All the vulnerabilites related to Mitsubishi Electric Corporation - GT Designer3 Version1 (GOT2000)
cve-2023-0525
Vulnerability from cvelistv5
Published
2023-08-03 23:42
Modified
2024-10-18 20:11
Summary
Weak Encoding for Password vulnerability in Mitsubishi Electric Corporation GOT2000 Series GT27 model versions 01.49.000 and prior, GT25 model versions 01.49.000 and prior, GT23 model versions 01.49.000 and prior, GT21 model versions 01.49.000 and prior, GOT SIMPLE Series GS25 model versions 01.49.000 and prior, GS21 model versions 01.49.000 and prior, GT Designer3 Version1 (GOT2000) versions 1.295H and prior and GT SoftGOT2000 versions 1.295H and prior allows a remote unauthenticated attacker to obtain plaintext passwords by sniffing packets containing encrypted passwords and decrypting the encrypted passwords, in the case of transferring data with GT Designer3 Version1(GOT2000) and GOT2000 Series or GOT SIMPLE Series with the Data Transfer Security function enabled, or in the case of transferring data by the SoftGOT-GOT link function with GT SoftGOT2000 and GOT2000 series with the Data Transfer Security function enabled.
Show details on NVD website


{
  "containers": {
    "adp": [
      {
        "providerMetadata": {
          "dateUpdated": "2024-08-02T05:17:49.235Z",
          "orgId": "af854a3a-2127-422b-91ae-364da2661108",
          "shortName": "CVE"
        },
        "references": [
          {
            "tags": [
              "x_transferred"
            ],
            "url": "https://www.mitsubishielectric.com/en/psirt/vulnerability/pdf/2023-008_en.pdf"
          },
          {
            "tags": [
              "x_transferred"
            ],
            "url": "https://jvn.jp/vu/JVNVU95285923/index.html"
          },
          {
            "tags": [
              "x_transferred"
            ],
            "url": "https://www.cisa.gov/news-events/ics-advisories/icsa-23-215-02"
          }
        ],
        "title": "CVE Program Container"
      },
      {
        "metrics": [
          {
            "other": {
              "content": {
                "id": "CVE-2023-0525",
                "options": [
                  {
                    "Exploitation": "none"
                  },
                  {
                    "Automatable": "no"
                  },
                  {
                    "Technical Impact": "partial"
                  }
                ],
                "role": "CISA Coordinator",
                "timestamp": "2024-10-18T20:11:02.631860Z",
                "version": "2.0.3"
              },
              "type": "ssvc"
            }
          }
        ],
        "providerMetadata": {
          "dateUpdated": "2024-10-18T20:11:17.005Z",
          "orgId": "134c704f-9b21-4f2e-91b3-4a467353bcc0",
          "shortName": "CISA-ADP"
        },
        "title": "CISA ADP Vulnrichment"
      }
    ],
    "cna": {
      "affected": [
        {
          "defaultStatus": "unaffected",
          "product": "GOT2000 Series GT27 model",
          "vendor": "Mitsubishi Electric Corporation",
          "versions": [
            {
              "status": "affected",
              "version": "01.49.000 and prior"
            }
          ]
        },
        {
          "defaultStatus": "unaffected",
          "product": "GOT2000 Series GT25 model",
          "vendor": "Mitsubishi Electric Corporation",
          "versions": [
            {
              "status": "affected",
              "version": "01.49.000 and prior"
            }
          ]
        },
        {
          "defaultStatus": "unaffected",
          "product": "GOT2000 Series GT23 model",
          "vendor": "Mitsubishi Electric Corporation",
          "versions": [
            {
              "status": "affected",
              "version": "01.49.000 and prior"
            }
          ]
        },
        {
          "defaultStatus": "unaffected",
          "product": "GOT2000 Series GT21 model",
          "vendor": "Mitsubishi Electric Corporation",
          "versions": [
            {
              "status": "affected",
              "version": "01.49.000 and prior"
            }
          ]
        },
        {
          "defaultStatus": "unaffected",
          "product": "GOT SIMPLE Series GS25 model",
          "vendor": "Mitsubishi Electric Corporation",
          "versions": [
            {
              "status": "affected",
              "version": "01.49.000 and prior"
            }
          ]
        },
        {
          "defaultStatus": "unaffected",
          "product": "GOT SIMPLE Series GS21 model",
          "vendor": "Mitsubishi Electric Corporation",
          "versions": [
            {
              "status": "affected",
              "version": "01.49.000 and prior"
            }
          ]
        },
        {
          "defaultStatus": "unaffected",
          "product": "GT Designer3 Version1 (GOT2000)",
          "vendor": "Mitsubishi Electric Corporation",
          "versions": [
            {
              "status": "affected",
              "version": "1.295H and prior"
            }
          ]
        },
        {
          "defaultStatus": "unaffected",
          "product": "GT SoftGOT2000",
          "vendor": "Mitsubishi Electric Corporation",
          "versions": [
            {
              "status": "affected",
              "version": "1.295H and prior"
            }
          ]
        }
      ],
      "datePublic": "2023-08-03T03:00:00.000Z",
      "descriptions": [
        {
          "lang": "en",
          "supportingMedia": [
            {
              "base64": false,
              "type": "text/html",
              "value": "Weak Encoding for Password vulnerability in Mitsubishi Electric Corporation GOT2000 Series GT27 model versions 01.49.000 and prior, GT25 model versions 01.49.000 and prior, GT23 model versions 01.49.000 and prior, GT21 model versions 01.49.000 and prior, GOT SIMPLE Series GS25 model versions 01.49.000 and prior, GS21 model versions 01.49.000 and prior, GT Designer3 Version1 (GOT2000) versions 1.295H and prior and GT SoftGOT2000 versions 1.295H and prior allows a remote unauthenticated attacker to obtain plaintext passwords by sniffing packets containing encrypted passwords and decrypting the encrypted passwords, in the case of transferring data with GT Designer3 Version1(GOT2000) and GOT2000 Series or GOT SIMPLE Series with the Data Transfer Security function enabled, or in the case of transferring data by the SoftGOT-GOT link function with GT SoftGOT2000 and GOT2000 series with the Data Transfer Security function enabled."
            }
          ],
          "value": "Weak Encoding for Password vulnerability in Mitsubishi Electric Corporation GOT2000 Series GT27 model versions 01.49.000 and prior, GT25 model versions 01.49.000 and prior, GT23 model versions 01.49.000 and prior, GT21 model versions 01.49.000 and prior, GOT SIMPLE Series GS25 model versions 01.49.000 and prior, GS21 model versions 01.49.000 and prior, GT Designer3 Version1 (GOT2000) versions 1.295H and prior and GT SoftGOT2000 versions 1.295H and prior allows a remote unauthenticated attacker to obtain plaintext passwords by sniffing packets containing encrypted passwords and decrypting the encrypted passwords, in the case of transferring data with GT Designer3 Version1(GOT2000) and GOT2000 Series or GOT SIMPLE Series with the Data Transfer Security function enabled, or in the case of transferring data by the SoftGOT-GOT link function with GT SoftGOT2000 and GOT2000 series with the Data Transfer Security function enabled."
        }
      ],
      "metrics": [
        {
          "cvssV3_1": {
            "attackComplexity": "LOW",
            "attackVector": "NETWORK",
            "availabilityImpact": "NONE",
            "baseScore": 7.5,
            "baseSeverity": "HIGH",
            "confidentialityImpact": "HIGH",
            "integrityImpact": "NONE",
            "privilegesRequired": "NONE",
            "scope": "UNCHANGED",
            "userInteraction": "NONE",
            "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N",
            "version": "3.1"
          },
          "format": "CVSS",
          "scenarios": [
            {
              "lang": "en",
              "value": "GENERAL"
            }
          ]
        }
      ],
      "problemTypes": [
        {
          "descriptions": [
            {
              "cweId": "CWE-261",
              "description": "CWE-261 Weak Encoding for Password",
              "lang": "en",
              "type": "CWE"
            }
          ]
        }
      ],
      "providerMetadata": {
        "dateUpdated": "2023-08-03T23:42:43.290Z",
        "orgId": "e0f77b61-78fd-4786-b3fb-1ee347a748ad",
        "shortName": "Mitsubishi"
      },
      "references": [
        {
          "url": "https://www.mitsubishielectric.com/en/psirt/vulnerability/pdf/2023-008_en.pdf"
        },
        {
          "url": "https://jvn.jp/vu/JVNVU95285923/index.html"
        },
        {
          "url": "https://www.cisa.gov/news-events/ics-advisories/icsa-23-215-02"
        }
      ],
      "source": {
        "discovery": "UNKNOWN"
      },
      "x_generator": {
        "engine": "Vulnogram 0.1.0-dev"
      }
    }
  },
  "cveMetadata": {
    "assignerOrgId": "e0f77b61-78fd-4786-b3fb-1ee347a748ad",
    "assignerShortName": "Mitsubishi",
    "cveId": "CVE-2023-0525",
    "datePublished": "2023-08-03T23:42:43.290Z",
    "dateReserved": "2023-01-27T05:27:17.859Z",
    "dateUpdated": "2024-10-18T20:11:17.005Z",
    "state": "PUBLISHED"
  },
  "dataType": "CVE_RECORD",
  "dataVersion": "5.1"
}

cve-2022-29829
Vulnerability from cvelistv5
Published
2022-11-24 23:23
Modified
2024-08-03 06:33
Summary
Use of Hard-coded Cryptographic Key vulnerability in Mitsubishi Electric GX Works3 versions from 1.000A to 1.090U, GT Designer3 Version1 (GOT2000) versions from 1.122C to 1.290C and Motion Control Setting(GX Works3 related software) versions from 1.035M to 1.042U allows a remote unauthenticated attacker to disclose sensitive information. As a result, unauthenticated users may view programs and project files or execute programs illegally.
Show details on NVD website


{
  "containers": {
    "adp": [
      {
        "providerMetadata": {
          "dateUpdated": "2024-08-03T06:33:42.868Z",
          "orgId": "af854a3a-2127-422b-91ae-364da2661108",
          "shortName": "CVE"
        },
        "references": [
          {
            "tags": [
              "vendor-advisory",
              "x_transferred"
            ],
            "url": "https://www.mitsubishielectric.com/en/psirt/vulnerability/pdf/2022-015_en.pdf"
          },
          {
            "tags": [
              "government-resource",
              "x_transferred"
            ],
            "url": "https://jvn.jp/vu/JVNVU97244961/index.html"
          },
          {
            "tags": [
              "government-resource",
              "x_transferred"
            ],
            "url": "https://www.cisa.gov/uscert/ics/advisories/icsa-22-333-05"
          }
        ],
        "title": "CVE Program Container"
      }
    ],
    "cna": {
      "affected": [
        {
          "defaultStatus": "unaffected",
          "product": "GX Works3",
          "vendor": "Mitsubishi Electric Corporation",
          "versions": [
            {
              "status": "affected",
              "version": "from 1.000A to 1.090U"
            }
          ]
        },
        {
          "defaultStatus": "unaffected",
          "product": "GT Designer3 Version1 (GOT2000)",
          "vendor": "Mitsubishi Electric Corporation",
          "versions": [
            {
              "status": "affected",
              "version": "from 1.122C to 1.290C"
            }
          ]
        },
        {
          "defaultStatus": "unaffected",
          "product": "Motion Control Setting(GX Works3 related software)",
          "vendor": "Mitsubishi Electric Corporation",
          "versions": [
            {
              "status": "affected",
              "version": "from 1.035M to 1.042U"
            }
          ]
        }
      ],
      "descriptions": [
        {
          "lang": "en",
          "supportingMedia": [
            {
              "base64": false,
              "type": "text/html",
              "value": "Use of Hard-coded Cryptographic Key vulnerability in Mitsubishi Electric GX Works3 versions from 1.000A to 1.090U, GT Designer3 Version1 (GOT2000) versions from 1.122C to 1.290C and Motion Control Setting(GX Works3 related software) versions from 1.035M to 1.042U allows a remote unauthenticated attacker to disclose sensitive information. As a result, unauthenticated users may view programs and project files or execute programs illegally."
            }
          ],
          "value": "Use of Hard-coded Cryptographic Key vulnerability in Mitsubishi Electric GX Works3 versions from 1.000A to 1.090U, GT Designer3 Version1 (GOT2000) versions from 1.122C to 1.290C and Motion Control Setting(GX Works3 related software) versions from 1.035M to 1.042U allows a remote unauthenticated attacker to disclose sensitive information. As a result, unauthenticated users may view programs and project files or execute programs illegally."
        }
      ],
      "metrics": [
        {
          "cvssV3_1": {
            "attackComplexity": "HIGH",
            "attackVector": "NETWORK",
            "availabilityImpact": "NONE",
            "baseScore": 6.8,
            "baseSeverity": "MEDIUM",
            "confidentialityImpact": "HIGH",
            "integrityImpact": "NONE",
            "privilegesRequired": "NONE",
            "scope": "CHANGED",
            "userInteraction": "NONE",
            "vectorString": "CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:C/C:H/I:N/A:N",
            "version": "3.1"
          },
          "format": "CVSS",
          "scenarios": [
            {
              "lang": "en",
              "value": "GENERAL"
            }
          ]
        }
      ],
      "problemTypes": [
        {
          "descriptions": [
            {
              "cweId": "CWE-321",
              "description": "CWE-321 Use of Hard-coded Cryptographic Key",
              "lang": "en",
              "type": "CWE"
            }
          ]
        }
      ],
      "providerMetadata": {
        "dateUpdated": "2023-05-31T08:41:10.662Z",
        "orgId": "e0f77b61-78fd-4786-b3fb-1ee347a748ad",
        "shortName": "Mitsubishi"
      },
      "references": [
        {
          "tags": [
            "vendor-advisory"
          ],
          "url": "https://www.mitsubishielectric.com/en/psirt/vulnerability/pdf/2022-015_en.pdf"
        },
        {
          "tags": [
            "government-resource"
          ],
          "url": "https://jvn.jp/vu/JVNVU97244961/index.html"
        },
        {
          "tags": [
            "government-resource"
          ],
          "url": "https://www.cisa.gov/uscert/ics/advisories/icsa-22-333-05"
        }
      ],
      "source": {
        "discovery": "UNKNOWN"
      },
      "x_generator": {
        "engine": "Vulnogram 0.1.0-dev"
      }
    }
  },
  "cveMetadata": {
    "assignerOrgId": "e0f77b61-78fd-4786-b3fb-1ee347a748ad",
    "assignerShortName": "Mitsubishi",
    "cveId": "CVE-2022-29829",
    "datePublished": "2022-11-24T23:23:31.959Z",
    "dateReserved": "2022-04-27T20:47:43.443Z",
    "dateUpdated": "2024-08-03T06:33:42.868Z",
    "requesterUserId": "520cc88b-a1c8-44f6-9154-21a4d74c769f",
    "state": "PUBLISHED"
  },
  "dataType": "CVE_RECORD",
  "dataVersion": "5.1"
}

cve-2022-29825
Vulnerability from cvelistv5
Published
2022-11-24 23:21
Modified
2024-08-03 06:33
Summary
Use of Hard-coded Password vulnerability in Mitsubishi Electric GX Works3 versions from 1.000A to 1.090U and GT Designer3 Version1 (GOT2000) versions from 1.122C to 1.290C allows an unauthenticated attacker to disclose sensitive information. As a result, unauthenticated users may view programs and project files or execute programs illegally.
Show details on NVD website


{
  "containers": {
    "adp": [
      {
        "providerMetadata": {
          "dateUpdated": "2024-08-03T06:33:42.627Z",
          "orgId": "af854a3a-2127-422b-91ae-364da2661108",
          "shortName": "CVE"
        },
        "references": [
          {
            "tags": [
              "vendor-advisory",
              "x_transferred"
            ],
            "url": "https://www.mitsubishielectric.com/en/psirt/vulnerability/pdf/2022-015_en.pdf"
          },
          {
            "tags": [
              "government-resource",
              "x_transferred"
            ],
            "url": "https://jvn.jp/vu/JVNVU97244961/index.html"
          },
          {
            "tags": [
              "government-resource",
              "x_transferred"
            ],
            "url": "https://www.cisa.gov/uscert/ics/advisories/icsa-22-333-05"
          }
        ],
        "title": "CVE Program Container"
      }
    ],
    "cna": {
      "affected": [
        {
          "defaultStatus": "unaffected",
          "product": "GX Works3",
          "vendor": "Mitsubishi Electric Corporation",
          "versions": [
            {
              "status": "affected",
              "version": "from 1.000A to 1.090U"
            }
          ]
        },
        {
          "defaultStatus": "unaffected",
          "product": "GT Designer3 Version1 (GOT2000)",
          "vendor": "Mitsubishi Electric Corporation",
          "versions": [
            {
              "status": "affected",
              "version": "from 1.122C to 1.290C"
            }
          ]
        }
      ],
      "descriptions": [
        {
          "lang": "en",
          "supportingMedia": [
            {
              "base64": false,
              "type": "text/html",
              "value": "Use of Hard-coded Password vulnerability in Mitsubishi Electric GX Works3 versions from 1.000A to 1.090U and GT Designer3 Version1 (GOT2000) versions from 1.122C to 1.290C allows an unauthenticated attacker to disclose sensitive information. As a result, unauthenticated users may view programs and project files or execute programs illegally."
            }
          ],
          "value": "Use of Hard-coded Password vulnerability in Mitsubishi Electric GX Works3 versions from 1.000A to 1.090U and GT Designer3 Version1 (GOT2000) versions from 1.122C to 1.290C allows an unauthenticated attacker to disclose sensitive information. As a result, unauthenticated users may view programs and project files or execute programs illegally."
        }
      ],
      "metrics": [
        {
          "cvssV3_1": {
            "attackComplexity": "HIGH",
            "attackVector": "LOCAL",
            "availabilityImpact": "NONE",
            "baseScore": 5.6,
            "baseSeverity": "MEDIUM",
            "confidentialityImpact": "HIGH",
            "integrityImpact": "NONE",
            "privilegesRequired": "LOW",
            "scope": "CHANGED",
            "userInteraction": "NONE",
            "vectorString": "CVSS:3.1/AV:L/AC:H/PR:L/UI:N/S:C/C:H/I:N/A:N",
            "version": "3.1"
          },
          "format": "CVSS",
          "scenarios": [
            {
              "lang": "en",
              "value": "GENERAL"
            }
          ]
        }
      ],
      "problemTypes": [
        {
          "descriptions": [
            {
              "cweId": "CWE-259",
              "description": "CWE-259 Use of Hard-coded Password",
              "lang": "en",
              "type": "CWE"
            }
          ]
        }
      ],
      "providerMetadata": {
        "dateUpdated": "2023-05-31T08:39:05.292Z",
        "orgId": "e0f77b61-78fd-4786-b3fb-1ee347a748ad",
        "shortName": "Mitsubishi"
      },
      "references": [
        {
          "tags": [
            "vendor-advisory"
          ],
          "url": "https://www.mitsubishielectric.com/en/psirt/vulnerability/pdf/2022-015_en.pdf"
        },
        {
          "tags": [
            "government-resource"
          ],
          "url": "https://jvn.jp/vu/JVNVU97244961/index.html"
        },
        {
          "tags": [
            "government-resource"
          ],
          "url": "https://www.cisa.gov/uscert/ics/advisories/icsa-22-333-05"
        }
      ],
      "source": {
        "discovery": "UNKNOWN"
      },
      "x_generator": {
        "engine": "Vulnogram 0.1.0-dev"
      }
    }
  },
  "cveMetadata": {
    "assignerOrgId": "e0f77b61-78fd-4786-b3fb-1ee347a748ad",
    "assignerShortName": "Mitsubishi",
    "cveId": "CVE-2022-29825",
    "datePublished": "2022-11-24T23:21:54.776Z",
    "dateReserved": "2022-04-27T20:47:43.441Z",
    "dateUpdated": "2024-08-03T06:33:42.627Z",
    "requesterUserId": "520cc88b-a1c8-44f6-9154-21a4d74c769f",
    "state": "PUBLISHED"
  },
  "dataType": "CVE_RECORD",
  "dataVersion": "5.1"
}