GHSA-2CG6-W8MM-22RG

Vulnerability from github – Published: 2022-05-13 01:31 – Updated: 2022-05-13 01:31
VLAI?
Details

A vulnerability has been identified in SIMATIC CP 343-1 Advanced (All versions), SIMATIC CP 343-1 Standard (All versions), SIMATIC CP 443-1 Advanced (All versions), SIMATIC CP 443-1 Standard (All versions), SIMATIC S7-1500 Software Controller incl. F (All versions < V1.7.0), SIMATIC S7-1500 incl. F (All versions < V1.7.0), SIMATIC S7-300 incl. F and T (All versions < V3.X.16), SIMATIC S7-400 H V6 (All versions < V6.0.9), SIMATIC S7-400 PN/DP V6 Incl. F (All versions < V6.0.7), SIMATIC S7-400 PN/DP V7 Incl. F (All versions), SIMATIC S7-410 (All versions < V8.1), SIMATIC WinAC RTX (F) 2010 (All versions < SIMATIC WinAC RTX 2010 SP3), SINUMERIK 828D (All versions < V4.7 SP6 HF1), Softnet PROFINET IO for PC-based Windows systems (All versions). Responding to a PROFINET DCP request with a specially crafted PROFINET DCP packet could cause a Denial-of-Service condition of the requesting system. The security vulnerability could be exploited by an attacker located on the same Ethernet segment (OSI Layer 2) as the targeted device. Successful exploitation requires no user interaction or privileges and impacts the availability of core functionality of the affected device. A manual restart is required to recover the system. At the time of advisory publication no public exploitation of this security vulnerability is known. Siemens provides mitigations to resolve the security issue. PROFIBUS interfaces are not affected.

Show details on source website

{
  "affected": [],
  "aliases": [
    "CVE-2018-4843"
  ],
  "database_specific": {
    "cwe_ids": [
      "CWE-20"
    ],
    "github_reviewed": false,
    "github_reviewed_at": null,
    "nvd_published_at": "2018-03-20T14:29:00Z",
    "severity": "MODERATE"
  },
  "details": "A vulnerability has been identified in SIMATIC CP 343-1 Advanced (All versions), SIMATIC CP 343-1 Standard (All versions), SIMATIC CP 443-1 Advanced (All versions), SIMATIC CP 443-1 Standard (All versions), SIMATIC S7-1500 Software Controller incl. F (All versions \u003c V1.7.0), SIMATIC S7-1500 incl. F (All versions \u003c V1.7.0), SIMATIC S7-300 incl. F and T (All versions \u003c V3.X.16), SIMATIC S7-400 H V6 (All versions \u003c V6.0.9), SIMATIC S7-400 PN/DP V6 Incl. F (All versions \u003c V6.0.7), SIMATIC S7-400 PN/DP V7 Incl. F (All versions), SIMATIC S7-410 (All versions \u003c V8.1), SIMATIC WinAC RTX (F) 2010 (All versions \u003c SIMATIC WinAC RTX 2010 SP3), SINUMERIK 828D (All versions \u003c V4.7 SP6 HF1), Softnet PROFINET IO for PC-based Windows systems (All versions). Responding to a PROFINET DCP request with a specially crafted PROFINET DCP packet could cause a Denial-of-Service condition of the requesting system. The security vulnerability could be exploited by an attacker located on the same Ethernet segment (OSI Layer 2) as the targeted device. Successful exploitation requires no user interaction or privileges and impacts the availability of core functionality of the affected device. A manual restart is required to recover the system. At the time of advisory publication no public exploitation of this security vulnerability is known. Siemens provides mitigations to resolve the security issue. PROFIBUS interfaces are not affected.",
  "id": "GHSA-2cg6-w8mm-22rg",
  "modified": "2022-05-13T01:31:10Z",
  "published": "2022-05-13T01:31:10Z",
  "references": [
    {
      "type": "ADVISORY",
      "url": "https://nvd.nist.gov/vuln/detail/CVE-2018-4843"
    },
    {
      "type": "WEB",
      "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-592007.pdf"
    }
  ],
  "schema_version": "1.4.0",
  "severity": [
    {
      "score": "CVSS:3.0/AV:A/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H",
      "type": "CVSS_V3"
    }
  ]
}


Log in or create an account to share your comment.




Tags
Taxonomy of the tags.


Loading…

Loading…

Loading…

Sightings

Author Source Type Date

Nomenclature

  • Seen: The vulnerability was mentioned, discussed, or observed by the user.
  • Confirmed: The vulnerability has been validated from an analyst's perspective.
  • Published Proof of Concept: A public proof of concept is available for this vulnerability.
  • Exploited: The vulnerability was observed as exploited by the user who reported the sighting.
  • Patched: The vulnerability was observed as successfully patched by the user who reported the sighting.
  • Not exploited: The vulnerability was not observed as exploited by the user who reported the sighting.
  • Not confirmed: The user expressed doubt about the validity of the vulnerability.
  • Not patched: The vulnerability was not observed as successfully patched by the user who reported the sighting.


Loading…

Detection rules are retrieved from Rulezet.

Loading…

Loading…