Search criteria
5 vulnerabilities by sauter-controls
CVE-2023-0053 (GCVE-0-2023-0053)
Vulnerability from cvelistv5 – Published: 2023-03-02 00:15 – Updated: 2025-01-16 21:55
VLAI?
Summary
SAUTER Controls Nova 200–220 Series with firmware version 3.3-006 and
prior and BACnetstac version 4.2.1 and prior have only FTP and Telnet
available for device management. Any sensitive information communicated
through these protocols, such as credentials, is sent in cleartext. An
attacker could obtain sensitive information such as user credentials to
gain access to the system.
Severity ?
7.5 (High)
CWE
- CWE-319 - Cleartext Transmission of Sensitive Information
Assigner
References
Impacted products
| Vendor | Product | Version | |||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| SAUTER Controls | Nova 220 (EYK220F001) DDC with BACnet connection |
Affected:
Firmware all versions , ≤ 3.3-006
(custom)
Affected: BACnetstac all versions , ≤ 4.2.1 (custom) |
|||||||||||||||||
|
|||||||||||||||||||
Credits
Jairo Alonso Ortiz, Aarón Flecha Menéndez and Iñaki Lázaro Ayanz of S21Sec
{
"containers": {
"adp": [
{
"providerMetadata": {
"dateUpdated": "2024-08-02T04:54:32.601Z",
"orgId": "af854a3a-2127-422b-91ae-364da2661108",
"shortName": "CVE"
},
"references": [
{
"tags": [
"x_transferred"
],
"url": "https://www.cisa.gov/uscert/ics/advisories/icsa-23-012-05"
}
],
"title": "CVE Program Container"
},
{
"metrics": [
{
"other": {
"content": {
"id": "CVE-2023-0053",
"options": [
{
"Exploitation": "none"
},
{
"Automatable": "yes"
},
{
"Technical Impact": "partial"
}
],
"role": "CISA Coordinator",
"timestamp": "2025-01-16T20:56:33.933472Z",
"version": "2.0.3"
},
"type": "ssvc"
}
}
],
"providerMetadata": {
"dateUpdated": "2025-01-16T21:55:31.611Z",
"orgId": "134c704f-9b21-4f2e-91b3-4a467353bcc0",
"shortName": "CISA-ADP"
},
"title": "CISA ADP Vulnrichment"
}
],
"cna": {
"affected": [
{
"defaultStatus": "unaffected",
"product": "Nova 220 (EYK220F001) DDC with BACnet connection",
"vendor": "SAUTER Controls",
"versions": [
{
"lessThanOrEqual": "3.3-006",
"status": "affected",
"version": "Firmware all versions",
"versionType": "custom"
},
{
"lessThanOrEqual": "4.2.1",
"status": "affected",
"version": "BACnetstac all versions",
"versionType": "custom"
}
]
},
{
"defaultStatus": "unaffected",
"product": "Nova 230 (EYK230F001) DDC with BACnet connection",
"vendor": "SAUTER Controls",
"versions": [
{
"lessThanOrEqual": "3.3-006",
"status": "affected",
"version": "Firmware all versions",
"versionType": "custom"
},
{
"lessThanOrEqual": "4.2.1",
"status": "affected",
"version": "BACnetstac all versions",
"versionType": "custom"
}
]
},
{
"defaultStatus": "unaffected",
"product": "Nova 106 (EYK300F001) BACnet communication card",
"vendor": "SAUTER Controls",
"versions": [
{
"lessThanOrEqual": "3.3-006",
"status": "affected",
"version": "Firmware all versions",
"versionType": "custom"
},
{
"lessThanOrEqual": "4.2.1",
"status": "affected",
"version": "BACnetstac all versions",
"versionType": "custom"
}
]
},
{
"defaultStatus": "unaffected",
"product": "moduNet300 (EY-AM300F001, EY-AM300F002)",
"vendor": "SAUTER Controls",
"versions": [
{
"lessThanOrEqual": "3.3-006",
"status": "affected",
"version": "Firmware all versions",
"versionType": "custom"
},
{
"lessThanOrEqual": "4.2.1",
"status": "affected",
"version": "BACnetstac all versions",
"versionType": "custom"
}
]
}
],
"credits": [
{
"lang": "en",
"type": "reporter",
"user": "00000000-0000-4000-9000-000000000000",
"value": "Jairo Alonso Ortiz, Aar\u00f3n Flecha Men\u00e9ndez and I\u00f1aki L\u00e1zaro Ayanz of S21Sec"
}
],
"datePublic": "2023-01-12T18:15:00.000Z",
"descriptions": [
{
"lang": "en",
"supportingMedia": [
{
"base64": false,
"type": "text/html",
"value": "\u003cp\u003e\nSAUTER Controls Nova 200\u2013220 Series with firmware version 3.3-006 and \nprior and BACnetstac version 4.2.1 and prior have only FTP and Telnet \navailable for device management. Any sensitive information communicated \nthrough these protocols, such as credentials, is sent in cleartext. An \nattacker could obtain sensitive information such as user credentials to \ngain access to the system. \n\n\u003c/p\u003e"
}
],
"value": "SAUTER Controls Nova 200\u2013220 Series with firmware version 3.3-006 and \nprior and BACnetstac version 4.2.1 and prior have only FTP and Telnet \navailable for device management. Any sensitive information communicated \nthrough these protocols, such as credentials, is sent in cleartext. An \nattacker could obtain sensitive information such as user credentials to \ngain access to the system. \n\n\n\n"
}
],
"metrics": [
{
"cvssV3_1": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "NONE",
"baseScore": 7.5,
"baseSeverity": "HIGH",
"confidentialityImpact": "HIGH",
"integrityImpact": "NONE",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N",
"version": "3.1"
},
"format": "CVSS",
"scenarios": [
{
"lang": "en",
"value": "GENERAL"
}
]
}
],
"problemTypes": [
{
"descriptions": [
{
"cweId": "CWE-319",
"description": "CWE-319 Cleartext Transmission of Sensitive Information",
"lang": "en",
"type": "CWE"
}
]
}
],
"providerMetadata": {
"dateUpdated": "2023-10-26T23:18:13.533Z",
"orgId": "7d14cffa-0d7d-4270-9dc0-52cabd5a23a6",
"shortName": "icscert"
},
"references": [
{
"url": "https://www.cisa.gov/uscert/ics/advisories/icsa-23-012-05"
}
],
"source": {
"discovery": "EXTERNAL"
},
"title": "SAUTER Controls Nova 200\u2013220 Series Cleartext Transmission of Sensitive Information",
"workarounds": [
{
"lang": "en",
"supportingMedia": [
{
"base64": false,
"type": "text/html",
"value": "\n\u003cp\u003eSAUTER Controls has stated that this product line is no longer \nsupported, as it was discontinued in 2016. SAUTER Controls recommends \nusers take all necessary measures to protect the integrity of building \nautomation network access, using all appropriate means and policies to \nminimize risks. Sauter Controls recommends users evaluate and upgrade \nlegacy systems to current solutions where necessary. \u0026nbsp;\u003c/p\u003e\n\u003cp\u003eAffected users should contact \u003ca target=\"_blank\" rel=\"nofollow\" href=\"https://www.sauter-controls.com/\"\u003eSAUTER Controls\u003c/a\u003e\u0026nbsp;\u003cspan style=\"background-color: var(--wht);\"\u003efor instructions on upgrading legacy systems.\u003c/span\u003e\u003c/p\u003e"
}
],
"value": "SAUTER Controls has stated that this product line is no longer \nsupported, as it was discontinued in 2016. SAUTER Controls recommends \nusers take all necessary measures to protect the integrity of building \nautomation network access, using all appropriate means and policies to \nminimize risks. Sauter Controls recommends users evaluate and upgrade \nlegacy systems to current solutions where necessary. \u00a0\n\n\nAffected users should contact SAUTER Controls https://www.sauter-controls.com/ \u00a0for instructions on upgrading legacy systems.\n\n"
}
],
"x_generator": {
"engine": "VINCE 2.0.5",
"env": "prod",
"origin": "https://cveawg.mitre.org/api/cve/CVE-2023-0052"
}
}
},
"cveMetadata": {
"assignerOrgId": "7d14cffa-0d7d-4270-9dc0-52cabd5a23a6",
"assignerShortName": "icscert",
"cveId": "CVE-2023-0053",
"datePublished": "2023-03-02T00:15:49.817Z",
"dateReserved": "2023-01-04T16:24:06.705Z",
"dateUpdated": "2025-01-16T21:55:31.611Z",
"state": "PUBLISHED"
},
"dataType": "CVE_RECORD",
"dataVersion": "5.1"
}
CVE-2022-40190 (GCVE-0-2022-40190)
Vulnerability from cvelistv5 – Published: 2022-10-31 20:14 – Updated: 2025-04-16 17:43
VLAI?
Summary
SAUTER Controls moduWeb firmware version 2.7.1 is vulnerable to reflective cross-site scripting (XSS). The web application does not adequately sanitize request strings of malicious JavaScript. An attacker utilizing XSS could then execute malicious code in users’ browsers and steal sensitive information, including user credentials.
Severity ?
8.8 (High)
CWE
- CWE-79 - Cross-site Scripting (XSS)
Assigner
References
Impacted products
| Vendor | Product | Version | ||
|---|---|---|---|---|
| SAUTER Controls | moduWeb |
Affected:
firmware Version 2.7.1
|
Credits
Ithaca Labs of Odyssey Cyber Security reported this vulnerability.
{
"containers": {
"adp": [
{
"providerMetadata": {
"dateUpdated": "2024-08-03T12:14:39.857Z",
"orgId": "af854a3a-2127-422b-91ae-364da2661108",
"shortName": "CVE"
},
"references": [
{
"tags": [
"x_transferred"
],
"url": "https://www.cisa.gov/uscert/ics/advisories/icsa-22-300-02"
}
],
"title": "CVE Program Container"
},
{
"metrics": [
{
"other": {
"content": {
"id": "CVE-2022-40190",
"options": [
{
"Exploitation": "none"
},
{
"Automatable": "no"
},
{
"Technical Impact": "total"
}
],
"role": "CISA Coordinator",
"timestamp": "2025-04-16T17:26:09.761346Z",
"version": "2.0.3"
},
"type": "ssvc"
}
}
],
"providerMetadata": {
"dateUpdated": "2025-04-16T17:43:26.696Z",
"orgId": "134c704f-9b21-4f2e-91b3-4a467353bcc0",
"shortName": "CISA-ADP"
},
"title": "CISA ADP Vulnrichment"
}
],
"cna": {
"affected": [
{
"product": "moduWeb",
"vendor": "SAUTER Controls",
"versions": [
{
"status": "affected",
"version": "firmware Version 2.7.1"
}
]
}
],
"credits": [
{
"lang": "en",
"value": "Ithaca Labs of Odyssey Cyber Security reported this vulnerability."
}
],
"datePublic": "2022-10-27T00:00:00.000Z",
"descriptions": [
{
"lang": "en",
"value": "SAUTER Controls moduWeb firmware version 2.7.1 is vulnerable to reflective cross-site scripting (XSS). The web application does not adequately sanitize request strings of malicious JavaScript. An attacker utilizing XSS could then execute malicious code in users\u2019 browsers and steal sensitive information, including user credentials."
}
],
"metrics": [
{
"cvssV3_1": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 8.8,
"baseSeverity": "HIGH",
"confidentialityImpact": "HIGH",
"integrityImpact": "HIGH",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"userInteraction": "REQUIRED",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H",
"version": "3.1"
}
}
],
"problemTypes": [
{
"descriptions": [
{
"cweId": "CWE-79",
"description": "CWE-79 Cross-site Scripting (XSS)",
"lang": "en",
"type": "CWE"
}
]
}
],
"providerMetadata": {
"dateUpdated": "2022-10-31T00:00:00.000Z",
"orgId": "7d14cffa-0d7d-4270-9dc0-52cabd5a23a6",
"shortName": "icscert"
},
"references": [
{
"url": "https://www.cisa.gov/uscert/ics/advisories/icsa-22-300-02"
}
],
"source": {
"discovery": "UNKNOWN"
},
"x_generator": {
"engine": "Vulnogram 0.0.9"
}
}
},
"cveMetadata": {
"assignerOrgId": "7d14cffa-0d7d-4270-9dc0-52cabd5a23a6",
"assignerShortName": "icscert",
"cveId": "CVE-2022-40190",
"datePublished": "2022-10-31T20:14:59.780Z",
"dateReserved": "2022-09-29T00:00:00.000Z",
"dateUpdated": "2025-04-16T17:43:26.696Z",
"state": "PUBLISHED"
},
"dataType": "CVE_RECORD",
"dataVersion": "5.1"
}
CVE-2018-17912 (GCVE-0-2018-17912)
Vulnerability from cvelistv5 – Published: 2018-11-02 14:00 – Updated: 2024-08-05 11:01
VLAI?
Summary
An XXE vulnerability exists in CASE Suite Versions 3.10 and prior when processing parameter entities, which may allow remote file disclosure.
Severity ?
No CVSS data available.
CWE
- CWE-611 - IMPROPER RESTRICTION OF XML EXTERNAL ENTITY REFERENCE ('XXE') CWE-611
Assigner
References
| URL | Tags | |||||||
|---|---|---|---|---|---|---|---|---|
|
||||||||
Impacted products
| Vendor | Product | Version | ||
|---|---|---|---|---|
| unknown | CASE Suite |
Affected:
Versions 3.10 and prior
|
{
"containers": {
"adp": [
{
"providerMetadata": {
"dateUpdated": "2024-08-05T11:01:14.606Z",
"orgId": "af854a3a-2127-422b-91ae-364da2661108",
"shortName": "CVE"
},
"references": [
{
"name": "105804",
"tags": [
"vdb-entry",
"x_refsource_BID",
"x_transferred"
],
"url": "http://www.securityfocus.com/bid/105804"
},
{
"tags": [
"x_refsource_MISC",
"x_transferred"
],
"url": "https://ics-cert.us-cert.gov/advisories/ICSA-18-305-04"
}
],
"title": "CVE Program Container"
}
],
"cna": {
"affected": [
{
"product": "CASE Suite",
"vendor": "unknown",
"versions": [
{
"status": "affected",
"version": "Versions 3.10 and prior"
}
]
}
],
"datePublic": "2018-11-02T00:00:00",
"descriptions": [
{
"lang": "en",
"value": "An XXE vulnerability exists in CASE Suite Versions 3.10 and prior when processing parameter entities, which may allow remote file disclosure."
}
],
"problemTypes": [
{
"descriptions": [
{
"cweId": "CWE-611",
"description": "IMPROPER RESTRICTION OF XML EXTERNAL ENTITY REFERENCE (\u0027XXE\u0027) CWE-611",
"lang": "en",
"type": "CWE"
}
]
}
],
"providerMetadata": {
"dateUpdated": "2018-11-05T10:57:01",
"orgId": "7d14cffa-0d7d-4270-9dc0-52cabd5a23a6",
"shortName": "icscert"
},
"references": [
{
"name": "105804",
"tags": [
"vdb-entry",
"x_refsource_BID"
],
"url": "http://www.securityfocus.com/bid/105804"
},
{
"tags": [
"x_refsource_MISC"
],
"url": "https://ics-cert.us-cert.gov/advisories/ICSA-18-305-04"
}
],
"x_legacyV4Record": {
"CVE_data_meta": {
"ASSIGNER": "ics-cert@hq.dhs.gov",
"ID": "CVE-2018-17912",
"STATE": "PUBLIC"
},
"affects": {
"vendor": {
"vendor_data": [
{
"product": {
"product_data": [
{
"product_name": "CASE Suite",
"version": {
"version_data": [
{
"version_value": "Versions 3.10 and prior"
}
]
}
}
]
},
"vendor_name": "unknown"
}
]
}
},
"data_format": "MITRE",
"data_type": "CVE",
"data_version": "4.0",
"description": {
"description_data": [
{
"lang": "eng",
"value": "An XXE vulnerability exists in CASE Suite Versions 3.10 and prior when processing parameter entities, which may allow remote file disclosure."
}
]
},
"problemtype": {
"problemtype_data": [
{
"description": [
{
"lang": "eng",
"value": "IMPROPER RESTRICTION OF XML EXTERNAL ENTITY REFERENCE (\u0027XXE\u0027) CWE-611"
}
]
}
]
},
"references": {
"reference_data": [
{
"name": "105804",
"refsource": "BID",
"url": "http://www.securityfocus.com/bid/105804"
},
{
"name": "https://ics-cert.us-cert.gov/advisories/ICSA-18-305-04",
"refsource": "MISC",
"url": "https://ics-cert.us-cert.gov/advisories/ICSA-18-305-04"
}
]
}
}
}
},
"cveMetadata": {
"assignerOrgId": "7d14cffa-0d7d-4270-9dc0-52cabd5a23a6",
"assignerShortName": "icscert",
"cveId": "CVE-2018-17912",
"datePublished": "2018-11-02T14:00:00",
"dateReserved": "2018-10-02T00:00:00",
"dateUpdated": "2024-08-05T11:01:14.606Z",
"state": "PUBLISHED"
},
"dataType": "CVE_RECORD",
"dataVersion": "5.1"
}
CVE-2016-10224 (GCVE-0-2016-10224)
Vulnerability from cvelistv5 – Published: 2017-02-13 21:00 – Updated: 2024-08-06 03:14
VLAI?
Summary
An issue was discovered in Sauter NovaWeb web HMI. The application uses a protection mechanism that relies on the existence or values of a cookie, but it does not properly ensure that the cookie is valid for the associated user.
Severity ?
No CVSS data available.
CWE
- Sauter NovaWeb Web HMI Authentication Bypass Vulnerability
Assigner
References
| URL | Tags | ||||
|---|---|---|---|---|---|
|
|||||
Impacted products
| Vendor | Product | Version | ||
|---|---|---|---|---|
| n/a | Sauter NovaWeb Web HMI |
Affected:
Sauter NovaWeb Web HMI
|
{
"containers": {
"adp": [
{
"providerMetadata": {
"dateUpdated": "2024-08-06T03:14:42.878Z",
"orgId": "af854a3a-2127-422b-91ae-364da2661108",
"shortName": "CVE"
},
"references": [
{
"tags": [
"x_refsource_MISC",
"x_transferred"
],
"url": "https://ics-cert.us-cert.gov/advisories/ICSA-16-343-02"
}
],
"title": "CVE Program Container"
}
],
"cna": {
"affected": [
{
"product": "Sauter NovaWeb Web HMI",
"vendor": "n/a",
"versions": [
{
"status": "affected",
"version": "Sauter NovaWeb Web HMI"
}
]
}
],
"datePublic": "2017-02-13T00:00:00",
"descriptions": [
{
"lang": "en",
"value": "An issue was discovered in Sauter NovaWeb web HMI. The application uses a protection mechanism that relies on the existence or values of a cookie, but it does not properly ensure that the cookie is valid for the associated user."
}
],
"problemTypes": [
{
"descriptions": [
{
"description": "Sauter NovaWeb Web HMI Authentication Bypass Vulnerability",
"lang": "en",
"type": "text"
}
]
}
],
"providerMetadata": {
"dateUpdated": "2017-02-13T20:57:01",
"orgId": "7d14cffa-0d7d-4270-9dc0-52cabd5a23a6",
"shortName": "icscert"
},
"references": [
{
"tags": [
"x_refsource_MISC"
],
"url": "https://ics-cert.us-cert.gov/advisories/ICSA-16-343-02"
}
],
"x_legacyV4Record": {
"CVE_data_meta": {
"ASSIGNER": "ics-cert@hq.dhs.gov",
"ID": "CVE-2016-10224",
"STATE": "PUBLIC"
},
"affects": {
"vendor": {
"vendor_data": [
{
"product": {
"product_data": [
{
"product_name": "Sauter NovaWeb Web HMI",
"version": {
"version_data": [
{
"version_value": "Sauter NovaWeb Web HMI"
}
]
}
}
]
},
"vendor_name": "n/a"
}
]
}
},
"data_format": "MITRE",
"data_type": "CVE",
"data_version": "4.0",
"description": {
"description_data": [
{
"lang": "eng",
"value": "An issue was discovered in Sauter NovaWeb web HMI. The application uses a protection mechanism that relies on the existence or values of a cookie, but it does not properly ensure that the cookie is valid for the associated user."
}
]
},
"problemtype": {
"problemtype_data": [
{
"description": [
{
"lang": "eng",
"value": "Sauter NovaWeb Web HMI Authentication Bypass Vulnerability"
}
]
}
]
},
"references": {
"reference_data": [
{
"name": "https://ics-cert.us-cert.gov/advisories/ICSA-16-343-02",
"refsource": "MISC",
"url": "https://ics-cert.us-cert.gov/advisories/ICSA-16-343-02"
}
]
}
}
}
},
"cveMetadata": {
"assignerOrgId": "7d14cffa-0d7d-4270-9dc0-52cabd5a23a6",
"assignerShortName": "icscert",
"cveId": "CVE-2016-10224",
"datePublished": "2017-02-13T21:00:00",
"dateReserved": "2017-02-12T00:00:00",
"dateUpdated": "2024-08-06T03:14:42.878Z",
"state": "PUBLISHED"
},
"dataType": "CVE_RECORD",
"dataVersion": "5.1"
}
CVE-2015-7916 (GCVE-0-2015-7916)
Vulnerability from cvelistv5 – Published: 2016-02-06 02:00 – Updated: 2024-08-06 08:06
VLAI?
Summary
Cross-site scripting (XSS) vulnerability in Sauter EY-WS505F0x0 moduWeb Vision before 1.6.0 allows remote authenticated users to inject arbitrary web script or HTML via a crafted query.
Severity ?
No CVSS data available.
CWE
- n/a
Assigner
References
| URL | Tags | |||||||
|---|---|---|---|---|---|---|---|---|
|
||||||||
{
"containers": {
"adp": [
{
"providerMetadata": {
"dateUpdated": "2024-08-06T08:06:30.961Z",
"orgId": "af854a3a-2127-422b-91ae-364da2661108",
"shortName": "CVE"
},
"references": [
{
"name": "20160203 Sauter ModuWEB Vision SCADA vulnerabilities",
"tags": [
"mailing-list",
"x_refsource_FULLDISC",
"x_transferred"
],
"url": "http://seclists.org/fulldisclosure/2016/Feb/25"
},
{
"tags": [
"x_refsource_MISC",
"x_transferred"
],
"url": "https://ics-cert.us-cert.gov/advisories/ICSA-16-033-01"
}
],
"title": "CVE Program Container"
}
],
"cna": {
"affected": [
{
"product": "n/a",
"vendor": "n/a",
"versions": [
{
"status": "affected",
"version": "n/a"
}
]
}
],
"datePublic": "2016-02-02T00:00:00",
"descriptions": [
{
"lang": "en",
"value": "Cross-site scripting (XSS) vulnerability in Sauter EY-WS505F0x0 moduWeb Vision before 1.6.0 allows remote authenticated users to inject arbitrary web script or HTML via a crafted query."
}
],
"problemTypes": [
{
"descriptions": [
{
"description": "n/a",
"lang": "en",
"type": "text"
}
]
}
],
"providerMetadata": {
"dateUpdated": "2016-12-01T15:57:02",
"orgId": "7d14cffa-0d7d-4270-9dc0-52cabd5a23a6",
"shortName": "icscert"
},
"references": [
{
"name": "20160203 Sauter ModuWEB Vision SCADA vulnerabilities",
"tags": [
"mailing-list",
"x_refsource_FULLDISC"
],
"url": "http://seclists.org/fulldisclosure/2016/Feb/25"
},
{
"tags": [
"x_refsource_MISC"
],
"url": "https://ics-cert.us-cert.gov/advisories/ICSA-16-033-01"
}
],
"x_legacyV4Record": {
"CVE_data_meta": {
"ASSIGNER": "ics-cert@hq.dhs.gov",
"ID": "CVE-2015-7916",
"STATE": "PUBLIC"
},
"affects": {
"vendor": {
"vendor_data": [
{
"product": {
"product_data": [
{
"product_name": "n/a",
"version": {
"version_data": [
{
"version_value": "n/a"
}
]
}
}
]
},
"vendor_name": "n/a"
}
]
}
},
"data_format": "MITRE",
"data_type": "CVE",
"data_version": "4.0",
"description": {
"description_data": [
{
"lang": "eng",
"value": "Cross-site scripting (XSS) vulnerability in Sauter EY-WS505F0x0 moduWeb Vision before 1.6.0 allows remote authenticated users to inject arbitrary web script or HTML via a crafted query."
}
]
},
"problemtype": {
"problemtype_data": [
{
"description": [
{
"lang": "eng",
"value": "n/a"
}
]
}
]
},
"references": {
"reference_data": [
{
"name": "20160203 Sauter ModuWEB Vision SCADA vulnerabilities",
"refsource": "FULLDISC",
"url": "http://seclists.org/fulldisclosure/2016/Feb/25"
},
{
"name": "https://ics-cert.us-cert.gov/advisories/ICSA-16-033-01",
"refsource": "MISC",
"url": "https://ics-cert.us-cert.gov/advisories/ICSA-16-033-01"
}
]
}
}
}
},
"cveMetadata": {
"assignerOrgId": "7d14cffa-0d7d-4270-9dc0-52cabd5a23a6",
"assignerShortName": "icscert",
"cveId": "CVE-2015-7916",
"datePublished": "2016-02-06T02:00:00",
"dateReserved": "2015-10-22T00:00:00",
"dateUpdated": "2024-08-06T08:06:30.961Z",
"state": "PUBLISHED"
},
"dataType": "CVE_RECORD",
"dataVersion": "5.1"
}