },
            "generator": {
              "engine": "Vulnogram 0.0.9"
            },
            "impact": {
              "cvss": {
                "attackComplexity": "LOW",
                "attackVector": "LOCAL",
                "availabilityImpact": "NONE",
                "baseScore": 7.7,
                "baseSeverity": "HIGH",
                "confidentialityImpact": "HIGH",
                "integrityImpact": "HIGH",
                "privilegesRequired": "NONE",
                "scope": "UNCHANGED",
                "userInteraction": "NONE",
                "vectorString": "CVSS:3.1/AV:L/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:N",
                "version": "3.1"
              }
            },
            "problemtype": {
              "problemtype_data": [
                {
                  "description": [
                    {
                      "lang": "eng",
                      "value": "CWE-319 Cleartext Transmission of Sensitive Information"
                    }
                  ]
                }
              ]
            },
            "references": {
              "reference_data": [
                {
                  "name": "https://www.cisa.gov/uscert/ics/advisories/icsa-22-167-02",
                  "refsource": "CONFIRM",
                  "url": "https://www.cisa.gov/uscert/ics/advisories/icsa-22-167-02"
                },
                {
                  "name": "https://www.cisa.gov/uscert/ics/advisories/icsa-22-167-03",
                  "refsource": "CONFIRM",
                  "url": "https://www.cisa.gov/uscert/ics/advisories/icsa-22-167-03"
                }
              ]
            },
            "solution": [
              {
                "lang": "en",
                "value": "AutomationDirect recommends users upgrade to firmware Version 2.72 or later, which will no longer respond with the password when requested with the specially crafted message.\n\nAdditional mitigation for brute force password access has also been added. Three incorrect password entries will result in a 3-hour lock out of password entry. Power cycle will allow subsequent password attempts.\n\nWhile automation networks and systems have built-in password protection schemes, this is only one step in securing the affected systems. Automation control system networks must incorporate data protection and security measures at least as robust as a typical business computer system. AutomationDirect recommends users of PLCs, HMI products, and other SCADA system products perform independent network security analysis to determine the proper level of security required for the application.\n\nAutomationDirect has identified the specific mitigation actions listed below:\n\nSecure physical access.\nIsolate and air gap networks when possible.\nConsider some of the AutomationDirect newer PLC families."
              }
            ],
            "source": {
              "discovery": "UNKNOWN"
            }
          }
        }
      },
      "cveMetadata": {
        "assignerOrgId": "7d14cffa-0d7d-4270-9dc0-52cabd5a23a6",
        "assignerShortName": "icscert",
        "cveId": "CVE-2022-2003",
        "datePublished": "2022-08-31T15:59:33.369Z",
        "dateReserved": "2022-06-06T00:00:00.000Z",
        "dateUpdated": "2025-04-16T17:49:17.171Z",
        "state": "PUBLISHED"
      },
      "dataType": "CVE_RECORD",