All the vulnerabilites related to Johnson Controls - Facility Explorer F4-SNC
cve-2023-4486
Vulnerability from cvelistv5
Published
2023-12-07 19:55
Modified
2024-08-02 07:31
Severity ?
EPSS score ?
Summary
Uncontrolled Resource Consumption in Metasys and Facility Explorer
References
Impacted products
{ "containers": { "adp": [ { "providerMetadata": { "dateUpdated": "2024-08-02T07:31:06.240Z", "orgId": "af854a3a-2127-422b-91ae-364da2661108", "shortName": "CVE" }, "references": [ { "tags": [ "x_transferred" ], "url": "https://www.johnsoncontrols.com/cyber-solutions/security-advisories" }, { "tags": [ "x_transferred" ], "url": "https://www.cisa.gov/news-events/ics-advisories/icsa-23-341-03" } ], "title": "CVE Program Container" } ], "cna": { "affected": [ { "defaultStatus": "unaffected", "product": "Metasys NAE55/SNE/SNC", "vendor": "Johnson Controls", "versions": [ { "lessThan": "12.0.4", "status": "affected", "version": "12.0", "versionType": "custom" }, { "lessThan": "11.0.6", "status": "affected", "version": "11.0", "versionType": "custom" } ] }, { "defaultStatus": "unaffected", "product": "Facility Explorer F4-SNC", "vendor": "Johnson Controls", "versions": [ { "lessThan": "12.0.4", "status": "affected", "version": "12.0", "versionType": "custom" }, { "lessThan": "11.0.6", "status": "affected", "version": "11.0", "versionType": "custom" } ] } ], "datePublic": "2023-12-07T19:24:00.000Z", "descriptions": [ { "lang": "en", "supportingMedia": [ { "base64": false, "type": "text/html", "value": "Under certain circumstances, invalid authentication credentials could be sent to the login endpoint of Johnson Controls Metasys NAE55, SNE, and SNC engines prior to \n\nversions 11.0.6 and 12.0.4\n\n and Facility Explorer F4-SNC engines prior to versions 11.0.6 and 12.0.4 to cause denial-of-service.\u003cbr\u003e\u003cbr\u003e" } ], "value": "Under certain circumstances, invalid authentication credentials could be sent to the login endpoint of Johnson Controls Metasys NAE55, SNE, and SNC engines prior to \n\nversions 11.0.6 and 12.0.4\n\n and Facility Explorer F4-SNC engines prior to versions 11.0.6 and 12.0.4 to cause denial-of-service.\n\n" } ], "impacts": [ { "capecId": "CAPEC-114", "descriptions": [ { "lang": "en", "value": "CAPEC-114 Authentication Abuse" } ] } ], "metrics": [ { "cvssV3_1": { "attackComplexity": "LOW", "attackVector": "NETWORK", "availabilityImpact": "HIGH", "baseScore": 7.5, "baseSeverity": "HIGH", "confidentialityImpact": "NONE", "integrityImpact": "NONE", "privilegesRequired": "NONE", "scope": "UNCHANGED", "userInteraction": "NONE", "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H", "version": "3.1" }, "format": "CVSS", "scenarios": [ { "lang": "en", "value": "GENERAL" } ] } ], "problemTypes": [ { "descriptions": [ { "cweId": "CWE-400", "description": "CWE-400 Uncontrolled Resource Consumption", "lang": "en", "type": "CWE" } ] } ], "providerMetadata": { "dateUpdated": "2023-12-19T16:57:41.349Z", "orgId": "7281d04a-a537-43df-bfb4-fa4110af9d01", "shortName": "jci" }, "references": [ { "url": "https://www.johnsoncontrols.com/cyber-solutions/security-advisories" }, { "url": "https://www.cisa.gov/news-events/ics-advisories/icsa-23-341-03" } ], "solutions": [ { "lang": "en", "supportingMedia": [ { "base64": false, "type": "text/html", "value": "Update Metasys NAE55, SNE, and SNC engines to version 12.0.4.\u003cbr\u003e" } ], "value": "Update Metasys NAE55, SNE, and SNC engines to version 12.0.4.\n" }, { "lang": "en", "supportingMedia": [ { "base64": false, "type": "text/html", "value": "Update Metasys NAE55, SNE, and SNC engines to version 11.0.6.\n\n\u003cbr\u003e" } ], "value": "Update Metasys NAE55, SNE, and SNC engines to version 11.0.6.\n\n\n" }, { "lang": "en", "supportingMedia": [ { "base64": false, "type": "text/html", "value": "Update Facility Explorer F4-SNC engine to version 12.0.4.\u003cbr\u003e" } ], "value": "Update Facility Explorer F4-SNC engine to version 12.0.4.\n" }, { "lang": "en", "supportingMedia": [ { "base64": false, "type": "text/html", "value": "\n\n\n\n\u003cspan style=\"background-color: rgb(255, 255, 255);\"\u003eUpdate Facility Explorer F4-SNC engine to version 11.0.6. \u003c/span\u003e\u003cspan style=\"background-color: rgb(255, 255, 255);\"\u003e\u0026nbsp;\u003c/span\u003e\n\n\n\n\u003cbr\u003e" } ], "value": "\n\n\nUpdate Facility Explorer F4-SNC engine to version 11.0.6. \u00a0\n\n\n\n\n" }, { "lang": "en", "supportingMedia": [ { "base64": false, "type": "text/html", "value": "\n\nFor more information, contact your local Johnson Controls office or Authorized Building Control Specialists (ABCS).\n\n\u003cbr\u003e" } ], "value": "\nFor more information, contact your local Johnson Controls office or Authorized Building Control Specialists (ABCS).\n\n\n" } ], "source": { "discovery": "INTERNAL" }, "title": "Uncontrolled Resource Consumption in Metasys and Facility Explorer", "x_generator": { "engine": "Vulnogram 0.1.0-dev" } } }, "cveMetadata": { "assignerOrgId": "7281d04a-a537-43df-bfb4-fa4110af9d01", "assignerShortName": "jci", "cveId": "CVE-2023-4486", "datePublished": "2023-12-07T19:55:39.265Z", "dateReserved": "2023-08-22T19:40:01.192Z", "dateUpdated": "2024-08-02T07:31:06.240Z", "state": "PUBLISHED" }, "dataType": "CVE_RECORD", "dataVersion": "5.1" }