cve-2016-8370
Vulnerability from cvelistv5
Published
2017-02-13 21:00
Modified
2024-08-06 02:20
Severity ?
Summary
An issue was discovered in Mitsubishi Electric Automation MELSEC-Q series Ethernet interface modules QJ71E71-100, all versions, QJ71E71-B5, all versions, and QJ71E71-B2, all versions. Weakly encrypted passwords are transmitted to a MELSEC-Q PLC.
References
Impacted products
Vendor Product Version
n/a Mitsubishi Electric MELSEC-Q Series Ethernet Interface Module Version: Mitsubishi Electric MELSEC-Q Series Ethernet Interface Module
Show details on NVD website


{
  "containers": {
    "adp": [
      {
        "providerMetadata": {
          "dateUpdated": "2024-08-06T02:20:30.810Z",
          "orgId": "af854a3a-2127-422b-91ae-364da2661108",
          "shortName": "CVE"
        },
        "references": [
          {
            "tags": [
              "x_refsource_MISC",
              "x_transferred"
            ],
            "url": "https://ics-cert.us-cert.gov/advisories/ICSA-16-336-03"
          },
          {
            "name": "94632",
            "tags": [
              "vdb-entry",
              "x_refsource_BID",
              "x_transferred"
            ],
            "url": "http://www.securityfocus.com/bid/94632"
          }
        ],
        "title": "CVE Program Container"
      }
    ],
    "cna": {
      "affected": [
        {
          "product": "Mitsubishi Electric MELSEC-Q Series Ethernet Interface Module",
          "vendor": "n/a",
          "versions": [
            {
              "status": "affected",
              "version": "Mitsubishi Electric MELSEC-Q Series Ethernet Interface Module"
            }
          ]
        }
      ],
      "datePublic": "2017-02-13T00:00:00",
      "descriptions": [
        {
          "lang": "en",
          "value": "An issue was discovered in Mitsubishi Electric Automation MELSEC-Q series Ethernet interface modules QJ71E71-100, all versions, QJ71E71-B5, all versions, and QJ71E71-B2, all versions. Weakly encrypted passwords are transmitted to a MELSEC-Q PLC."
        }
      ],
      "problemTypes": [
        {
          "descriptions": [
            {
              "description": "Mitsubishi Electric MELSEC-Q Series Ethernet Interface Module weak encryption",
              "lang": "en",
              "type": "text"
            }
          ]
        }
      ],
      "providerMetadata": {
        "dateUpdated": "2017-02-14T10:57:01",
        "orgId": "7d14cffa-0d7d-4270-9dc0-52cabd5a23a6",
        "shortName": "icscert"
      },
      "references": [
        {
          "tags": [
            "x_refsource_MISC"
          ],
          "url": "https://ics-cert.us-cert.gov/advisories/ICSA-16-336-03"
        },
        {
          "name": "94632",
          "tags": [
            "vdb-entry",
            "x_refsource_BID"
          ],
          "url": "http://www.securityfocus.com/bid/94632"
        }
      ],
      "x_legacyV4Record": {
        "CVE_data_meta": {
          "ASSIGNER": "ics-cert@hq.dhs.gov",
          "ID": "CVE-2016-8370",
          "STATE": "PUBLIC"
        },
        "affects": {
          "vendor": {
            "vendor_data": [
              {
                "product": {
                  "product_data": [
                    {
                      "product_name": "Mitsubishi Electric MELSEC-Q Series Ethernet Interface Module",
                      "version": {
                        "version_data": [
                          {
                            "version_value": "Mitsubishi Electric MELSEC-Q Series Ethernet Interface Module"
                          }
                        ]
                      }
                    }
                  ]
                },
                "vendor_name": "n/a"
              }
            ]
          }
        },
        "data_format": "MITRE",
        "data_type": "CVE",
        "data_version": "4.0",
        "description": {
          "description_data": [
            {
              "lang": "eng",
              "value": "An issue was discovered in Mitsubishi Electric Automation MELSEC-Q series Ethernet interface modules QJ71E71-100, all versions, QJ71E71-B5, all versions, and QJ71E71-B2, all versions. Weakly encrypted passwords are transmitted to a MELSEC-Q PLC."
            }
          ]
        },
        "problemtype": {
          "problemtype_data": [
            {
              "description": [
                {
                  "lang": "eng",
                  "value": "Mitsubishi Electric MELSEC-Q Series Ethernet Interface Module weak encryption"
                }
              ]
            }
          ]
        },
        "references": {
          "reference_data": [
            {
              "name": "https://ics-cert.us-cert.gov/advisories/ICSA-16-336-03",
              "refsource": "MISC",
              "url": "https://ics-cert.us-cert.gov/advisories/ICSA-16-336-03"
            },
            {
              "name": "94632",
              "refsource": "BID",
              "url": "http://www.securityfocus.com/bid/94632"
            }
          ]
        }
      }
    }
  },
  "cveMetadata": {
    "assignerOrgId": "7d14cffa-0d7d-4270-9dc0-52cabd5a23a6",
    "assignerShortName": "icscert",
    "cveId": "CVE-2016-8370",
    "datePublished": "2017-02-13T21:00:00",
    "dateReserved": "2016-09-28T00:00:00",
    "dateUpdated": "2024-08-06T02:20:30.810Z",
    "state": "PUBLISHED"
  },
  "dataType": "CVE_RECORD",
  "dataVersion": "5.1"
}

cve-2016-8368
Vulnerability from cvelistv5
Published
2017-02-13 21:00
Modified
2024-08-06 02:20
Severity ?
Summary
An issue was discovered in Mitsubishi Electric Automation MELSEC-Q series Ethernet interface modules QJ71E71-100, all versions, QJ71E71-B5, all versions, and QJ71E71-B2, all versions. The affected Ethernet interface module is connected to a MELSEC-Q PLC, which may allow a remote attacker to connect to the PLC via Port 5002/TCP and cause a denial of service, requiring the PLC to be reset to resume operation. This is caused by an Unrestricted Externally Accessible Lock.
References
Impacted products
Vendor Product Version
n/a Mitsubishi Electric MELSEC-Q Series Ethernet Interface Module Version: Mitsubishi Electric MELSEC-Q Series Ethernet Interface Module
Show details on NVD website


{
  "containers": {
    "adp": [
      {
        "providerMetadata": {
          "dateUpdated": "2024-08-06T02:20:31.217Z",
          "orgId": "af854a3a-2127-422b-91ae-364da2661108",
          "shortName": "CVE"
        },
        "references": [
          {
            "tags": [
              "x_refsource_MISC",
              "x_transferred"
            ],
            "url": "https://ics-cert.us-cert.gov/advisories/ICSA-16-336-03"
          },
          {
            "name": "94632",
            "tags": [
              "vdb-entry",
              "x_refsource_BID",
              "x_transferred"
            ],
            "url": "http://www.securityfocus.com/bid/94632"
          }
        ],
        "title": "CVE Program Container"
      }
    ],
    "cna": {
      "affected": [
        {
          "product": "Mitsubishi Electric MELSEC-Q Series Ethernet Interface Module",
          "vendor": "n/a",
          "versions": [
            {
              "status": "affected",
              "version": "Mitsubishi Electric MELSEC-Q Series Ethernet Interface Module"
            }
          ]
        }
      ],
      "datePublic": "2017-02-13T00:00:00",
      "descriptions": [
        {
          "lang": "en",
          "value": "An issue was discovered in Mitsubishi Electric Automation MELSEC-Q series Ethernet interface modules QJ71E71-100, all versions, QJ71E71-B5, all versions, and QJ71E71-B2, all versions. The affected Ethernet interface module is connected to a MELSEC-Q PLC, which may allow a remote attacker to connect to the PLC via Port 5002/TCP and cause a denial of service, requiring the PLC to be reset to resume operation. This is caused by an Unrestricted Externally Accessible Lock."
        }
      ],
      "problemTypes": [
        {
          "descriptions": [
            {
              "description": "Mitsubishi Electric MELSEC-Q Series Ethernet Interface Module Unrestricted Externally Accessible Lock",
              "lang": "en",
              "type": "text"
            }
          ]
        }
      ],
      "providerMetadata": {
        "dateUpdated": "2017-02-14T10:57:01",
        "orgId": "7d14cffa-0d7d-4270-9dc0-52cabd5a23a6",
        "shortName": "icscert"
      },
      "references": [
        {
          "tags": [
            "x_refsource_MISC"
          ],
          "url": "https://ics-cert.us-cert.gov/advisories/ICSA-16-336-03"
        },
        {
          "name": "94632",
          "tags": [
            "vdb-entry",
            "x_refsource_BID"
          ],
          "url": "http://www.securityfocus.com/bid/94632"
        }
      ],
      "x_legacyV4Record": {
        "CVE_data_meta": {
          "ASSIGNER": "ics-cert@hq.dhs.gov",
          "ID": "CVE-2016-8368",
          "STATE": "PUBLIC"
        },
        "affects": {
          "vendor": {
            "vendor_data": [
              {
                "product": {
                  "product_data": [
                    {
                      "product_name": "Mitsubishi Electric MELSEC-Q Series Ethernet Interface Module",
                      "version": {
                        "version_data": [
                          {
                            "version_value": "Mitsubishi Electric MELSEC-Q Series Ethernet Interface Module"
                          }
                        ]
                      }
                    }
                  ]
                },
                "vendor_name": "n/a"
              }
            ]
          }
        },
        "data_format": "MITRE",
        "data_type": "CVE",
        "data_version": "4.0",
        "description": {
          "description_data": [
            {
              "lang": "eng",
              "value": "An issue was discovered in Mitsubishi Electric Automation MELSEC-Q series Ethernet interface modules QJ71E71-100, all versions, QJ71E71-B5, all versions, and QJ71E71-B2, all versions. The affected Ethernet interface module is connected to a MELSEC-Q PLC, which may allow a remote attacker to connect to the PLC via Port 5002/TCP and cause a denial of service, requiring the PLC to be reset to resume operation. This is caused by an Unrestricted Externally Accessible Lock."
            }
          ]
        },
        "problemtype": {
          "problemtype_data": [
            {
              "description": [
                {
                  "lang": "eng",
                  "value": "Mitsubishi Electric MELSEC-Q Series Ethernet Interface Module Unrestricted Externally Accessible Lock"
                }
              ]
            }
          ]
        },
        "references": {
          "reference_data": [
            {
              "name": "https://ics-cert.us-cert.gov/advisories/ICSA-16-336-03",
              "refsource": "MISC",
              "url": "https://ics-cert.us-cert.gov/advisories/ICSA-16-336-03"
            },
            {
              "name": "94632",
              "refsource": "BID",
              "url": "http://www.securityfocus.com/bid/94632"
            }
          ]
        }
      }
    }
  },
  "cveMetadata": {
    "assignerOrgId": "7d14cffa-0d7d-4270-9dc0-52cabd5a23a6",
    "assignerShortName": "icscert",
    "cveId": "CVE-2016-8368",
    "datePublished": "2017-02-13T21:00:00",
    "dateReserved": "2016-09-28T00:00:00",
    "dateUpdated": "2024-08-06T02:20:31.217Z",
    "state": "PUBLISHED"
  },
  "dataType": "CVE_RECORD",
  "dataVersion": "5.1"
}

Vulnerability from fkie_nvd
Published
2017-02-13 21:59
Modified
2024-11-21 02:59
Summary
An issue was discovered in Mitsubishi Electric Automation MELSEC-Q series Ethernet interface modules QJ71E71-100, all versions, QJ71E71-B5, all versions, and QJ71E71-B2, all versions. The affected Ethernet interface module is connected to a MELSEC-Q PLC, which may allow a remote attacker to connect to the PLC via Port 5002/TCP and cause a denial of service, requiring the PLC to be reset to resume operation. This is caused by an Unrestricted Externally Accessible Lock.
References



{
  "configurations": [
    {
      "nodes": [
        {
          "cpeMatch": [
            {
              "criteria": "cpe:2.3:o:mitsubishielectric:qj71e71-100_firmware:-:*:*:*:*:*:*:*",
              "matchCriteriaId": "B02D732B-25E3-4D8A-872B-EC655195DE44",
              "vulnerable": true
            }
          ],
          "negate": false,
          "operator": "OR"
        },
        {
          "cpeMatch": [
            {
              "criteria": "cpe:2.3:h:mitsubishielectric:qj71e71-100:-:*:*:*:*:*:*:*",
              "matchCriteriaId": "6FD1EB30-B1FC-49CC-97D7-739AA5E92E86",
              "vulnerable": false
            }
          ],
          "negate": false,
          "operator": "OR"
        }
      ],
      "operator": "AND"
    },
    {
      "nodes": [
        {
          "cpeMatch": [
            {
              "criteria": "cpe:2.3:o:mitsubishielectric:qj71e71-b5_firmware:-:*:*:*:*:*:*:*",
              "matchCriteriaId": "579FA375-1A72-4A5D-BC3E-285CBA5BD1A2",
              "vulnerable": true
            }
          ],
          "negate": false,
          "operator": "OR"
        },
        {
          "cpeMatch": [
            {
              "criteria": "cpe:2.3:h:mitsubishielectric:qj71e71-b5:-:*:*:*:*:*:*:*",
              "matchCriteriaId": "E6C571AE-9A2B-4673-90C1-A369B91E74FD",
              "vulnerable": false
            }
          ],
          "negate": false,
          "operator": "OR"
        }
      ],
      "operator": "AND"
    },
    {
      "nodes": [
        {
          "cpeMatch": [
            {
              "criteria": "cpe:2.3:o:mitsubishielectric:qj71e71-b2_firmware:-:*:*:*:*:*:*:*",
              "matchCriteriaId": "2DA33198-3964-490A-B4CE-388FC4C585FE",
              "vulnerable": true
            }
          ],
          "negate": false,
          "operator": "OR"
        },
        {
          "cpeMatch": [
            {
              "criteria": "cpe:2.3:h:mitsubishielectric:qj71e71-b2:-:*:*:*:*:*:*:*",
              "matchCriteriaId": "DCB98436-7C3D-480C-927B-1D55DB1404B7",
              "vulnerable": false
            }
          ],
          "negate": false,
          "operator": "OR"
        }
      ],
      "operator": "AND"
    }
  ],
  "cveTags": [],
  "descriptions": [
    {
      "lang": "en",
      "value": "An issue was discovered in Mitsubishi Electric Automation MELSEC-Q series Ethernet interface modules QJ71E71-100, all versions, QJ71E71-B5, all versions, and QJ71E71-B2, all versions. The affected Ethernet interface module is connected to a MELSEC-Q PLC, which may allow a remote attacker to connect to the PLC via Port 5002/TCP and cause a denial of service, requiring the PLC to be reset to resume operation. This is caused by an Unrestricted Externally Accessible Lock."
    },
    {
      "lang": "es",
      "value": "Ha sido descubierto un problema en las series Mitsubishi Electric Automation MELSEC-Q en m\u00f3dulos de interfaz Ethernet QJ71E71-100, todas las versiones, QJ71E71-B5, todas las versiones y QJ71E71-B2, todas las versiones. El m\u00f3dulo de interfaz Ethernet afectado est\u00e1 conectado a MELSEC-Q PLC, lo que puede permitir a un atacante remoto conectarse al PLC a trav\u00e9s de Port 5002/TCP y provocar una denegaci\u00f3n de servicio, requiriendo que el PLC sea reseteado para continuar operando. Esto se produce por un Unrestricted Externally Accessible Lock."
    }
  ],
  "id": "CVE-2016-8368",
  "lastModified": "2024-11-21T02:59:14.183",
  "metrics": {
    "cvssMetricV2": [
      {
        "acInsufInfo": false,
        "baseSeverity": "MEDIUM",
        "cvssData": {
          "accessComplexity": "LOW",
          "accessVector": "NETWORK",
          "authentication": "NONE",
          "availabilityImpact": "PARTIAL",
          "baseScore": 5.0,
          "confidentialityImpact": "NONE",
          "integrityImpact": "NONE",
          "vectorString": "AV:N/AC:L/Au:N/C:N/I:N/A:P",
          "version": "2.0"
        },
        "exploitabilityScore": 10.0,
        "impactScore": 2.9,
        "obtainAllPrivilege": false,
        "obtainOtherPrivilege": false,
        "obtainUserPrivilege": false,
        "source": "nvd@nist.gov",
        "type": "Primary",
        "userInteractionRequired": false
      }
    ],
    "cvssMetricV31": [
      {
        "cvssData": {
          "attackComplexity": "LOW",
          "attackVector": "NETWORK",
          "availabilityImpact": "HIGH",
          "baseScore": 8.6,
          "baseSeverity": "HIGH",
          "confidentialityImpact": "NONE",
          "integrityImpact": "NONE",
          "privilegesRequired": "NONE",
          "scope": "CHANGED",
          "userInteraction": "NONE",
          "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:C/C:N/I:N/A:H",
          "version": "3.1"
        },
        "exploitabilityScore": 3.9,
        "impactScore": 4.0,
        "source": "nvd@nist.gov",
        "type": "Primary"
      }
    ]
  },
  "published": "2017-02-13T21:59:01.173",
  "references": [
    {
      "source": "ics-cert@hq.dhs.gov",
      "tags": [
        "Third Party Advisory",
        "VDB Entry"
      ],
      "url": "http://www.securityfocus.com/bid/94632"
    },
    {
      "source": "ics-cert@hq.dhs.gov",
      "tags": [
        "Mitigation",
        "Third Party Advisory",
        "US Government Resource"
      ],
      "url": "https://ics-cert.us-cert.gov/advisories/ICSA-16-336-03"
    },
    {
      "source": "af854a3a-2127-422b-91ae-364da2661108",
      "tags": [
        "Third Party Advisory",
        "VDB Entry"
      ],
      "url": "http://www.securityfocus.com/bid/94632"
    },
    {
      "source": "af854a3a-2127-422b-91ae-364da2661108",
      "tags": [
        "Mitigation",
        "Third Party Advisory",
        "US Government Resource"
      ],
      "url": "https://ics-cert.us-cert.gov/advisories/ICSA-16-336-03"
    }
  ],
  "sourceIdentifier": "ics-cert@hq.dhs.gov",
  "vulnStatus": "Modified",
  "weaknesses": [
    {
      "description": [
        {
          "lang": "en",
          "value": "CWE-662"
        }
      ],
      "source": "nvd@nist.gov",
      "type": "Primary"
    }
  ]
}

Vulnerability from fkie_nvd
Published
2017-02-13 21:59
Modified
2024-11-21 02:59
Summary
An issue was discovered in Mitsubishi Electric Automation MELSEC-Q series Ethernet interface modules QJ71E71-100, all versions, QJ71E71-B5, all versions, and QJ71E71-B2, all versions. Weakly encrypted passwords are transmitted to a MELSEC-Q PLC.
References



{
  "configurations": [
    {
      "nodes": [
        {
          "cpeMatch": [
            {
              "criteria": "cpe:2.3:o:mitsubishielectric:qj71e71-100_firmware:-:*:*:*:*:*:*:*",
              "matchCriteriaId": "B02D732B-25E3-4D8A-872B-EC655195DE44",
              "vulnerable": true
            }
          ],
          "negate": false,
          "operator": "OR"
        },
        {
          "cpeMatch": [
            {
              "criteria": "cpe:2.3:h:mitsubishielectric:qj71e71-100:-:*:*:*:*:*:*:*",
              "matchCriteriaId": "6FD1EB30-B1FC-49CC-97D7-739AA5E92E86",
              "vulnerable": false
            }
          ],
          "negate": false,
          "operator": "OR"
        }
      ],
      "operator": "AND"
    },
    {
      "nodes": [
        {
          "cpeMatch": [
            {
              "criteria": "cpe:2.3:o:mitsubishielectric:qj71e71-b5_firmware:-:*:*:*:*:*:*:*",
              "matchCriteriaId": "579FA375-1A72-4A5D-BC3E-285CBA5BD1A2",
              "vulnerable": true
            }
          ],
          "negate": false,
          "operator": "OR"
        },
        {
          "cpeMatch": [
            {
              "criteria": "cpe:2.3:h:mitsubishielectric:qj71e71-b5:-:*:*:*:*:*:*:*",
              "matchCriteriaId": "E6C571AE-9A2B-4673-90C1-A369B91E74FD",
              "vulnerable": false
            }
          ],
          "negate": false,
          "operator": "OR"
        }
      ],
      "operator": "AND"
    },
    {
      "nodes": [
        {
          "cpeMatch": [
            {
              "criteria": "cpe:2.3:o:mitsubishielectric:qj71e71-b2_firmware:-:*:*:*:*:*:*:*",
              "matchCriteriaId": "2DA33198-3964-490A-B4CE-388FC4C585FE",
              "vulnerable": true
            }
          ],
          "negate": false,
          "operator": "OR"
        },
        {
          "cpeMatch": [
            {
              "criteria": "cpe:2.3:h:mitsubishielectric:qj71e71-b2:-:*:*:*:*:*:*:*",
              "matchCriteriaId": "DCB98436-7C3D-480C-927B-1D55DB1404B7",
              "vulnerable": false
            }
          ],
          "negate": false,
          "operator": "OR"
        }
      ],
      "operator": "AND"
    }
  ],
  "cveTags": [],
  "descriptions": [
    {
      "lang": "en",
      "value": "An issue was discovered in Mitsubishi Electric Automation MELSEC-Q series Ethernet interface modules QJ71E71-100, all versions, QJ71E71-B5, all versions, and QJ71E71-B2, all versions. Weakly encrypted passwords are transmitted to a MELSEC-Q PLC."
    },
    {
      "lang": "es",
      "value": "Ha sido descubierto un problema en las series Mitsubishi Electric Automation MELSEC-Q en m\u00f3dulos de interfaz Ethernet QJ71E71-100, todas las versiones, QJ71E71-B5, todas las versiones y QJ71E71-B2, todas las versiones. Las contrase\u00f1as cifradas d\u00e9bilmente son transmitidas a un MELSEC-Q PLC."
    }
  ],
  "id": "CVE-2016-8370",
  "lastModified": "2024-11-21T02:59:14.433",
  "metrics": {
    "cvssMetricV2": [
      {
        "acInsufInfo": false,
        "baseSeverity": "MEDIUM",
        "cvssData": {
          "accessComplexity": "LOW",
          "accessVector": "NETWORK",
          "authentication": "NONE",
          "availabilityImpact": "NONE",
          "baseScore": 5.0,
          "confidentialityImpact": "PARTIAL",
          "integrityImpact": "NONE",
          "vectorString": "AV:N/AC:L/Au:N/C:P/I:N/A:N",
          "version": "2.0"
        },
        "exploitabilityScore": 10.0,
        "impactScore": 2.9,
        "obtainAllPrivilege": false,
        "obtainOtherPrivilege": false,
        "obtainUserPrivilege": false,
        "source": "nvd@nist.gov",
        "type": "Primary",
        "userInteractionRequired": false
      }
    ],
    "cvssMetricV31": [
      {
        "cvssData": {
          "attackComplexity": "LOW",
          "attackVector": "NETWORK",
          "availabilityImpact": "NONE",
          "baseScore": 7.5,
          "baseSeverity": "HIGH",
          "confidentialityImpact": "HIGH",
          "integrityImpact": "NONE",
          "privilegesRequired": "NONE",
          "scope": "UNCHANGED",
          "userInteraction": "NONE",
          "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N",
          "version": "3.1"
        },
        "exploitabilityScore": 3.9,
        "impactScore": 3.6,
        "source": "nvd@nist.gov",
        "type": "Primary"
      }
    ]
  },
  "published": "2017-02-13T21:59:01.220",
  "references": [
    {
      "source": "ics-cert@hq.dhs.gov",
      "tags": [
        "Third Party Advisory",
        "VDB Entry"
      ],
      "url": "http://www.securityfocus.com/bid/94632"
    },
    {
      "source": "ics-cert@hq.dhs.gov",
      "tags": [
        "Mitigation",
        "Third Party Advisory",
        "US Government Resource"
      ],
      "url": "https://ics-cert.us-cert.gov/advisories/ICSA-16-336-03"
    },
    {
      "source": "af854a3a-2127-422b-91ae-364da2661108",
      "tags": [
        "Third Party Advisory",
        "VDB Entry"
      ],
      "url": "http://www.securityfocus.com/bid/94632"
    },
    {
      "source": "af854a3a-2127-422b-91ae-364da2661108",
      "tags": [
        "Mitigation",
        "Third Party Advisory",
        "US Government Resource"
      ],
      "url": "https://ics-cert.us-cert.gov/advisories/ICSA-16-336-03"
    }
  ],
  "sourceIdentifier": "ics-cert@hq.dhs.gov",
  "vulnStatus": "Modified",
  "weaknesses": [
    {
      "description": [
        {
          "lang": "en",
          "value": "CWE-327"
        }
      ],
      "source": "nvd@nist.gov",
      "type": "Primary"
    }
  ]
}