icsa-21-350-06
Vulnerability from csaf_cisa
Published
2021-12-16 00:00
Modified
2021-12-16 00:00
Summary
Siemens Capital VSTAR
Notes
CISA Disclaimer
This CSAF advisory was extracted from unstructured data and may contain inaccuracies. If you notice any errors, please reach out to the designated contact at CISA CSAF: central@cisa.dhs.gov
Legal Notice
All information products included in https://us-cert.cisa.gov/ics are provided "as is" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see https://us-cert.cisa.gov/tlp/.
Risk evaluation
Successful exploitation of these vulnerabilities could be leveraged by an attacker to initiate a crash, information leak, denial-of-service conditions, or remote code execution.
Critical infrastructure sectors
Critical Manufacturing
Countries/areas deployed
Worldwide
Company headquarters location
Germany
Recommended Practices
CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability. Specifically, users should: Minimize network exposure for all control system devices and/or systems, and ensure they are not accessible from the Internet; Locate control system networks and remote devices behind firewalls and isolate them from the business network; When remote access is required, use secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize VPN is only as secure as its connected devices.
Recommended Practices
CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.
CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov. Several recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.
Recommended Practices
Additional mitigation guidance and recommended practices are publicly available on the ICS webpage on cisa.gov in the Technical Information Paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.
Organizations observing any suspected malicious activity should follow their established internal procedures and report their findings to CISA for tracking and correlation against other incidents.
Additional Resources
For further inquiries on security vulnerabilities in Siemens products and solutions, please contact the Siemens ProductCERT: https://www.siemens.com/cert/advisories
Exploitability
No known public exploits specifically target these vulnerabilities. These vulnerabilities are exploitable remotely.
{ "document": { "acknowledgments": [ { "organization": "Siemens", "summary": "reporting these vulnerabilities to CISA" } ], "category": "csaf_security_advisory", "csaf_version": "2.0", "distribution": { "text": "Disclosure is not limited", "tlp": { "label": "WHITE", "url": "https://us-cert.cisa.gov/tlp/" } }, "lang": "en-US", "notes": [ { "category": "general", "text": "This CSAF advisory was extracted from unstructured data and may contain inaccuracies. If you notice any errors, please reach out to the designated contact at CISA CSAF: central@cisa.dhs.gov", "title": "CISA Disclaimer" }, { "category": "legal_disclaimer", "text": "All information products included in https://us-cert.cisa.gov/ics are provided \"as is\" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see https://us-cert.cisa.gov/tlp/.", "title": "Legal Notice" }, { "category": "summary", "text": "Successful exploitation of these vulnerabilities could be leveraged by an attacker to initiate a crash, information leak, denial-of-service conditions, or remote code execution.", "title": "Risk evaluation" }, { "category": "other", "text": "Critical Manufacturing", "title": "Critical infrastructure sectors" }, { "category": "other", "text": "Worldwide", "title": "Countries/areas deployed" }, { "category": "other", "text": "Germany", "title": "Company headquarters location" }, { "category": "general", "text": "CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability. Specifically, users should: Minimize network exposure for all control system devices and/or systems, and ensure they are not accessible from the Internet; Locate control system networks and remote devices behind firewalls and isolate them from the business network; When remote access is required, use secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize VPN is only as secure as its connected devices.", "title": "Recommended Practices" }, { "category": "general", "text": "CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.\nCISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov. Several recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.", "title": "Recommended Practices" }, { "category": "general", "text": "Additional mitigation guidance and recommended practices are publicly available on the ICS webpage on cisa.gov in the Technical Information Paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.\nOrganizations observing any suspected malicious activity should follow their established internal procedures and report their findings to CISA for tracking and correlation against other incidents.", "title": "Recommended Practices" }, { "category": "general", "text": "For further inquiries on security vulnerabilities in Siemens products and solutions, please contact the Siemens ProductCERT: https://www.siemens.com/cert/advisories", "title": "Additional Resources" }, { "category": "other", "text": "No known public exploits specifically target these vulnerabilities. These vulnerabilities are exploitable remotely.", "title": "Exploitability" } ], "publisher": { "category": "coordinator", "contact_details": "Email: CISAservicedesk@cisa.dhs.gov;\n Toll Free: 1-888-282-0870", "name": "CISA", "namespace": "https://www.cisa.gov/" }, "references": [ { "category": "external", "summary": "SSA-620288: Multiple Vulnerabilities (NUCLEUS:13) in CAPITAL VSTAR - CSAF Version", "url": "https://cert-portal.siemens.com/productcert/csaf/ssa-620288.json" }, { "category": "self", "summary": "ICS Advisory ICSA-21-350-06 JSON", "url": "https://raw.githubusercontent.com/cisagov/CSAF/develop/csaf_files/OT/white/2021/icsa-21-350-06.json" }, { "category": "self", "summary": "ICS Advisory ICSA-21-350-06 Web Version", "url": "https://www.cisa.gov/news-events/ics-advisories/icsa-21-350-06" }, { "category": "external", "summary": "Recommended Practices", "url": "https://www.cisa.gov/uscert/ics/alerts/ICS-ALERT-10-301-01" }, { "category": "external", "summary": "Recommended Practices", "url": "https://www.cisa.gov/uscert/sites/default/files/recommended_practices/NCCIC_ICS-CERT_Defense_in_Depth_2016_S508C.pdf" }, { "category": "external", "summary": "Recommended Practices", "url": "https://www.cisa.gov/uscert/ics/tips/ICS-TIP-12-146-01B" }, { "category": "external", "summary": "SSA-620288: Multiple Vulnerabilities (NUCLEUS:13) in CAPITAL VSTAR - PDF Version", "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-620288.pdf" }, { "category": "external", "summary": "SSA-620288: Multiple Vulnerabilities (NUCLEUS:13) in CAPITAL VSTAR - TXT Version", "url": "https://cert-portal.siemens.com/productcert/txt/ssa-620288.txt" } ], "title": "Siemens Capital VSTAR", "tracking": { "current_release_date": "2021-12-16T00:00:00.000000Z", "generator": { "engine": { "name": "CISA CSAF Generator", "version": "1.0.0" } }, "id": "ICSA-21-350-06", "initial_release_date": "2021-12-16T00:00:00.000000Z", "revision_history": [ { "date": "2021-12-16T00:00:00.000000Z", "legacy_version": "Initial", "number": "1", "summary": "ICSA-21-350-06 Siemens CAPITAL VSTAR" } ], "status": "final", "version": "1" } }, "product_tree": { "branches": [ { "branches": [ { "branches": [ { "category": "product_version_range", "name": "All versions with enabled Ethernet options", "product": { "name": "Capital VSTAR", "product_id": "CSAFPID-0001" } } ], "category": "product_name", "name": "Capital VSTAR" } ], "category": "vendor", "name": "Siemens" } ] }, "vulnerabilities": [ { "cve": "CVE-2021-31344", "cwe": { "id": "CWE-843", "name": "Access of Resource Using Incompatible Type (\u0027Type Confusion\u0027)" }, "notes": [ { "category": "summary", "text": "ICMP echo packets with fake IP options allow sending ICMP echo reply messages to arbitrary hosts on the network. (FSMD-2021-0004). CVE-2021-31344 has been assigned to this vulnerability. A CVSS v3 base score of 5.3 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:L/A:N).", "title": "Summary" } ], "product_status": { "known_affected": [ "CSAFPID-0001" ] }, "references": [ { "category": "external", "summary": "web.nvd.nist.gov", "url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2021-31344" }, { "category": "external", "summary": "www.first.org", "url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:L/A:N" } ], "remediations": [ { "category": "mitigation", "details": "CVE-2021-31344, CVE-2021-31345, CVE-2021-31346, CVE-2021-31889, CVE-2021-31890: Apply network segmentation and put the ECUs behind properly configured gateways/firewalls", "product_ids": [ "CSAFPID-0001" ] }, { "category": "none_available", "details": "Currently no fix is available", "product_ids": [ "CSAFPID-0001" ] }, { "category": "mitigation", "details": "As a general security measure, Siemens strongly recommends to protect network access to devices with appropriate mechanisms. In order to operate the devices in a protected IT environment, Siemens recommends to configure the environment according to Siemens\u0027 operational guidelines for Industrial Security (Download: \nhttps://www.siemens.com/cert/operational-guidelines-industrial-security), and to follow the recommendations in the product manuals.\nAdditional information on Industrial Security by Siemens can be found at: \nhttps://www.siemens.com/industrialsecurity", "product_ids": [ "CSAFPID-0001" ] } ], "scores": [ { "cvss_v3": { "baseScore": 5.3, "baseSeverity": "MEDIUM", "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:L/A:N/E:P/RL:O/RC:C", "version": "3.1" }, "products": [ "CSAFPID-0001" ] } ], "title": "CVE-2021-31344" }, { "cve": "CVE-2021-31345", "cwe": { "id": "CWE-1284", "name": "Improper Validation of Specified Quantity in Input" }, "notes": [ { "category": "summary", "text": "The total length of an UDP payload (set in the IP header) is unchecked. This may lead to various side effects, including Information Leak and Denial-of-Service conditions, depending on a user-defined applications that runs on top of the UDP protocol. (FSMD-2021-0006). CVE-2021-31345 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N).", "title": "Summary" } ], "product_status": { "known_affected": [ "CSAFPID-0001" ] }, "references": [ { "category": "external", "summary": "web.nvd.nist.gov", "url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2021-31345" }, { "category": "external", "summary": "www.first.org", "url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N" } ], "remediations": [ { "category": "none_available", "details": "Currently no fix is available", "product_ids": [ "CSAFPID-0001" ] }, { "category": "mitigation", "details": "As a general security measure, Siemens strongly recommends to protect network access to devices with appropriate mechanisms. In order to operate the devices in a protected IT environment, Siemens recommends to configure the environment according to Siemens\u0027 operational guidelines for Industrial Security (Download: \nhttps://www.siemens.com/cert/operational-guidelines-industrial-security), and to follow the recommendations in the product manuals.\nAdditional information on Industrial Security by Siemens can be found at: \nhttps://www.siemens.com/industrialsecurity", "product_ids": [ "CSAFPID-0001" ] } ], "scores": [ { "cvss_v3": { "baseScore": 7.5, "baseSeverity": "HIGH", "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N/E:P/RL:O/RC:C", "version": "3.1" }, "products": [ "CSAFPID-0001" ] } ], "title": "CVE-2021-31345" }, { "cve": "CVE-2021-31346", "cwe": { "id": "CWE-1284", "name": "Improper Validation of Specified Quantity in Input" }, "notes": [ { "category": "summary", "text": "The total length of an ICMP payload (set in the IP header) is unchecked. This may lead to various side effects, including Information Leak and Denial-of-Service conditions, depending on the network buffer organization in memory. (FSMD-2021-0007). CVE-2021-31346 has been assigned to this vulnerability. A CVSS v3 base score of 8.2 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:N/A:H).", "title": "Summary" } ], "product_status": { "known_affected": [ "CSAFPID-0001" ] }, "references": [ { "category": "external", "summary": "web.nvd.nist.gov", "url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2021-31346" }, { "category": "external", "summary": "www.first.org", "url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:N/A:H" } ], "remediations": [ { "category": "none_available", "details": "Currently no fix is available", "product_ids": [ "CSAFPID-0001" ] }, { "category": "mitigation", "details": "As a general security measure, Siemens strongly recommends to protect network access to devices with appropriate mechanisms. In order to operate the devices in a protected IT environment, Siemens recommends to configure the environment according to Siemens\u0027 operational guidelines for Industrial Security (Download: \nhttps://www.siemens.com/cert/operational-guidelines-industrial-security), and to follow the recommendations in the product manuals.\nAdditional information on Industrial Security by Siemens can be found at: \nhttps://www.siemens.com/industrialsecurity", "product_ids": [ "CSAFPID-0001" ] } ], "scores": [ { "cvss_v3": { "baseScore": 8.2, "baseSeverity": "HIGH", "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:N/A:H/E:P/RL:O/RC:C", "version": "3.1" }, "products": [ "CSAFPID-0001" ] } ], "title": "CVE-2021-31346" }, { "cve": "CVE-2021-31881", "cwe": { "id": "CWE-125", "name": "Out-of-bounds Read" }, "notes": [ { "category": "summary", "text": "When processing a DHCP OFFER message, the DHCP client application does not validate the length of the Vendor option(s), leading to Denial-of-Service conditions. (FSMD-2021-0008). CVE-2021-31881 has been assigned to this vulnerability. A CVSS v3 base score of 7.1 has been calculated; the CVSS vector string is (AV:A/AC:L/PR:N/UI:N/S:U/C:L/I:N/A:H).", "title": "Summary" } ], "product_status": { "known_affected": [ "CSAFPID-0001" ] }, "references": [ { "category": "external", "summary": "web.nvd.nist.gov", "url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2021-31881" }, { "category": "external", "summary": "www.first.org", "url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:A/AC:L/PR:N/UI:N/S:U/C:L/I:N/A:H" } ], "remediations": [ { "category": "mitigation", "details": "CVE-2021-31881, CVE-2021-31882, CVE-2021-31883: Disable DHCP client functionality, if feature not used, by deselecting the TcpIpIpV4General/TcpIpDhcpClientEnabled Pre-Compile configuration option", "product_ids": [ "CSAFPID-0001" ] }, { "category": "none_available", "details": "Currently no fix is available", "product_ids": [ "CSAFPID-0001" ] }, { "category": "mitigation", "details": "As a general security measure, Siemens strongly recommends to protect network access to devices with appropriate mechanisms. In order to operate the devices in a protected IT environment, Siemens recommends to configure the environment according to Siemens\u0027 operational guidelines for Industrial Security (Download: \nhttps://www.siemens.com/cert/operational-guidelines-industrial-security), and to follow the recommendations in the product manuals.\nAdditional information on Industrial Security by Siemens can be found at: \nhttps://www.siemens.com/industrialsecurity", "product_ids": [ "CSAFPID-0001" ] } ], "scores": [ { "cvss_v3": { "baseScore": 7.1, "baseSeverity": "HIGH", "vectorString": "CVSS:3.1/AV:A/AC:L/PR:N/UI:N/S:U/C:L/I:N/A:H/E:P/RL:O/RC:C", "version": "3.1" }, "products": [ "CSAFPID-0001" ] } ], "title": "CVE-2021-31881" }, { "cve": "CVE-2021-31882", "cwe": { "id": "CWE-119", "name": "Improper Restriction of Operations within the Bounds of a Memory Buffer" }, "notes": [ { "category": "summary", "text": "The DHCP client application does not validate the length of the Domain Name Server IP option(s) (0x06) when processing DHCP ACK packets. This may lead to Denial-of-Service conditions. (FSMD-2021-0011). CVE-2021-31882 has been assigned to this vulnerability. A CVSS v3 base score of 6.5 has been calculated; the CVSS vector string is (AV:A/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).", "title": "Summary" } ], "product_status": { "known_affected": [ "CSAFPID-0001" ] }, "references": [ { "category": "external", "summary": "web.nvd.nist.gov", "url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2021-31882" }, { "category": "external", "summary": "www.first.org", "url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:A/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H" } ], "remediations": [ { "category": "none_available", "details": "Currently no fix is available", "product_ids": [ "CSAFPID-0001" ] }, { "category": "mitigation", "details": "As a general security measure, Siemens strongly recommends to protect network access to devices with appropriate mechanisms. In order to operate the devices in a protected IT environment, Siemens recommends to configure the environment according to Siemens\u0027 operational guidelines for Industrial Security (Download: \nhttps://www.siemens.com/cert/operational-guidelines-industrial-security), and to follow the recommendations in the product manuals.\nAdditional information on Industrial Security by Siemens can be found at: \nhttps://www.siemens.com/industrialsecurity", "product_ids": [ "CSAFPID-0001" ] } ], "scores": [ { "cvss_v3": { "baseScore": 6.5, "baseSeverity": "MEDIUM", "vectorString": "CVSS:3.1/AV:A/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H/E:P/RL:O/RC:C", "version": "3.1" }, "products": [ "CSAFPID-0001" ] } ], "title": "CVE-2021-31882" }, { "cve": "CVE-2021-31883", "cwe": { "id": "CWE-119", "name": "Improper Restriction of Operations within the Bounds of a Memory Buffer" }, "notes": [ { "category": "summary", "text": "When processing a DHCP ACK message, the DHCP client application does not validate the length of the Vendor option(s), leading to Denial-of-Service conditions. (FSMD-2021-0013). CVE-2021-31883 has been assigned to this vulnerability. A CVSS v3 base score of 7.1 has been calculated; the CVSS vector string is (AV:A/AC:L/PR:N/UI:N/S:U/C:L/I:N/A:H).", "title": "Summary" } ], "product_status": { "known_affected": [ "CSAFPID-0001" ] }, "references": [ { "category": "external", "summary": "web.nvd.nist.gov", "url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2021-31883" }, { "category": "external", "summary": "www.first.org", "url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:A/AC:L/PR:N/UI:N/S:U/C:L/I:N/A:H" } ], "remediations": [ { "category": "none_available", "details": "Currently no fix is available", "product_ids": [ "CSAFPID-0001" ] }, { "category": "mitigation", "details": "As a general security measure, Siemens strongly recommends to protect network access to devices with appropriate mechanisms. In order to operate the devices in a protected IT environment, Siemens recommends to configure the environment according to Siemens\u0027 operational guidelines for Industrial Security (Download: \nhttps://www.siemens.com/cert/operational-guidelines-industrial-security), and to follow the recommendations in the product manuals.\nAdditional information on Industrial Security by Siemens can be found at: \nhttps://www.siemens.com/industrialsecurity", "product_ids": [ "CSAFPID-0001" ] } ], "scores": [ { "cvss_v3": { "baseScore": 7.1, "baseSeverity": "HIGH", "vectorString": "CVSS:3.1/AV:A/AC:L/PR:N/UI:N/S:U/C:L/I:N/A:H/E:P/RL:O/RC:C", "version": "3.1" }, "products": [ "CSAFPID-0001" ] } ], "title": "CVE-2021-31883" }, { "cve": "CVE-2021-31889", "cwe": { "id": "CWE-191", "name": "Integer Underflow (Wrap or Wraparound)" }, "notes": [ { "category": "summary", "text": "Malformed TCP packets with a corrupted SACK option leads to Information Leaks and Denial-of-Service conditions. (FSMD-2021-0015). CVE-2021-31889 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:N).", "title": "Summary" } ], "product_status": { "known_affected": [ "CSAFPID-0001" ] }, "references": [ { "category": "external", "summary": "web.nvd.nist.gov", "url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2021-31889" }, { "category": "external", "summary": "www.first.org", "url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H" } ], "remediations": [ { "category": "none_available", "details": "Currently no fix is available", "product_ids": [ "CSAFPID-0001" ] }, { "category": "mitigation", "details": "As a general security measure, Siemens strongly recommends to protect network access to devices with appropriate mechanisms. In order to operate the devices in a protected IT environment, Siemens recommends to configure the environment according to Siemens\u0027 operational guidelines for Industrial Security (Download: \nhttps://www.siemens.com/cert/operational-guidelines-industrial-security), and to follow the recommendations in the product manuals.\nAdditional information on Industrial Security by Siemens can be found at: \nhttps://www.siemens.com/industrialsecurity", "product_ids": [ "CSAFPID-0001" ] } ], "scores": [ { "cvss_v3": { "baseScore": 7.5, "baseSeverity": "HIGH", "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H/E:P/RL:O/RC:C", "version": "3.1" }, "products": [ "CSAFPID-0001" ] } ], "title": "CVE-2021-31889" }, { "cve": "CVE-2021-31890", "cwe": { "id": "CWE-240", "name": "Improper Handling of Inconsistent Structural Elements" }, "notes": [ { "category": "summary", "text": "The total length of an TCP payload (set in the IP header) is unchecked. This may lead to various side effects, including Information Leak and Denial-of-Service conditions, depending on the network buffer organization in memory. (FSMD-2021-0017). CVE-2021-31890 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).", "title": "Summary" } ], "product_status": { "known_affected": [ "CSAFPID-0001" ] }, "references": [ { "category": "external", "summary": "web.nvd.nist.gov", "url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2021-31890" }, { "category": "external", "summary": "www.first.org", "url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H" } ], "remediations": [ { "category": "none_available", "details": "Currently no fix is available", "product_ids": [ "CSAFPID-0001" ] }, { "category": "mitigation", "details": "As a general security measure, Siemens strongly recommends to protect network access to devices with appropriate mechanisms. In order to operate the devices in a protected IT environment, Siemens recommends to configure the environment according to Siemens\u0027 operational guidelines for Industrial Security (Download: \nhttps://www.siemens.com/cert/operational-guidelines-industrial-security), and to follow the recommendations in the product manuals.\nAdditional information on Industrial Security by Siemens can be found at: \nhttps://www.siemens.com/industrialsecurity", "product_ids": [ "CSAFPID-0001" ] } ], "scores": [ { "cvss_v3": { "baseScore": 7.5, "baseSeverity": "HIGH", "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H/E:P/RL:O/RC:C", "version": "3.1" }, "products": [ "CSAFPID-0001" ] } ], "title": "CVE-2021-31890" } ] }
Loading...
Loading...
Sightings
Author | Source | Type | Date |
---|
Nomenclature
- Seen: The vulnerability was mentioned, discussed, or seen somewhere by the user.
- Confirmed: The vulnerability is confirmed from an analyst perspective.
- Exploited: This vulnerability was exploited and seen by the user reporting the sighting.
- Patched: This vulnerability was successfully patched by the user reporting the sighting.
- Not exploited: This vulnerability was not exploited or seen by the user reporting the sighting.