CVE-2019-10938 (GCVE-0-2019-10938)
Vulnerability from cvelistv5
Published
2019-08-02 13:54
Modified
2024-08-04 22:40
Severity ?
Summary
A vulnerability has been identified in SIPROTEC 5 devices with CPU variants CP200 (All versions < V7.59), SIPROTEC 5 devices with CPU variants CP300 and CP100 (All versions < V8.01), Siemens Power Meters Series 9410 (All versions < V2.2.1), Siemens Power Meters Series 9810 (All versions). An unauthenticated attacker with network access to the device could potentially insert arbitrary code which is executed before firmware verification in the device. At the time of advisory publication no public exploitation of this security vulnerability was known.
Show details on NVD website


{
   containers: {
      adp: [
         {
            providerMetadata: {
               dateUpdated: "2024-08-04T22:40:15.404Z",
               orgId: "af854a3a-2127-422b-91ae-364da2661108",
               shortName: "CVE",
            },
            references: [
               {
                  tags: [
                     "x_refsource_MISC",
                     "x_transferred",
                  ],
                  url: "https://cert-portal.siemens.com/productcert/pdf/ssa-632562.pdf",
               },
               {
                  tags: [
                     "x_refsource_CONFIRM",
                     "x_transferred",
                  ],
                  url: "https://cert-portal.siemens.com/productcert/pdf/ssa-352504.pdf",
               },
            ],
            title: "CVE Program Container",
         },
      ],
      cna: {
         affected: [
            {
               product: "SIPROTEC 5 devices with CPU variants CP200",
               vendor: "Siemens AG",
               versions: [
                  {
                     status: "affected",
                     version: "All versions < V7.59",
                  },
               ],
            },
            {
               product: "SIPROTEC 5 devices with CPU variants CP300 and CP100",
               vendor: "Siemens AG",
               versions: [
                  {
                     status: "affected",
                     version: "All versions < V8.01",
                  },
               ],
            },
            {
               product: "Siemens Power Meters Series 9410",
               vendor: "Siemens AG",
               versions: [
                  {
                     status: "affected",
                     version: "All versions < V2.2.1",
                  },
               ],
            },
            {
               product: "Siemens Power Meters Series 9810",
               vendor: "Siemens AG",
               versions: [
                  {
                     status: "affected",
                     version: "All versions",
                  },
               ],
            },
         ],
         descriptions: [
            {
               lang: "en",
               value: "A vulnerability has been identified in SIPROTEC 5 devices with CPU variants CP200 (All versions < V7.59), SIPROTEC 5 devices with CPU variants CP300 and CP100 (All versions < V8.01), Siemens Power Meters Series 9410 (All versions < V2.2.1), Siemens Power Meters Series 9810 (All versions). An unauthenticated attacker with network access to the device could potentially insert arbitrary code which is executed before firmware verification in the device. At the time of advisory publication no public exploitation of this security vulnerability was known.",
            },
         ],
         problemTypes: [
            {
               descriptions: [
                  {
                     cweId: "CWE-284",
                     description: "CWE-284: Improper Access Control",
                     lang: "en",
                     type: "CWE",
                  },
               ],
            },
         ],
         providerMetadata: {
            dateUpdated: "2020-06-10T16:17:59",
            orgId: "cec7a2ec-15b4-4faf-bd53-b40f371f3a77",
            shortName: "siemens",
         },
         references: [
            {
               tags: [
                  "x_refsource_MISC",
               ],
               url: "https://cert-portal.siemens.com/productcert/pdf/ssa-632562.pdf",
            },
            {
               tags: [
                  "x_refsource_CONFIRM",
               ],
               url: "https://cert-portal.siemens.com/productcert/pdf/ssa-352504.pdf",
            },
         ],
         x_legacyV4Record: {
            CVE_data_meta: {
               ASSIGNER: "productcert@siemens.com",
               ID: "CVE-2019-10938",
               STATE: "PUBLIC",
            },
            affects: {
               vendor: {
                  vendor_data: [
                     {
                        product: {
                           product_data: [
                              {
                                 product_name: "SIPROTEC 5 devices with CPU variants CP200",
                                 version: {
                                    version_data: [
                                       {
                                          version_value: "All versions < V7.59",
                                       },
                                    ],
                                 },
                              },
                              {
                                 product_name: "SIPROTEC 5 devices with CPU variants CP300 and CP100",
                                 version: {
                                    version_data: [
                                       {
                                          version_value: "All versions < V8.01",
                                       },
                                    ],
                                 },
                              },
                              {
                                 product_name: "Siemens Power Meters Series 9410",
                                 version: {
                                    version_data: [
                                       {
                                          version_value: "All versions < V2.2.1",
                                       },
                                    ],
                                 },
                              },
                              {
                                 product_name: "Siemens Power Meters Series 9810",
                                 version: {
                                    version_data: [
                                       {
                                          version_value: "All versions",
                                       },
                                    ],
                                 },
                              },
                           ],
                        },
                        vendor_name: "Siemens AG",
                     },
                  ],
               },
            },
            data_format: "MITRE",
            data_type: "CVE",
            data_version: "4.0",
            description: {
               description_data: [
                  {
                     lang: "eng",
                     value: "A vulnerability has been identified in SIPROTEC 5 devices with CPU variants CP200 (All versions < V7.59), SIPROTEC 5 devices with CPU variants CP300 and CP100 (All versions < V8.01), Siemens Power Meters Series 9410 (All versions < V2.2.1), Siemens Power Meters Series 9810 (All versions). An unauthenticated attacker with network access to the device could potentially insert arbitrary code which is executed before firmware verification in the device. At the time of advisory publication no public exploitation of this security vulnerability was known.",
                  },
               ],
            },
            problemtype: {
               problemtype_data: [
                  {
                     description: [
                        {
                           lang: "eng",
                           value: "CWE-284: Improper Access Control",
                        },
                     ],
                  },
               ],
            },
            references: {
               reference_data: [
                  {
                     name: "https://cert-portal.siemens.com/productcert/pdf/ssa-632562.pdf",
                     refsource: "MISC",
                     url: "https://cert-portal.siemens.com/productcert/pdf/ssa-632562.pdf",
                  },
                  {
                     name: "https://cert-portal.siemens.com/productcert/pdf/ssa-352504.pdf",
                     refsource: "CONFIRM",
                     url: "https://cert-portal.siemens.com/productcert/pdf/ssa-352504.pdf",
                  },
               ],
            },
         },
      },
   },
   cveMetadata: {
      assignerOrgId: "cec7a2ec-15b4-4faf-bd53-b40f371f3a77",
      assignerShortName: "siemens",
      cveId: "CVE-2019-10938",
      datePublished: "2019-08-02T13:54:07",
      dateReserved: "2019-04-08T00:00:00",
      dateUpdated: "2024-08-04T22:40:15.404Z",
      state: "PUBLISHED",
   },
   dataType: "CVE_RECORD",
   dataVersion: "5.1",
   "vulnerability-lookup:meta": {
      fkie_nvd: {
         configurations: "[{\"operator\": \"AND\", \"nodes\": [{\"operator\": \"OR\", \"negate\": false, \"cpeMatch\": [{\"vulnerable\": true, \"criteria\": \"cpe:2.3:a:siemens:siprotec_5_digsi_device_driver:*:*:*:*:*:*:*:*\", \"matchCriteriaId\": \"302821EE-C152-47A9-95F6-9D6B82803E3C\"}]}, {\"operator\": \"OR\", \"negate\": false, \"cpeMatch\": [{\"vulnerable\": false, \"criteria\": \"cpe:2.3:h:siemens:6md85:-:*:*:*:*:*:*:*\", \"matchCriteriaId\": \"23076116-128D-4366-B5BC-B965001FE356\"}, {\"vulnerable\": false, \"criteria\": \"cpe:2.3:h:siemens:6md86:-:*:*:*:*:*:*:*\", \"matchCriteriaId\": \"3457758B-A04D-4544-B0FA-DF87AA11D8FE\"}, {\"vulnerable\": false, \"criteria\": \"cpe:2.3:h:siemens:6md89:-:*:*:*:*:*:*:*\", \"matchCriteriaId\": \"1F0672FC-AEC1-445B-B958-AEDB6DCEE1E6\"}, {\"vulnerable\": false, \"criteria\": \"cpe:2.3:h:siemens:7sa82:-:*:*:*:*:*:*:*\", \"matchCriteriaId\": \"AF247CA0-37E1-40DF-96F5-9F00128EA250\"}, {\"vulnerable\": false, \"criteria\": \"cpe:2.3:h:siemens:7sa86:-:*:*:*:*:*:*:*\", \"matchCriteriaId\": \"EDD3C99B-CDD8-4919-BE72-73814C2642A4\"}, {\"vulnerable\": false, \"criteria\": \"cpe:2.3:h:siemens:7sa87:-:*:*:*:*:*:*:*\", \"matchCriteriaId\": \"DBE6CCA9-A246-4EB2-A57B-FE6823A9E3FD\"}, {\"vulnerable\": false, \"criteria\": \"cpe:2.3:h:siemens:7sd82:-:*:*:*:*:*:*:*\", \"matchCriteriaId\": \"E11B4A68-F533-4AC0-80A9-7374FDFE2DEA\"}, {\"vulnerable\": false, \"criteria\": \"cpe:2.3:h:siemens:7sd86:-:*:*:*:*:*:*:*\", \"matchCriteriaId\": \"73F8D692-F268-45A4-9348-C67890A58881\"}, {\"vulnerable\": false, \"criteria\": \"cpe:2.3:h:siemens:7sd87:-:*:*:*:*:*:*:*\", \"matchCriteriaId\": \"3C5A3FFD-17AD-4820-97D3-2F093BD5F322\"}, {\"vulnerable\": false, \"criteria\": \"cpe:2.3:h:siemens:7sj82:-:*:*:*:*:*:*:*\", \"matchCriteriaId\": \"5739872A-E271-48BB-ABB5-17608E81AE7A\"}, {\"vulnerable\": false, \"criteria\": \"cpe:2.3:h:siemens:7sj85:-:*:*:*:*:*:*:*\", \"matchCriteriaId\": \"ECC6417D-2C81-4654-B7FF-6C3E1B709962\"}, {\"vulnerable\": false, \"criteria\": \"cpe:2.3:h:siemens:7sj86:-:*:*:*:*:*:*:*\", \"matchCriteriaId\": \"C52A6630-46F3-4113-B5E8-F5BAB7801CB0\"}, {\"vulnerable\": false, \"criteria\": \"cpe:2.3:h:siemens:7sk82:-:*:*:*:*:*:*:*\", \"matchCriteriaId\": \"088AC7F2-4FF3-4EF9-A111-D47DB859ECA1\"}, {\"vulnerable\": false, \"criteria\": \"cpe:2.3:h:siemens:7sk85:-:*:*:*:*:*:*:*\", \"matchCriteriaId\": \"73DD95AC-9B8F-43CD-9483-2BB9C4E86376\"}, {\"vulnerable\": false, \"criteria\": \"cpe:2.3:h:siemens:7sl82:-:*:*:*:*:*:*:*\", \"matchCriteriaId\": \"8A9F05D9-C1DF-4D73-8634-239ABFE526DB\"}, {\"vulnerable\": false, \"criteria\": \"cpe:2.3:h:siemens:7sl86:-:*:*:*:*:*:*:*\", \"matchCriteriaId\": \"0C6662F7-5E3D-43A8-9984-EF1540BC917B\"}, {\"vulnerable\": false, \"criteria\": \"cpe:2.3:h:siemens:7sl87:-:*:*:*:*:*:*:*\", \"matchCriteriaId\": \"E122323B-A42B-4DAB-A071-ACF76DC45E28\"}, {\"vulnerable\": false, \"criteria\": \"cpe:2.3:h:siemens:7um85:-:*:*:*:*:*:*:*\", \"matchCriteriaId\": \"AAA9E810-2C00-4721-B3A6-E7CD7184BA24\"}, {\"vulnerable\": false, \"criteria\": \"cpe:2.3:h:siemens:7ut82:-:*:*:*:*:*:*:*\", \"matchCriteriaId\": \"2E959A8E-21D1-4950-974B-A89693C14DC9\"}, {\"vulnerable\": false, \"criteria\": \"cpe:2.3:h:siemens:7ut85:-:*:*:*:*:*:*:*\", \"matchCriteriaId\": \"DA075D19-21BF-4A7C-87B8-6A9D99799826\"}, {\"vulnerable\": false, \"criteria\": \"cpe:2.3:h:siemens:7ut86:-:*:*:*:*:*:*:*\", \"matchCriteriaId\": \"7AC0D445-9A9B-4799-8B83-8B15821A6CC1\"}, {\"vulnerable\": false, \"criteria\": \"cpe:2.3:h:siemens:7ut87:-:*:*:*:*:*:*:*\", \"matchCriteriaId\": \"D2A73860-76C5-435B-8150-1EABF644ADA0\"}, {\"vulnerable\": false, \"criteria\": \"cpe:2.3:h:siemens:7ve85:-:*:*:*:*:*:*:*\", \"matchCriteriaId\": \"2D58566D-C2F7-4D9A-ACD6-D493E4531491\"}, {\"vulnerable\": false, \"criteria\": \"cpe:2.3:h:siemens:7vk87:-:*:*:*:*:*:*:*\", \"matchCriteriaId\": \"5D9FD3B7-C7F7-41C1-9290-411F9D912D00\"}]}]}]",
         descriptions: "[{\"lang\": \"en\", \"value\": \"A vulnerability has been identified in SIPROTEC 5 devices with CPU variants CP200 (All versions < V7.59), SIPROTEC 5 devices with CPU variants CP300 and CP100 (All versions < V8.01), Siemens Power Meters Series 9410 (All versions < V2.2.1), Siemens Power Meters Series 9810 (All versions). An unauthenticated attacker with network access to the device could potentially insert arbitrary code which is executed before firmware verification in the device. At the time of advisory publication no public exploitation of this security vulnerability was known.\"}, {\"lang\": \"es\", \"value\": \"Se ha identificado una vulnerabilidad en los dispositivos SIPROTEC 5 con variantes de CP200 (Todas las versiones anteriores a la versi\\u00f3n V7.59), dispositivos SIPROTEC 5 con variantes de CP300 y CP100 (Todas las versiones anteriores a la versi\\u00f3n V8.01), Siemens Power Meters Series 9410 (Todas las versiones anteriores a la versi\\u00f3n V2.2.1), Siemens Power Meters Series 9810 (Todas las versiones). Un atacante no autenticado con acceso de red al dispositivo podr\\u00eda insertar un c\\u00f3digo arbitrario que se ejecuta antes de la verificaci\\u00f3n del firmware en el dispositivo. En el momento de la publicaci\\u00f3n del aviso, no se conoc\\u00eda la explotaci\\u00f3n p\\u00fablica de esta vulnerabilidad de seguridad\"}]",
         id: "CVE-2019-10938",
         lastModified: "2024-11-21T04:20:11.667",
         metrics: "{\"cvssMetricV31\": [{\"source\": \"nvd@nist.gov\", \"type\": \"Primary\", \"cvssData\": {\"version\": \"3.1\", \"vectorString\": \"CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H\", \"baseScore\": 9.8, \"baseSeverity\": \"CRITICAL\", \"attackVector\": \"NETWORK\", \"attackComplexity\": \"LOW\", \"privilegesRequired\": \"NONE\", \"userInteraction\": \"NONE\", \"scope\": \"UNCHANGED\", \"confidentialityImpact\": \"HIGH\", \"integrityImpact\": \"HIGH\", \"availabilityImpact\": \"HIGH\"}, \"exploitabilityScore\": 3.9, \"impactScore\": 5.9}], \"cvssMetricV2\": [{\"source\": \"nvd@nist.gov\", \"type\": \"Primary\", \"cvssData\": {\"version\": \"2.0\", \"vectorString\": \"AV:N/AC:L/Au:N/C:P/I:P/A:P\", \"baseScore\": 7.5, \"accessVector\": \"NETWORK\", \"accessComplexity\": \"LOW\", \"authentication\": \"NONE\", \"confidentialityImpact\": \"PARTIAL\", \"integrityImpact\": \"PARTIAL\", \"availabilityImpact\": \"PARTIAL\"}, \"baseSeverity\": \"HIGH\", \"exploitabilityScore\": 10.0, \"impactScore\": 6.4, \"acInsufInfo\": false, \"obtainAllPrivilege\": false, \"obtainUserPrivilege\": false, \"obtainOtherPrivilege\": false, \"userInteractionRequired\": false}]}",
         published: "2019-08-02T14:15:14.147",
         references: "[{\"url\": \"https://cert-portal.siemens.com/productcert/pdf/ssa-352504.pdf\", \"source\": \"productcert@siemens.com\", \"tags\": [\"Mitigation\", \"Patch\", \"Vendor Advisory\"]}, {\"url\": \"https://cert-portal.siemens.com/productcert/pdf/ssa-632562.pdf\", \"source\": \"productcert@siemens.com\", \"tags\": [\"Mitigation\", \"Patch\", \"Vendor Advisory\"]}, {\"url\": \"https://cert-portal.siemens.com/productcert/pdf/ssa-352504.pdf\", \"source\": \"af854a3a-2127-422b-91ae-364da2661108\", \"tags\": [\"Mitigation\", \"Patch\", \"Vendor Advisory\"]}, {\"url\": \"https://cert-portal.siemens.com/productcert/pdf/ssa-632562.pdf\", \"source\": \"af854a3a-2127-422b-91ae-364da2661108\", \"tags\": [\"Mitigation\", \"Patch\", \"Vendor Advisory\"]}]",
         sourceIdentifier: "productcert@siemens.com",
         vulnStatus: "Modified",
         weaknesses: "[{\"source\": \"productcert@siemens.com\", \"type\": \"Secondary\", \"description\": [{\"lang\": \"en\", \"value\": \"CWE-284\"}]}, {\"source\": \"nvd@nist.gov\", \"type\": \"Primary\", \"description\": [{\"lang\": \"en\", \"value\": \"NVD-CWE-Other\"}]}]",
      },
      nvd: "{\"cve\":{\"id\":\"CVE-2019-10938\",\"sourceIdentifier\":\"productcert@siemens.com\",\"published\":\"2019-08-02T14:15:14.147\",\"lastModified\":\"2024-11-21T04:20:11.667\",\"vulnStatus\":\"Modified\",\"cveTags\":[],\"descriptions\":[{\"lang\":\"en\",\"value\":\"A vulnerability has been identified in SIPROTEC 5 devices with CPU variants CP200 (All versions < V7.59), SIPROTEC 5 devices with CPU variants CP300 and CP100 (All versions < V8.01), Siemens Power Meters Series 9410 (All versions < V2.2.1), Siemens Power Meters Series 9810 (All versions). An unauthenticated attacker with network access to the device could potentially insert arbitrary code which is executed before firmware verification in the device. At the time of advisory publication no public exploitation of this security vulnerability was known.\"},{\"lang\":\"es\",\"value\":\"Se ha identificado una vulnerabilidad en los dispositivos SIPROTEC 5 con variantes de CP200 (Todas las versiones anteriores a la versión V7.59), dispositivos SIPROTEC 5 con variantes de CP300 y CP100 (Todas las versiones anteriores a la versión V8.01), Siemens Power Meters Series 9410 (Todas las versiones anteriores a la versión V2.2.1), Siemens Power Meters Series 9810 (Todas las versiones). Un atacante no autenticado con acceso de red al dispositivo podría insertar un código arbitrario que se ejecuta antes de la verificación del firmware en el dispositivo. En el momento de la publicación del aviso, no se conocía la explotación pública de esta vulnerabilidad de seguridad\"}],\"metrics\":{\"cvssMetricV31\":[{\"source\":\"nvd@nist.gov\",\"type\":\"Primary\",\"cvssData\":{\"version\":\"3.1\",\"vectorString\":\"CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H\",\"baseScore\":9.8,\"baseSeverity\":\"CRITICAL\",\"attackVector\":\"NETWORK\",\"attackComplexity\":\"LOW\",\"privilegesRequired\":\"NONE\",\"userInteraction\":\"NONE\",\"scope\":\"UNCHANGED\",\"confidentialityImpact\":\"HIGH\",\"integrityImpact\":\"HIGH\",\"availabilityImpact\":\"HIGH\"},\"exploitabilityScore\":3.9,\"impactScore\":5.9}],\"cvssMetricV2\":[{\"source\":\"nvd@nist.gov\",\"type\":\"Primary\",\"cvssData\":{\"version\":\"2.0\",\"vectorString\":\"AV:N/AC:L/Au:N/C:P/I:P/A:P\",\"baseScore\":7.5,\"accessVector\":\"NETWORK\",\"accessComplexity\":\"LOW\",\"authentication\":\"NONE\",\"confidentialityImpact\":\"PARTIAL\",\"integrityImpact\":\"PARTIAL\",\"availabilityImpact\":\"PARTIAL\"},\"baseSeverity\":\"HIGH\",\"exploitabilityScore\":10.0,\"impactScore\":6.4,\"acInsufInfo\":false,\"obtainAllPrivilege\":false,\"obtainUserPrivilege\":false,\"obtainOtherPrivilege\":false,\"userInteractionRequired\":false}]},\"weaknesses\":[{\"source\":\"productcert@siemens.com\",\"type\":\"Secondary\",\"description\":[{\"lang\":\"en\",\"value\":\"CWE-284\"}]},{\"source\":\"nvd@nist.gov\",\"type\":\"Primary\",\"description\":[{\"lang\":\"en\",\"value\":\"NVD-CWE-Other\"}]}],\"configurations\":[{\"operator\":\"AND\",\"nodes\":[{\"operator\":\"OR\",\"negate\":false,\"cpeMatch\":[{\"vulnerable\":true,\"criteria\":\"cpe:2.3:a:siemens:siprotec_5_digsi_device_driver:*:*:*:*:*:*:*:*\",\"matchCriteriaId\":\"302821EE-C152-47A9-95F6-9D6B82803E3C\"}]},{\"operator\":\"OR\",\"negate\":false,\"cpeMatch\":[{\"vulnerable\":false,\"criteria\":\"cpe:2.3:h:siemens:6md85:-:*:*:*:*:*:*:*\",\"matchCriteriaId\":\"23076116-128D-4366-B5BC-B965001FE356\"},{\"vulnerable\":false,\"criteria\":\"cpe:2.3:h:siemens:6md86:-:*:*:*:*:*:*:*\",\"matchCriteriaId\":\"3457758B-A04D-4544-B0FA-DF87AA11D8FE\"},{\"vulnerable\":false,\"criteria\":\"cpe:2.3:h:siemens:6md89:-:*:*:*:*:*:*:*\",\"matchCriteriaId\":\"1F0672FC-AEC1-445B-B958-AEDB6DCEE1E6\"},{\"vulnerable\":false,\"criteria\":\"cpe:2.3:h:siemens:7sa82:-:*:*:*:*:*:*:*\",\"matchCriteriaId\":\"AF247CA0-37E1-40DF-96F5-9F00128EA250\"},{\"vulnerable\":false,\"criteria\":\"cpe:2.3:h:siemens:7sa86:-:*:*:*:*:*:*:*\",\"matchCriteriaId\":\"EDD3C99B-CDD8-4919-BE72-73814C2642A4\"},{\"vulnerable\":false,\"criteria\":\"cpe:2.3:h:siemens:7sa87:-:*:*:*:*:*:*:*\",\"matchCriteriaId\":\"DBE6CCA9-A246-4EB2-A57B-FE6823A9E3FD\"},{\"vulnerable\":false,\"criteria\":\"cpe:2.3:h:siemens:7sd82:-:*:*:*:*:*:*:*\",\"matchCriteriaId\":\"E11B4A68-F533-4AC0-80A9-7374FDFE2DEA\"},{\"vulnerable\":false,\"criteria\":\"cpe:2.3:h:siemens:7sd86:-:*:*:*:*:*:*:*\",\"matchCriteriaId\":\"73F8D692-F268-45A4-9348-C67890A58881\"},{\"vulnerable\":false,\"criteria\":\"cpe:2.3:h:siemens:7sd87:-:*:*:*:*:*:*:*\",\"matchCriteriaId\":\"3C5A3FFD-17AD-4820-97D3-2F093BD5F322\"},{\"vulnerable\":false,\"criteria\":\"cpe:2.3:h:siemens:7sj82:-:*:*:*:*:*:*:*\",\"matchCriteriaId\":\"5739872A-E271-48BB-ABB5-17608E81AE7A\"},{\"vulnerable\":false,\"criteria\":\"cpe:2.3:h:siemens:7sj85:-:*:*:*:*:*:*:*\",\"matchCriteriaId\":\"ECC6417D-2C81-4654-B7FF-6C3E1B709962\"},{\"vulnerable\":false,\"criteria\":\"cpe:2.3:h:siemens:7sj86:-:*:*:*:*:*:*:*\",\"matchCriteriaId\":\"C52A6630-46F3-4113-B5E8-F5BAB7801CB0\"},{\"vulnerable\":false,\"criteria\":\"cpe:2.3:h:siemens:7sk82:-:*:*:*:*:*:*:*\",\"matchCriteriaId\":\"088AC7F2-4FF3-4EF9-A111-D47DB859ECA1\"},{\"vulnerable\":false,\"criteria\":\"cpe:2.3:h:siemens:7sk85:-:*:*:*:*:*:*:*\",\"matchCriteriaId\":\"73DD95AC-9B8F-43CD-9483-2BB9C4E86376\"},{\"vulnerable\":false,\"criteria\":\"cpe:2.3:h:siemens:7sl82:-:*:*:*:*:*:*:*\",\"matchCriteriaId\":\"8A9F05D9-C1DF-4D73-8634-239ABFE526DB\"},{\"vulnerable\":false,\"criteria\":\"cpe:2.3:h:siemens:7sl86:-:*:*:*:*:*:*:*\",\"matchCriteriaId\":\"0C6662F7-5E3D-43A8-9984-EF1540BC917B\"},{\"vulnerable\":false,\"criteria\":\"cpe:2.3:h:siemens:7sl87:-:*:*:*:*:*:*:*\",\"matchCriteriaId\":\"E122323B-A42B-4DAB-A071-ACF76DC45E28\"},{\"vulnerable\":false,\"criteria\":\"cpe:2.3:h:siemens:7um85:-:*:*:*:*:*:*:*\",\"matchCriteriaId\":\"AAA9E810-2C00-4721-B3A6-E7CD7184BA24\"},{\"vulnerable\":false,\"criteria\":\"cpe:2.3:h:siemens:7ut82:-:*:*:*:*:*:*:*\",\"matchCriteriaId\":\"2E959A8E-21D1-4950-974B-A89693C14DC9\"},{\"vulnerable\":false,\"criteria\":\"cpe:2.3:h:siemens:7ut85:-:*:*:*:*:*:*:*\",\"matchCriteriaId\":\"DA075D19-21BF-4A7C-87B8-6A9D99799826\"},{\"vulnerable\":false,\"criteria\":\"cpe:2.3:h:siemens:7ut86:-:*:*:*:*:*:*:*\",\"matchCriteriaId\":\"7AC0D445-9A9B-4799-8B83-8B15821A6CC1\"},{\"vulnerable\":false,\"criteria\":\"cpe:2.3:h:siemens:7ut87:-:*:*:*:*:*:*:*\",\"matchCriteriaId\":\"D2A73860-76C5-435B-8150-1EABF644ADA0\"},{\"vulnerable\":false,\"criteria\":\"cpe:2.3:h:siemens:7ve85:-:*:*:*:*:*:*:*\",\"matchCriteriaId\":\"2D58566D-C2F7-4D9A-ACD6-D493E4531491\"},{\"vulnerable\":false,\"criteria\":\"cpe:2.3:h:siemens:7vk87:-:*:*:*:*:*:*:*\",\"matchCriteriaId\":\"5D9FD3B7-C7F7-41C1-9290-411F9D912D00\"}]}]}],\"references\":[{\"url\":\"https://cert-portal.siemens.com/productcert/pdf/ssa-352504.pdf\",\"source\":\"productcert@siemens.com\",\"tags\":[\"Mitigation\",\"Patch\",\"Vendor Advisory\"]},{\"url\":\"https://cert-portal.siemens.com/productcert/pdf/ssa-632562.pdf\",\"source\":\"productcert@siemens.com\",\"tags\":[\"Mitigation\",\"Patch\",\"Vendor Advisory\"]},{\"url\":\"https://cert-portal.siemens.com/productcert/pdf/ssa-352504.pdf\",\"source\":\"af854a3a-2127-422b-91ae-364da2661108\",\"tags\":[\"Mitigation\",\"Patch\",\"Vendor Advisory\"]},{\"url\":\"https://cert-portal.siemens.com/productcert/pdf/ssa-632562.pdf\",\"source\":\"af854a3a-2127-422b-91ae-364da2661108\",\"tags\":[\"Mitigation\",\"Patch\",\"Vendor Advisory\"]}]}}",
   },
}


Log in or create an account to share your comment.

Security Advisory comment format.

This schema specifies the format of a comment related to a security advisory.

UUIDv4 of the comment
UUIDv4 of the Vulnerability-Lookup instance
When the comment was created originally
When the comment was last updated
Title of the comment
Description of the comment
The identifier of the vulnerability (CVE ID, GHSA-ID, PYSEC ID, etc.).



Tags
Taxonomy of the tags.


Loading…

Loading…

Loading…

Sightings

Author Source Type Date

Nomenclature

  • Seen: The vulnerability was mentioned, discussed, or seen somewhere by the user.
  • Confirmed: The vulnerability is confirmed from an analyst perspective.
  • Exploited: This vulnerability was exploited and seen by the user reporting the sighting.
  • Patched: This vulnerability was successfully patched by the user reporting the sighting.
  • Not exploited: This vulnerability was not exploited or seen by the user reporting the sighting.
  • Not confirmed: The user expresses doubt about the veracity of the vulnerability.
  • Not patched: This vulnerability was not successfully patched by the user reporting the sighting.