Search criteria

2 vulnerabilities by Consilium Safety

CVE-2025-46352 (GCVE-0-2025-46352)

Vulnerability from cvelistv5 – Published: 2025-05-29 23:18 – Updated: 2025-05-30 12:49
VLAI?
Summary
The CS5000 Fire Panel is vulnerable due to a hard-coded password that runs on a VNC server and is visible as a string in the binary responsible for running VNC. This password cannot be altered, allowing anyone with knowledge of it to gain remote access to the panel. Such access could enable an attacker to operate the panel remotely, potentially putting the fire panel into a non-functional state and causing serious safety issues.
CWE
Assigner
Impacted products
Credits
Andrew Tierney of Pen Test Partners reported these vulnerabilities to CISA.
Show details on NVD website

{
  "containers": {
    "adp": [
      {
        "metrics": [
          {
            "other": {
              "content": {
                "id": "CVE-2025-46352",
                "options": [
                  {
                    "Exploitation": "none"
                  },
                  {
                    "Automatable": "yes"
                  },
                  {
                    "Technical Impact": "total"
                  }
                ],
                "role": "CISA Coordinator",
                "timestamp": "2025-05-30T12:49:22.434773Z",
                "version": "2.0.3"
              },
              "type": "ssvc"
            }
          }
        ],
        "providerMetadata": {
          "dateUpdated": "2025-05-30T12:49:31.802Z",
          "orgId": "134c704f-9b21-4f2e-91b3-4a467353bcc0",
          "shortName": "CISA-ADP"
        },
        "title": "CISA ADP Vulnrichment"
      }
    ],
    "cna": {
      "affected": [
        {
          "defaultStatus": "unaffected",
          "product": "CS5000 Fire Panel",
          "vendor": "Consilium Safety",
          "versions": [
            {
              "status": "affected",
              "version": "All versions"
            }
          ]
        }
      ],
      "credits": [
        {
          "lang": "en",
          "type": "finder",
          "value": "Andrew Tierney of Pen Test Partners reported these vulnerabilities to CISA."
        }
      ],
      "descriptions": [
        {
          "lang": "en",
          "supportingMedia": [
            {
              "base64": false,
              "type": "text/html",
              "value": "The CS5000 Fire Panel is vulnerable due to a hard-coded password that \nruns on a VNC server and is visible as a string in the binary \nresponsible for running VNC. This password cannot be altered, allowing \nanyone with knowledge of it to gain remote access to the panel. Such \naccess could enable an attacker to operate the panel remotely, \npotentially putting the fire panel into a non-functional state and \ncausing serious safety issues."
            }
          ],
          "value": "The CS5000 Fire Panel is vulnerable due to a hard-coded password that \nruns on a VNC server and is visible as a string in the binary \nresponsible for running VNC. This password cannot be altered, allowing \nanyone with knowledge of it to gain remote access to the panel. Such \naccess could enable an attacker to operate the panel remotely, \npotentially putting the fire panel into a non-functional state and \ncausing serious safety issues."
        }
      ],
      "metrics": [
        {
          "cvssV3_1": {
            "attackComplexity": "LOW",
            "attackVector": "NETWORK",
            "availabilityImpact": "HIGH",
            "baseScore": 9.8,
            "baseSeverity": "CRITICAL",
            "confidentialityImpact": "HIGH",
            "integrityImpact": "HIGH",
            "privilegesRequired": "NONE",
            "scope": "UNCHANGED",
            "userInteraction": "NONE",
            "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H",
            "version": "3.1"
          },
          "format": "CVSS",
          "scenarios": [
            {
              "lang": "en",
              "value": "GENERAL"
            }
          ]
        },
        {
          "cvssV4_0": {
            "Automatable": "NOT_DEFINED",
            "Recovery": "NOT_DEFINED",
            "Safety": "NOT_DEFINED",
            "attackComplexity": "LOW",
            "attackRequirements": "NONE",
            "attackVector": "NETWORK",
            "baseScore": 9.3,
            "baseSeverity": "CRITICAL",
            "privilegesRequired": "NONE",
            "providerUrgency": "NOT_DEFINED",
            "subAvailabilityImpact": "NONE",
            "subConfidentialityImpact": "NONE",
            "subIntegrityImpact": "NONE",
            "userInteraction": "NONE",
            "valueDensity": "NOT_DEFINED",
            "vectorString": "CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N",
            "version": "4.0",
            "vulnAvailabilityImpact": "HIGH",
            "vulnConfidentialityImpact": "HIGH",
            "vulnIntegrityImpact": "HIGH",
            "vulnerabilityResponseEffort": "NOT_DEFINED"
          },
          "format": "CVSS",
          "scenarios": [
            {
              "lang": "en",
              "value": "GENERAL"
            }
          ]
        }
      ],
      "problemTypes": [
        {
          "descriptions": [
            {
              "cweId": "CWE-798",
              "description": "CWE-798",
              "lang": "en",
              "type": "CWE"
            }
          ]
        }
      ],
      "providerMetadata": {
        "dateUpdated": "2025-05-29T23:18:33.934Z",
        "orgId": "7d14cffa-0d7d-4270-9dc0-52cabd5a23a6",
        "shortName": "icscert"
      },
      "references": [
        {
          "url": "https://www.cisa.gov/news-events/ics-advisories/icsa-25-148-03"
        },
        {
          "url": "https://www.consiliumsafety.com/en/support/"
        }
      ],
      "solutions": [
        {
          "lang": "en",
          "supportingMedia": [
            {
              "base64": false,
              "type": "text/html",
              "value": "\u003cdiv\u003eUsers wanting enhanced security features are advised to upgrade to \nConsilium Safety\u0027s newer line of fire panels. Specifically, products \nmanufactured after July 1, 2024, incorporate more secure-by-design \nprinciples.\u003cbr\u003e\u003c/div\u003e\nMore product safety information can be found on Consilium Safety\u0027s \u003ca target=\"_blank\" rel=\"nofollow\" href=\"https://www.consiliumsafety.com/en/support/\"\u003esupport webpage\u003c/a\u003e."
            }
          ],
          "value": "Users wanting enhanced security features are advised to upgrade to \nConsilium Safety\u0027s newer line of fire panels. Specifically, products \nmanufactured after July 1, 2024, incorporate more secure-by-design \nprinciples.\n\n\n\nMore product safety information can be found on Consilium Safety\u0027s  support webpage https://www.consiliumsafety.com/en/support/ ."
        }
      ],
      "source": {
        "advisory": "ICSA-25-148-03",
        "discovery": "EXTERNAL"
      },
      "title": "Consilium Safety CS5000 Fire Panel Use of Hard-coded Credentials",
      "workarounds": [
        {
          "lang": "en",
          "supportingMedia": [
            {
              "base64": false,
              "type": "text/html",
              "value": "\u003cp\u003eConsilium Safety is aware of these vulnerabilities. Currently, no fixes are planned for the CS5000 Fire Panel.\u003c/p\u003e\n\u003cp\u003eUsers wanting enhanced security features are advised to upgrade to \nConsilium Safety\u0027s newer line of fire panels. Specifically, products \nmanufactured after July 1, 2024, incorporate more secure-by-design \nprinciples.\u003c/p\u003e\n\u003cp\u003eUsers of the CS5000 Fire Panel are recommended to implement \ncompensating countermeasures, such as physical security and access \ncontrol restrictions for dedicated personnel.\u003c/p\u003e\u003cp\u003eMore product safety information can be found on Consilium Safety\u0027s \u003ca target=\"_blank\" rel=\"nofollow\" href=\"https://www.consiliumsafety.com/en/support/\"\u003esupport webpage\u003c/a\u003e.\n\n\u003cbr\u003e\u003c/p\u003e"
            }
          ],
          "value": "Consilium Safety is aware of these vulnerabilities. Currently, no fixes are planned for the CS5000 Fire Panel.\n\n\nUsers wanting enhanced security features are advised to upgrade to \nConsilium Safety\u0027s newer line of fire panels. Specifically, products \nmanufactured after July 1, 2024, incorporate more secure-by-design \nprinciples.\n\n\nUsers of the CS5000 Fire Panel are recommended to implement \ncompensating countermeasures, such as physical security and access \ncontrol restrictions for dedicated personnel.\n\nMore product safety information can be found on Consilium Safety\u0027s  support webpage https://www.consiliumsafety.com/en/support/ ."
        }
      ],
      "x_generator": {
        "engine": "Vulnogram 0.2.0"
      }
    }
  },
  "cveMetadata": {
    "assignerOrgId": "7d14cffa-0d7d-4270-9dc0-52cabd5a23a6",
    "assignerShortName": "icscert",
    "cveId": "CVE-2025-46352",
    "datePublished": "2025-05-29T23:18:33.934Z",
    "dateReserved": "2025-05-15T21:07:17.955Z",
    "dateUpdated": "2025-05-30T12:49:31.802Z",
    "state": "PUBLISHED"
  },
  "dataType": "CVE_RECORD",
  "dataVersion": "5.1"
}

CVE-2025-41438 (GCVE-0-2025-41438)

Vulnerability from cvelistv5 – Published: 2025-05-29 23:17 – Updated: 2025-05-30 12:50
VLAI?
Summary
The CS5000 Fire Panel is vulnerable due to a default account that exists on the panel. Even though it is possible to change this by SSHing into the device, it has remained unchanged on every installed system observed. This account is not root but holds high-level permissions that could severely impact the device's operation if exploited.
CWE
Assigner
Impacted products
Credits
Andrew Tierney of Pen Test Partners reported these vulnerabilities to CISA.
Show details on NVD website

{
  "containers": {
    "adp": [
      {
        "metrics": [
          {
            "other": {
              "content": {
                "id": "CVE-2025-41438",
                "options": [
                  {
                    "Exploitation": "none"
                  },
                  {
                    "Automatable": "yes"
                  },
                  {
                    "Technical Impact": "total"
                  }
                ],
                "role": "CISA Coordinator",
                "timestamp": "2025-05-30T12:50:10.819626Z",
                "version": "2.0.3"
              },
              "type": "ssvc"
            }
          }
        ],
        "providerMetadata": {
          "dateUpdated": "2025-05-30T12:50:16.987Z",
          "orgId": "134c704f-9b21-4f2e-91b3-4a467353bcc0",
          "shortName": "CISA-ADP"
        },
        "title": "CISA ADP Vulnrichment"
      }
    ],
    "cna": {
      "affected": [
        {
          "defaultStatus": "unaffected",
          "product": "CS5000 Fire Panel",
          "vendor": "Consilium Safety",
          "versions": [
            {
              "status": "affected",
              "version": "All versions"
            }
          ]
        }
      ],
      "credits": [
        {
          "lang": "en",
          "type": "finder",
          "value": "Andrew Tierney of Pen Test Partners reported these vulnerabilities to CISA."
        }
      ],
      "descriptions": [
        {
          "lang": "en",
          "supportingMedia": [
            {
              "base64": false,
              "type": "text/html",
              "value": "The CS5000 Fire Panel is vulnerable due to a default account that exists\n on the panel. Even though it is possible to change this by SSHing into \nthe device, it has remained unchanged on every installed system \nobserved. This account is not root but holds high-level permissions that\n could severely impact the device\u0027s operation if exploited."
            }
          ],
          "value": "The CS5000 Fire Panel is vulnerable due to a default account that exists\n on the panel. Even though it is possible to change this by SSHing into \nthe device, it has remained unchanged on every installed system \nobserved. This account is not root but holds high-level permissions that\n could severely impact the device\u0027s operation if exploited."
        }
      ],
      "metrics": [
        {
          "cvssV3_1": {
            "attackComplexity": "LOW",
            "attackVector": "NETWORK",
            "availabilityImpact": "HIGH",
            "baseScore": 9.8,
            "baseSeverity": "CRITICAL",
            "confidentialityImpact": "HIGH",
            "integrityImpact": "HIGH",
            "privilegesRequired": "NONE",
            "scope": "UNCHANGED",
            "userInteraction": "NONE",
            "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H",
            "version": "3.1"
          },
          "format": "CVSS",
          "scenarios": [
            {
              "lang": "en",
              "value": "GENERAL"
            }
          ]
        },
        {
          "cvssV4_0": {
            "Automatable": "NOT_DEFINED",
            "Recovery": "NOT_DEFINED",
            "Safety": "NOT_DEFINED",
            "attackComplexity": "LOW",
            "attackRequirements": "NONE",
            "attackVector": "NETWORK",
            "baseScore": 9.3,
            "baseSeverity": "CRITICAL",
            "privilegesRequired": "NONE",
            "providerUrgency": "NOT_DEFINED",
            "subAvailabilityImpact": "NONE",
            "subConfidentialityImpact": "NONE",
            "subIntegrityImpact": "NONE",
            "userInteraction": "NONE",
            "valueDensity": "NOT_DEFINED",
            "vectorString": "CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N",
            "version": "4.0",
            "vulnAvailabilityImpact": "HIGH",
            "vulnConfidentialityImpact": "HIGH",
            "vulnIntegrityImpact": "HIGH",
            "vulnerabilityResponseEffort": "NOT_DEFINED"
          },
          "format": "CVSS",
          "scenarios": [
            {
              "lang": "en",
              "value": "GENERAL"
            }
          ]
        }
      ],
      "problemTypes": [
        {
          "descriptions": [
            {
              "cweId": "CWE-1188",
              "description": "CWE-1188",
              "lang": "en",
              "type": "CWE"
            }
          ]
        }
      ],
      "providerMetadata": {
        "dateUpdated": "2025-05-29T23:17:18.012Z",
        "orgId": "7d14cffa-0d7d-4270-9dc0-52cabd5a23a6",
        "shortName": "icscert"
      },
      "references": [
        {
          "url": "https://www.cisa.gov/news-events/ics-advisories/icsa-25-148-03"
        },
        {
          "url": "https://www.consiliumsafety.com/en/support/"
        }
      ],
      "solutions": [
        {
          "lang": "en",
          "supportingMedia": [
            {
              "base64": false,
              "type": "text/html",
              "value": "\u003cdiv\u003eUsers wanting enhanced security features are advised to upgrade to \nConsilium Safety\u0027s newer line of fire panels. Specifically, products \nmanufactured after July 1, 2024, incorporate more secure-by-design \nprinciples.\u003cbr\u003e\u003c/div\u003e\nMore product safety information can be found on Consilium Safety\u0027s \u003ca target=\"_blank\" rel=\"nofollow\" href=\"https://www.consiliumsafety.com/en/support/\"\u003esupport webpage\u003c/a\u003e."
            }
          ],
          "value": "Users wanting enhanced security features are advised to upgrade to \nConsilium Safety\u0027s newer line of fire panels. Specifically, products \nmanufactured after July 1, 2024, incorporate more secure-by-design \nprinciples.\n\n\n\nMore product safety information can be found on Consilium Safety\u0027s  support webpage https://www.consiliumsafety.com/en/support/ ."
        }
      ],
      "source": {
        "advisory": "ICSA-25-148-03",
        "discovery": "EXTERNAL"
      },
      "title": "Consilium Safety CS5000 Fire Panel Initialization of a Resource with an Insecure Default",
      "workarounds": [
        {
          "lang": "en",
          "supportingMedia": [
            {
              "base64": false,
              "type": "text/html",
              "value": "\u003cp\u003eConsilium Safety is aware of these vulnerabilities. Currently, no fixes are planned for the CS5000 Fire Panel.\u003c/p\u003e\n\u003cp\u003eUsers wanting enhanced security features are advised to upgrade to \nConsilium Safety\u0027s newer line of fire panels. Specifically, products \nmanufactured after July 1, 2024, incorporate more secure-by-design \nprinciples.\u003c/p\u003e\n\u003cp\u003eUsers of the CS5000 Fire Panel are recommended to implement \ncompensating countermeasures, such as physical security and access \ncontrol restrictions for dedicated personnel.\u003c/p\u003e\u003cp\u003eMore product safety information can be found on Consilium Safety\u0027s \u003ca target=\"_blank\" rel=\"nofollow\" href=\"https://www.consiliumsafety.com/en/support/\"\u003esupport webpage\u003c/a\u003e.\n\n\u003cbr\u003e\u003c/p\u003e"
            }
          ],
          "value": "Consilium Safety is aware of these vulnerabilities. Currently, no fixes are planned for the CS5000 Fire Panel.\n\n\nUsers wanting enhanced security features are advised to upgrade to \nConsilium Safety\u0027s newer line of fire panels. Specifically, products \nmanufactured after July 1, 2024, incorporate more secure-by-design \nprinciples.\n\n\nUsers of the CS5000 Fire Panel are recommended to implement \ncompensating countermeasures, such as physical security and access \ncontrol restrictions for dedicated personnel.\n\nMore product safety information can be found on Consilium Safety\u0027s  support webpage https://www.consiliumsafety.com/en/support/ ."
        }
      ],
      "x_generator": {
        "engine": "Vulnogram 0.2.0"
      }
    }
  },
  "cveMetadata": {
    "assignerOrgId": "7d14cffa-0d7d-4270-9dc0-52cabd5a23a6",
    "assignerShortName": "icscert",
    "cveId": "CVE-2025-41438",
    "datePublished": "2025-05-29T23:17:18.012Z",
    "dateReserved": "2025-05-15T21:07:17.944Z",
    "dateUpdated": "2025-05-30T12:50:16.987Z",
    "state": "PUBLISHED"
  },
  "dataType": "CVE_RECORD",
  "dataVersion": "5.1"
}