Summary
Siemens SIMATIC S7-1200 and S7-1500 CPU Families

Notes

CISA Disclaimer
This CSAF advisory was extracted from unstructured data and may contain inaccuracies. If you notice any errors, please reach out to the designated contact at CISA CSAF: central@cisa.dhs.gov
Legal Notice
All information products included in https://us-cert.cisa.gov/ics are provided "as is" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see https://us-cert.cisa.gov/tlp/.
Risk evaluation
Successful exploitation of this vulnerability could expose confidential configuration data.
Critical infrastructure sectors
Multiple Sectors
Countries/areas deployed
Worldwide
Company headquarters location
Germany
Recommended Practices
CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.
Recommended Practices
CISA also provides a section for control systems security recommended practices on the ICS webpage at cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.
Recommended Practices
Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.
Recommended Practices
Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.
Additional Resources
For further inquiries on security vulnerabilities in Siemens products and solutions, please contact the Siemens ProductCERT: https://www.siemens.com/cert/advisories
Exploitability
No known public exploits specifically target this vulnerability. This vulnerability is not exploitable remotely.



{
  "document": {
    "acknowledgments": [
      {
        "names": [
          "Tal Keren"
        ],
        "organization": "Claroty",
        "summary": "reporting this vulnerability to Siemens"
      }
    ],
    "category": "csaf_security_advisory",
    "csaf_version": "2.0",
    "distribution": {
      "text": "Disclosure is not limited",
      "tlp": {
        "label": "WHITE",
        "url": "https://us-cert.cisa.gov/tlp/"
      }
    },
    "lang": "en-US",
    "notes": [
      {
        "category": "general",
        "text": "This CSAF advisory was extracted from unstructured data and may contain inaccuracies. If you notice any errors, please reach out to the designated contact at CISA CSAF: central@cisa.dhs.gov",
        "title": "CISA Disclaimer"
      },
      {
        "category": "legal_disclaimer",
        "text": "All information products included in https://us-cert.cisa.gov/ics are provided \"as is\" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see https://us-cert.cisa.gov/tlp/.",
        "title": "Legal Notice"
      },
      {
        "category": "summary",
        "text": "Successful exploitation of this vulnerability could expose confidential configuration data.",
        "title": "Risk evaluation"
      },
      {
        "category": "other",
        "text": "Multiple Sectors",
        "title": "Critical infrastructure sectors"
      },
      {
        "category": "other",
        "text": "Worldwide",
        "title": "Countries/areas deployed"
      },
      {
        "category": "other",
        "text": "Germany",
        "title": "Company headquarters location"
      },
      {
        "category": "general",
        "text": "CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.",
        "title": "Recommended Practices"
      },
      {
        "category": "general",
        "text": "CISA also provides a section for control systems security recommended practices on the ICS webpage at cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.",
        "title": "Recommended Practices"
      },
      {
        "category": "general",
        "text": "Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.",
        "title": "Recommended Practices"
      },
      {
        "category": "general",
        "text": "Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.",
        "title": "Recommended Practices"
      },
      {
        "category": "general",
        "text": "For further inquiries on security vulnerabilities in Siemens products and solutions, please contact the Siemens ProductCERT: https://www.siemens.com/cert/advisories",
        "title": "Additional Resources"
      },
      {
        "category": "other",
        "text": "No known public exploits specifically target this vulnerability. This vulnerability is not exploitable remotely.",
        "title": "Exploitability"
      }
    ],
    "publisher": {
      "category": "coordinator",
      "contact_details": "Email: CISAservicedesk@cisa.dhs.gov;\n Toll Free: 1-888-282-0870",
      "name": "CISA",
      "namespace": "https://www.cisa.gov/"
    },
    "references": [
      {
        "category": "external",
        "summary": "SSA-568427: Weak Key Protection Vulnerability in SIMATIC S7-1200 and S7-1500 CPU Families - CSAF Version",
        "url": "https://cert-portal.siemens.com/productcert/csaf/ssa-568427.json"
      },
      {
        "category": "self",
        "summary": "ICS Advisory ICSA-22-286-04 JSON",
        "url": "https://raw.githubusercontent.com/cisagov/CSAF/develop/csaf_files/OT/white/2022/icsa-22-286-04.json"
      },
      {
        "category": "self",
        "summary": "ICS Advisory ICSA-22-286-04 Web Version",
        "url": "https://www.cisa.gov/news-events/ics-advisories/icsa-22-286-04"
      },
      {
        "category": "external",
        "summary": "Recommended Practices",
        "url": "https://www.cisa.gov/news-events/ics-advisories/icsa-22-286-04"
      },
      {
        "category": "external",
        "summary": "Recommended Practices",
        "url": "https://us-cert.cisa.gov/sites/default/files/recommended_practices/NCCIC_ICS-CERT_Defense_in_Depth_2016_S508C.pdf"
      },
      {
        "category": "external",
        "summary": "SSA-568427: Weak Key Protection Vulnerability in SIMATIC S7-1200 and S7-1500 CPU Families - PDF Version",
        "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-568427.pdf"
      },
      {
        "category": "external",
        "summary": "SSA-568427: Weak Key Protection Vulnerability in SIMATIC S7-1200 and S7-1500 CPU Families - TXT Version",
        "url": "https://cert-portal.siemens.com/productcert/txt/ssa-568427.txt"
      }
    ],
    "title": "Siemens SIMATIC S7-1200 and S7-1500 CPU Families",
    "tracking": {
      "current_release_date": "2022-10-13T00:00:00.000000Z",
      "generator": {
        "engine": {
          "name": "CISA CSAF Generator",
          "version": "1.0.0"
        }
      },
      "id": "ICSA-22-286-04",
      "initial_release_date": "2022-10-13T00:00:00.000000Z",
      "revision_history": [
        {
          "date": "2022-10-13T00:00:00.000000Z",
          "legacy_version": "Initial",
          "number": "1",
          "summary": "Publication Date"
        }
      ],
      "status": "final",
      "version": "1"
    }
  },
  "product_tree": {
    "branches": [
      {
        "branches": [
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "\u003c V2.9.2",
                "product": {
                  "name": "SIMATIC Drive Controller family",
                  "product_id": "CSAFPID-0001"
                }
              }
            ],
            "category": "product_name",
            "name": "SIMATIC Drive Controller family"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "vers:all/*",
                "product": {
                  "name": "SIMATIC ET 200SP Open Controller CPU 1515SP PC (incl. SIPLUS variants)",
                  "product_id": "CSAFPID-0002"
                }
              }
            ],
            "category": "product_name",
            "name": "SIMATIC ET 200SP Open Controller CPU 1515SP PC (incl. SIPLUS variants)"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "\u003c V21.9",
                "product": {
                  "name": "SIMATIC ET 200SP Open Controller CPU 1515SP PC2 (incl. SIPLUS variants)",
                  "product_id": "CSAFPID-0003"
                }
              }
            ],
            "category": "product_name",
            "name": "SIMATIC ET 200SP Open Controller CPU 1515SP PC2 (incl. SIPLUS variants)"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "\u003c V4.5.0",
                "product": {
                  "name": "SIMATIC S7-1200 CPU family (incl. SIPLUS variants)",
                  "product_id": "CSAFPID-0004"
                }
              }
            ],
            "category": "product_name",
            "name": "SIMATIC S7-1200 CPU family (incl. SIPLUS variants)"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "\u003c V2.9.2",
                "product": {
                  "name": "SIMATIC S7-1500 CPU family (incl. related ET200 CPUs and SIPLUS variants)",
                  "product_id": "CSAFPID-0005"
                }
              }
            ],
            "category": "product_name",
            "name": "SIMATIC S7-1500 CPU family (incl. related ET200 CPUs and SIPLUS variants)"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "\u003c V21.9",
                "product": {
                  "name": "SIMATIC S7-1500 Software Controller",
                  "product_id": "CSAFPID-0006"
                }
              }
            ],
            "category": "product_name",
            "name": "SIMATIC S7-1500 Software Controller"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "\u003c V4.0",
                "product": {
                  "name": "SIMATIC S7-PLCSIM Advanced",
                  "product_id": "CSAFPID-0007"
                }
              }
            ],
            "category": "product_name",
            "name": "SIMATIC S7-PLCSIM Advanced"
          }
        ],
        "category": "vendor",
        "name": "Siemens"
      }
    ]
  },
  "vulnerabilities": [
    {
      "cve": "CVE-2022-38465",
      "cwe": {
        "id": "CWE-522",
        "name": "Insufficiently Protected Credentials"
      },
      "notes": [
        {
          "category": "summary",
          "text": "Affected products  protect the built-in global private key in a way that cannot be considered sufficient any longer. The key is used for the legacy protection of confidential configuration data and the legacy PG/PC and HMI communication.\r\n\r\nThis could allow attackers to discover the private key of a CPU product family by an offline attack against a single CPU of the family. Attackers could then use this knowledge to extract confidential configuration data from projects that are protected by that key or to perform attacks against legacy PG/PC and HMI communication.",
          "title": "Summary"
        }
      ],
      "product_status": {
        "known_affected": [
          "CSAFPID-0001",
          "CSAFPID-0002",
          "CSAFPID-0003",
          "CSAFPID-0004",
          "CSAFPID-0005",
          "CSAFPID-0006",
          "CSAFPID-0007"
        ]
      },
      "references": [
        {
          "category": "external",
          "summary": "web.nvd.nist.gov",
          "url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2022-38465"
        },
        {
          "category": "external",
          "summary": "www.first.org",
          "url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:L/AC:L/PR:N/UI:N/S:C/C:H/I:H/A:H"
        }
      ],
      "remediations": [
        {
          "category": "mitigation",
          "details": "Use legacy (i.e., not TLS-based) PG/PC and HMI communication only in trusted network environments",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005",
            "CSAFPID-0006",
            "CSAFPID-0007"
          ]
        },
        {
          "category": "mitigation",
          "details": "Protect access to the TIA Portal project and CPU (including related memory cards) from unauthorized actors",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005",
            "CSAFPID-0006",
            "CSAFPID-0007"
          ]
        },
        {
          "category": "no_fix_planned",
          "details": "Currently no fix is planned",
          "product_ids": [
            "CSAFPID-0002"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "Update to V2.9.2 or later version, migrate project in TIA Portal to this version and redeploy.",
          "product_ids": [
            "CSAFPID-0001"
          ],
          "url": "https://support.industry.siemens.com/cs/ww/en/view/109773914/"
        },
        {
          "category": "vendor_fix",
          "details": "Within the project, configure the CPU to \n\"Only allow secure PG/PC and HMI communication\"",
          "product_ids": [
            "CSAFPID-0001"
          ],
          "url": "https://support.industry.siemens.com/cs/ww/en/view/109773914/"
        },
        {
          "category": "vendor_fix",
          "details": "Update to V21.9 or later version, migrate project in TIA Portal to this version and redeploy.",
          "product_ids": [
            "CSAFPID-0003"
          ],
          "url": "https://support.industry.siemens.com/cs/ww/en/view/109759122/"
        },
        {
          "category": "vendor_fix",
          "details": "Within the project, configure the CPU to \n\"Only allow secure PG/PC and HMI communication\"",
          "product_ids": [
            "CSAFPID-0003"
          ],
          "url": "https://support.industry.siemens.com/cs/ww/en/view/109759122/"
        },
        {
          "category": "vendor_fix",
          "details": "Update to V4.5.0 or later version, migrate project in TIA Portal to this version and redeploy.",
          "product_ids": [
            "CSAFPID-0004"
          ],
          "url": "https://support.industry.siemens.com/cs/ww/en/view/109793280/"
        },
        {
          "category": "vendor_fix",
          "details": "Within the project, configure the CPU to \n\"Only allow secure PG/PC and HMI communication\"",
          "product_ids": [
            "CSAFPID-0004"
          ],
          "url": "https://support.industry.siemens.com/cs/ww/en/view/109793280/"
        },
        {
          "category": "vendor_fix",
          "details": "Update to V2.9.2 or later version, migrate project in TIA Portal to this version and redeploy.",
          "product_ids": [
            "CSAFPID-0005"
          ],
          "url": "https://support.industry.siemens.com/cs/ww/en/view/109478459/"
        },
        {
          "category": "vendor_fix",
          "details": "Within the project, configure the CPU to \n\"Only allow secure PG/PC and HMI communication\"",
          "product_ids": [
            "CSAFPID-0005"
          ],
          "url": "https://support.industry.siemens.com/cs/ww/en/view/109478459/"
        },
        {
          "category": "vendor_fix",
          "details": "Update to V21.9 or later version, migrate project in TIA Portal to this version and redeploy.",
          "product_ids": [
            "CSAFPID-0006"
          ],
          "url": "https://support.industry.siemens.com/cs/ww/en/view/109478528/"
        },
        {
          "category": "vendor_fix",
          "details": "Within the project, configure the CPU to \n\"Only allow secure PG/PC and HMI communication\"",
          "product_ids": [
            "CSAFPID-0006"
          ],
          "url": "https://support.industry.siemens.com/cs/ww/en/view/109478528/"
        },
        {
          "category": "vendor_fix",
          "details": "Update to V4.0 or later version, migrate project in TIA Portal to the corresponding version and redeploy.",
          "product_ids": [
            "CSAFPID-0007"
          ],
          "url": "https://support.industry.siemens.com/cs/ww/en/view/109795016/"
        },
        {
          "category": "vendor_fix",
          "details": "Within the project, configure the CPU to \n\"Only allow secure PG/PC and HMI communication\"",
          "product_ids": [
            "CSAFPID-0007"
          ],
          "url": "https://support.industry.siemens.com/cs/ww/en/view/109795016/"
        },
        {
          "category": "mitigation",
          "details": "As a general security measure, Siemens strongly recommends to protect network access to devices with appropriate mechanisms. In order to operate the devices in a protected IT environment, Siemens recommends to configure the environment according to Siemens\u0027 operational guidelines for Industrial Security (Download: \nhttps://www.siemens.com/cert/operational-guidelines-industrial-security), and to follow the recommendations in the product manuals.\nAdditional information on Industrial Security by Siemens can be found at: \nhttps://www.siemens.com/industrialsecurity",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005",
            "CSAFPID-0006",
            "CSAFPID-0007"
          ]
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "baseScore": 9.3,
            "baseSeverity": "CRITICAL",
            "vectorString": "CVSS:3.1/AV:L/AC:L/PR:N/UI:N/S:C/C:H/I:H/A:H/E:P/RL:O/RC:C",
            "version": "3.1"
          },
          "products": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005",
            "CSAFPID-0006",
            "CSAFPID-0007"
          ]
        }
      ],
      "title": "CVE-2022-38465"
    }
  ]
}