GHSA-5WJQ-9MM7-CCM8
Vulnerability from github – Published: 2022-05-13 01:16 – Updated: 2022-05-13 01:16A vulnerability has been identified in SIMATIC S7-400 (incl. F) V6 and below (All versions), SIMATIC S7-400 PN/DP V7 (incl. F) (All versions), SIMATIC S7-400H V4.5 and below (All versions), SIMATIC S7-400H V6 (All versions < V6.0.9), SIMATIC S7-410 (All versions < V8.2.1). Sending of specially crafted packets to port 102/tcp via Ethernet interface via PROFIBUS or Multi Point Interfaces (MPI) could cause a Denial-of-Service condition on affected devices. Flashing with a firmware image may be required to recover the CPU. Successful exploitation requires an attacker to have network access to port 102/tcp via Ethernet interface or to be able to send messages via PROFIBUS or Multi Point Interfaces (MPI) to the device. No user interaction is required. If no access protection is configured, no privileges are required to exploit the security vulnerability. The vulnerability could allow causing a Denial-of-Service condition of the core functionality of the CPU, compromising the availability of the system. At the time of advisory publication no public exploitation of this security vulnerability was known.
{
"affected": [],
"aliases": [
"CVE-2018-16557"
],
"database_specific": {
"cwe_ids": [
"CWE-347"
],
"github_reviewed": false,
"github_reviewed_at": null,
"nvd_published_at": "2018-12-13T16:29:00Z",
"severity": "HIGH"
},
"details": "A vulnerability has been identified in SIMATIC S7-400 (incl. F) V6 and below (All versions), SIMATIC S7-400 PN/DP V7 (incl. F) (All versions), SIMATIC S7-400H V4.5 and below (All versions), SIMATIC S7-400H V6 (All versions \u003c V6.0.9), SIMATIC S7-410 (All versions \u003c V8.2.1). Sending of specially crafted packets to port 102/tcp via Ethernet interface via PROFIBUS or Multi Point Interfaces (MPI) could cause a Denial-of-Service condition on affected devices. Flashing with a firmware image may be required to recover the CPU. Successful exploitation requires an attacker to have network access to port 102/tcp via Ethernet interface or to be able to send messages via PROFIBUS or Multi Point Interfaces (MPI) to the device. No user interaction is required. If no access protection is configured, no privileges are required to exploit the security vulnerability. The vulnerability could allow causing a Denial-of-Service condition of the core functionality of the CPU, compromising the availability of the system. At the time of advisory publication no public exploitation of this security vulnerability was known.",
"id": "GHSA-5wjq-9mm7-ccm8",
"modified": "2022-05-13T01:16:11Z",
"published": "2022-05-13T01:16:11Z",
"references": [
{
"type": "ADVISORY",
"url": "https://nvd.nist.gov/vuln/detail/CVE-2018-16557"
},
{
"type": "WEB",
"url": "https://cert-portal.siemens.com/productcert/pdf/ssa-113131.pdf"
},
{
"type": "WEB",
"url": "https://ics-cert.us-cert.gov/advisories/ICSA-18-317-02"
}
],
"schema_version": "1.4.0",
"severity": [
{
"score": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H",
"type": "CVSS_V3"
}
]
}
Sightings
| Author | Source | Type | Date |
|---|
Nomenclature
- Seen: The vulnerability was mentioned, discussed, or observed by the user.
- Confirmed: The vulnerability has been validated from an analyst's perspective.
- Published Proof of Concept: A public proof of concept is available for this vulnerability.
- Exploited: The vulnerability was observed as exploited by the user who reported the sighting.
- Patched: The vulnerability was observed as successfully patched by the user who reported the sighting.
- Not exploited: The vulnerability was not observed as exploited by the user who reported the sighting.
- Not confirmed: The user expressed doubt about the validity of the vulnerability.
- Not patched: The vulnerability was not observed as successfully patched by the user who reported the sighting.