Siemens SIMATIC WinCC, PCS 7, and WinCC Runtime Professional Vulnerabilities (Update C)

Notes

Legal Notice
All information products included in https://us-cert.cisa.gov/ics are provided "as is" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see https://us-cert.cisa.gov/tlp/.
CISA Disclaimer
This CSAF advisory was extracted from unstructured data and may contain inaccuracies. If you notice any errors, please reach out to the designated contact at CISA CSAF: central@cisa.dhs.gov
Recommended Practices
CISA recommends users take defensive measures to minimize the risk of exploitation.
Recommended Practices
Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet.
Recommended Practices
Locate control system networks and remote devices behind firewalls and isolating them from business networks.
Recommended Practices
When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs). Recognize VPNs may have vulnerabilities, should be updated to the most recent version available, and are only as secure as the connected devices.
Recommended Practices
CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.
Recommended Practices
CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.
Recommended Practices
CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.
Recommended Practices
Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.
Recommended Practices
Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.
Recommended Practices
CISA also recommends users take the following measures to protect themselves from social engineering attacks: Do not click web links or open attachments in unsolicited email messages. Refer to Recognizing and Avoiding Email Scams for more information on avoiding email scams. Refer to Avoiding Social Engineering and Phishing Attacks for more information on social engineering attacks.



{
  "document": {
    "category": "csaf_security_advisory",
    "csaf_version": "2.0",
    "distribution": {
      "text": "Disclosure is not limited",
      "tlp": {
        "label": "WHITE",
        "url": "https://us-cert.cisa.gov/tlp/"
      }
    },
    "lang": "en-US",
    "notes": [
      {
        "category": "legal_disclaimer",
        "text": "All information products included in https://us-cert.cisa.gov/ics are provided \"as is\" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see https://us-cert.cisa.gov/tlp/.",
        "title": "Legal Notice"
      },
      {
        "category": "general",
        "text": "This CSAF advisory was extracted from unstructured data and may contain inaccuracies. If you notice any errors, please reach out to the designated contact at CISA CSAF: central@cisa.dhs.gov",
        "title": "CISA Disclaimer"
      },
      {
        "category": "general",
        "text": "CISA recommends users take defensive measures to minimize the risk of exploitation.",
        "title": "Recommended Practices"
      },
      {
        "category": "general",
        "text": "Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet.",
        "title": "Recommended Practices"
      },
      {
        "category": "general",
        "text": "Locate control system networks and remote devices behind firewalls and isolating them from business networks.",
        "title": "Recommended Practices"
      },
      {
        "category": "general",
        "text": "When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs). Recognize VPNs may have vulnerabilities, should be updated to the most recent version available, and are only as secure as the connected devices.",
        "title": "Recommended Practices"
      },
      {
        "category": "general",
        "text": "CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.",
        "title": "Recommended Practices"
      },
      {
        "category": "general",
        "text": "CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.",
        "title": "Recommended Practices"
      },
      {
        "category": "general",
        "text": "CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.",
        "title": "Recommended Practices"
      },
      {
        "category": "general",
        "text": "Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.",
        "title": "Recommended Practices"
      },
      {
        "category": "general",
        "text": "Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.",
        "title": "Recommended Practices"
      },
      {
        "category": "general",
        "text": "CISA also recommends users take the following measures to protect themselves from social engineering attacks: Do not click web links or open attachments in unsolicited email messages. Refer to Recognizing and Avoiding Email Scams for more information on avoiding email scams. Refer to Avoiding Social Engineering and Phishing Attacks for more information on social engineering attacks.",
        "title": "Recommended Practices"
      }
    ],
    "publisher": {
      "category": "coordinator",
      "contact_details": "central@cisa.dhs.gov",
      "name": "CISA",
      "namespace": "https://www.cisa.gov/"
    },
    "references": [
      {
        "category": "self",
        "summary": "ICS Advisory ICSA-16-208-01C JSON",
        "url": "https://raw.githubusercontent.com/cisagov/CSAF/develop/csaf_files/OT/white/2016/icsa-16-208-01c.json"
      },
      {
        "category": "self",
        "summary": "ICS Advisory ICSA-16-208-01C - Web Version",
        "url": "https://www.cisa.gov/news-events/ics-advisories/icsa-16-208-01c"
      },
      {
        "category": "external",
        "summary": "Recommended Practices",
        "url": "https://www.cisa.gov/uscert/ics/alerts/ICS-ALERT-10-301-01"
      },
      {
        "category": "external",
        "summary": "Recommended Practices",
        "url": "https://www.cisa.gov/resources-tools/resources/ics-recommended-practices"
      },
      {
        "category": "external",
        "summary": "Recommended Practices",
        "url": "https://www.cisa.gov/topics/industrial-control-systems"
      },
      {
        "category": "external",
        "summary": "Recommended Practices",
        "url": "https://us-cert.cisa.gov/sites/default/files/recommended_practices/NCCIC_ICS-CERT_Defense_in_Depth_2016_S508C.pdf"
      },
      {
        "category": "external",
        "summary": "Recommended Practices",
        "url": "https://www.cisa.gov/sites/default/files/publications/Cybersecurity_Best_Practices_for_Industrial_Control_Systems.pdf"
      },
      {
        "category": "external",
        "summary": "Recommended Practices",
        "url": "https://www.cisa.gov/uscert/ics/tips/ICS-TIP-12-146-01B"
      },
      {
        "category": "external",
        "summary": "Recommended Practices",
        "url": "https://www.cisa.gov/uscert/sites/default/files/publications/emailscams0905.pdf"
      },
      {
        "category": "external",
        "summary": "Recommended Practices",
        "url": "https://www.cisa.gov/uscert/ncas/tips/ST04-014"
      }
    ],
    "title": "Siemens SIMATIC WinCC, PCS 7, and WinCC Runtime Professional Vulnerabilities (Update C)",
    "tracking": {
      "current_release_date": "2025-06-25T18:13:26.602224Z",
      "generator": {
        "date": "2025-06-25T18:13:26.602197Z",
        "engine": {
          "name": "CISA CSAF Generator",
          "version": "1.0.0"
        }
      },
      "id": "ICSA-16-208-01C",
      "initial_release_date": "2016-04-29T06:00:00.000000Z",
      "revision_history": [
        {
          "date": "2016-04-29T06:00:00.000000Z",
          "legacy_version": "Initial",
          "number": "1",
          "summary": "Initial Publication"
        },
        {
          "date": "2025-06-25T18:13:26.602224Z",
          "legacy_version": "CSAF Conversion",
          "number": "2",
          "summary": "Advisory converted into a CSAF"
        }
      ],
      "status": "final",
      "version": "2"
    }
  },
  "product_tree": {
    "branches": [
      {
        "branches": [
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "\u003cUpdate_12",
                "product": {
                  "name": "Siemens SIMATIC WinCC 7.0 SP2: \u003cUpdate_12",
                  "product_id": "CSAFPID-0001"
                }
              }
            ],
            "category": "product_name",
            "name": "SIMATIC WinCC 7.0 SP2"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "\u003cUpdate_8",
                "product": {
                  "name": "Siemens SIMATIC WinCC 7.0 SP3: \u003cUpdate_8",
                  "product_id": "CSAFPID-0002"
                }
              }
            ],
            "category": "product_name",
            "name": "SIMATIC WinCC 7.0 SP3"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "\u003cUpdate_13",
                "product": {
                  "name": "Siemens SIMATIC WinCC 7.2: \u003cUpdate_13",
                  "product_id": "CSAFPID-0003"
                }
              }
            ],
            "category": "product_name",
            "name": "SIMATIC WinCC 7.2"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "\u003cUpdate_10",
                "product": {
                  "name": "Siemens SIMATIC WinCC 7.3: \u003cUpdate_10",
                  "product_id": "CSAFPID-0004"
                }
              }
            ],
            "category": "product_name",
            "name": "SIMATIC WinCC 7.3"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "\u003cUpdate_1",
                "product": {
                  "name": "Siemens SIMATIC WinCC 7.4: \u003cUpdate_1",
                  "product_id": "CSAFPID-0005"
                }
              }
            ],
            "category": "product_name",
            "name": "SIMATIC WinCC 7.4"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "\u003cV7.1_SP4_with_WinCC_V7.0_SP2_Update_12",
                "product": {
                  "name": "Siemens SIMATIC PCS 7 (WinCC, Batch, Route Control, OPEN PCS 7): \u003cV7.1_SP4_with_WinCC_V7.0_SP2_Update_12",
                  "product_id": "CSAFPID-0006"
                }
              }
            ],
            "category": "product_name",
            "name": "SIMATIC PCS 7 (WinCC, Batch, Route Control, OPEN PCS 7)"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "\u003cV8.0_SP2_with_WinCC_V7.2_Update_13",
                "product": {
                  "name": "Siemens SIMATIC PCS 7 (WinCC, Batch, Route Control, OPEN PCS 7): \u003cV8.0_SP2_with_WinCC_V7.2_Update_13",
                  "product_id": "CSAFPID-0007"
                }
              }
            ],
            "category": "product_name",
            "name": "SIMATIC PCS 7 (WinCC, Batch, Route Control, OPEN PCS 7)"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "\u003c8.1_SP1_with_WinCC_V7.3_Update_10",
                "product": {
                  "name": "Siemens SIMATIC PCS 7 (WinCC, Batch, Route Control, OPEN PCS 7): \u003c8.1_SP1_with_WinCC_V7.3_Update_10",
                  "product_id": "CSAFPID-0008"
                }
              }
            ],
            "category": "product_name",
            "name": "SIMATIC PCS 7 (WinCC, Batch, Route Control, OPEN PCS 7)"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "\u003c8.2_with_WinCC_V7.4_Update_1",
                "product": {
                  "name": "Siemens SIMATIC PCS 7 (WinCC, Batch, Route Control, OPEN PCS 7): \u003c8.2_with_WinCC_V7.4_Update_1",
                  "product_id": "CSAFPID-0009"
                }
              }
            ],
            "category": "product_name",
            "name": "SIMATIC PCS 7 (WinCC, Batch, Route Control, OPEN PCS 7)"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "\u003cV13_SP_1_Update_9",
                "product": {
                  "name": "Siemens SIMATIC WinCC Runtime Professional: \u003cV13_SP_1_Update_9",
                  "product_id": "CSAFPID-0010"
                }
              }
            ],
            "category": "product_name",
            "name": "SIMATIC WinCC Runtime Professional"
          }
        ],
        "category": "vendor",
        "name": "Siemens"
      }
    ]
  },
  "vulnerabilities": [
    {
      "cve": "CVE-2016-5743",
      "cwe": {
        "id": "CWE-20",
        "name": "Improper Input Validation"
      },
      "notes": [
        {
          "category": "summary",
          "text": "Siemens SIMATIC WinCC before 7.3 Update 10 and 7.4 before Update 1, SIMATIC BATCH before 8.1 SP1 Update 9 as distributed in SIMATIC PCS 7 through 8.1 SP1, SIMATIC OpenPCS 7 before 8.1 Update 3 as distributed in SIMATIC PCS 7 through 8.1 SP1, SIMATIC OpenPCS 7 before 8.2 Update 1 as distributed in SIMATIC PCS 7 8.2, and SIMATIC WinCC Runtime Professional before 13 SP1 Update 9 allow remote attackers to execute arbitrary code via crafted packets.",
          "title": "Vulnerability Summary"
        }
      ],
      "product_status": {
        "known_affected": [
          "CSAFPID-0001",
          "CSAFPID-0002",
          "CSAFPID-0003",
          "CSAFPID-0004",
          "CSAFPID-0005",
          "CSAFPID-0006",
          "CSAFPID-0007",
          "CSAFPID-0008",
          "CSAFPID-0009",
          "CSAFPID-0010"
        ]
      },
      "remediations": [
        {
          "category": "mitigation",
          "details": "Siemens has produced updates for the following products and strongly encourages users to upgrade to the new versions as soon as possible: SIMATIC WinCC V7.0 SP2: Update to V7.0 SP2 Update 12 (https://support.industry.siemens.com/cs/ww/en/view/109741519)",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005",
            "CSAFPID-0006",
            "CSAFPID-0007",
            "CSAFPID-0008",
            "CSAFPID-0009",
            "CSAFPID-0010"
          ],
          "url": "https://support.industry.siemens.com/cs/ww/en/view/109741519"
        },
        {
          "category": "mitigation",
          "details": "SIMATIC WinCC V7.0 SP3:: Update to V7.0 SP3 Update 8 (https://support.industry.siemens.com/cs/ww/en/view/109741127)",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005",
            "CSAFPID-0006",
            "CSAFPID-0007",
            "CSAFPID-0008",
            "CSAFPID-0009",
            "CSAFPID-0010"
          ],
          "url": "https://support.industry.siemens.com/cs/ww/en/view/109741127"
        },
        {
          "category": "mitigation",
          "details": "SIMATIC WinCC V7.2: Update to WinCC V7.2 Update 13 (https://support.industry.siemens.com/cs/ww/en/view/109739416)",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005",
            "CSAFPID-0006",
            "CSAFPID-0007",
            "CSAFPID-0008",
            "CSAFPID-0009",
            "CSAFPID-0010"
          ],
          "url": "https://support.industry.siemens.com/cs/ww/en/view/109739416"
        },
        {
          "category": "mitigation",
          "details": "SIMATIC WinCC V7.3: Update to WinCC V7.3 Update 10 (https://support.industry.siemens.com/cs/ww/en/view/109738470)",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005",
            "CSAFPID-0006",
            "CSAFPID-0007",
            "CSAFPID-0008",
            "CSAFPID-0009",
            "CSAFPID-0010"
          ],
          "url": "https://support.industry.siemens.com/cs/ww/en/view/109738470"
        },
        {
          "category": "mitigation",
          "details": "SIMATIC WinCC V7.4: Update to WinCC V7.4 Update 1 (https://support.industry.siemens.com/cs/ww/de/view/109738653)",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005",
            "CSAFPID-0006",
            "CSAFPID-0007",
            "CSAFPID-0008",
            "CSAFPID-0009",
            "CSAFPID-0010"
          ],
          "url": "https://support.industry.siemens.com/cs/ww/de/view/109738653"
        },
        {
          "category": "mitigation",
          "details": "SIMATIC PCS 7 V7.1 SP4 and earlier versions: WinCC: Update to WinCC V7.0 SP2 Update 12 (https://support.industry.siemens.com/cs/ww/en/view/109741519)",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005",
            "CSAFPID-0006",
            "CSAFPID-0007",
            "CSAFPID-0008",
            "CSAFPID-0009",
            "CSAFPID-0010"
          ],
          "url": "https://support.industry.siemens.com/cs/ww/en/view/109741519"
        },
        {
          "category": "mitigation",
          "details": "BATCH: Update to BATCH V7.1 SP1 Update 21 (https://support.industry.siemens.com/cs/ww/en/view/109738681)",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005",
            "CSAFPID-0006",
            "CSAFPID-0007",
            "CSAFPID-0008",
            "CSAFPID-0009",
            "CSAFPID-0010"
          ],
          "url": "https://support.industry.siemens.com/cs/ww/en/view/109738681"
        },
        {
          "category": "mitigation",
          "details": "BATCH: Update to BATCH V7.1 SP2 Update 11 (https://support.industry.siemens.com/cs/ww/en/view/109738681)",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005",
            "CSAFPID-0006",
            "CSAFPID-0007",
            "CSAFPID-0008",
            "CSAFPID-0009",
            "CSAFPID-0010"
          ],
          "url": "https://support.industry.siemens.com/cs/ww/en/view/109738681"
        },
        {
          "category": "mitigation",
          "details": "Route Control: Update to Route Control V7.1 SP2 Update 6 (https://support.industry.siemens.com/cs/ww/en/view/109738681)",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005",
            "CSAFPID-0006",
            "CSAFPID-0007",
            "CSAFPID-0008",
            "CSAFPID-0009",
            "CSAFPID-0010"
          ],
          "url": "https://support.industry.siemens.com/cs/ww/en/view/109738681"
        },
        {
          "category": "mitigation",
          "details": "OpenPCS 7: Update to OpenPCS 7 V7.1 SP4 Update 2 (https://support.industry.siemens.com/cs/ww/en/view/109738681)",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005",
            "CSAFPID-0006",
            "CSAFPID-0007",
            "CSAFPID-0008",
            "CSAFPID-0009",
            "CSAFPID-0010"
          ],
          "url": "https://support.industry.siemens.com/cs/ww/en/view/109738681"
        },
        {
          "category": "mitigation",
          "details": "SIMATIC PCS 7 V8.0 SP2: WinCC: Update to WinCC V7.2 Update 13 (https://support.industry.siemens.com/cs/ww/en/view/109739416)",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005",
            "CSAFPID-0006",
            "CSAFPID-0007",
            "CSAFPID-0008",
            "CSAFPID-0009",
            "CSAFPID-0010"
          ],
          "url": "https://support.industry.siemens.com/cs/ww/en/view/109739416"
        },
        {
          "category": "mitigation",
          "details": "BATCH: Update to BATCH V8.0 SP1 Update 17 (https://support.industry.siemens.com/cs/ww/en/view/109738680)",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005",
            "CSAFPID-0006",
            "CSAFPID-0007",
            "CSAFPID-0008",
            "CSAFPID-0009",
            "CSAFPID-0010"
          ],
          "url": "https://support.industry.siemens.com/cs/ww/en/view/109738680"
        },
        {
          "category": "mitigation",
          "details": "Route Control: Update to Route Control V8.0 SP1 Update 6 (https://support.industry.siemens.com/cs/ww/en/view/109738680)",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005",
            "CSAFPID-0006",
            "CSAFPID-0007",
            "CSAFPID-0008",
            "CSAFPID-0009",
            "CSAFPID-0010"
          ],
          "url": "https://support.industry.siemens.com/cs/ww/en/view/109738680"
        },
        {
          "category": "mitigation",
          "details": "OpenPCS 7: Update to OpenPCS 7 V8.0 SP1 Update 8 (https://support.industry.siemens.com/cs/ww/en/view/109738680)",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005",
            "CSAFPID-0006",
            "CSAFPID-0007",
            "CSAFPID-0008",
            "CSAFPID-0009",
            "CSAFPID-0010"
          ],
          "url": "https://support.industry.siemens.com/cs/ww/en/view/109738680"
        },
        {
          "category": "mitigation",
          "details": "SIMATIC PCS 7 V8.1 SP1: WinCC: Update to WinCC V7.3 Update 10 (https://support.industry.siemens.com/cs/ww/en/view/109738470)",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005",
            "CSAFPID-0006",
            "CSAFPID-0007",
            "CSAFPID-0008",
            "CSAFPID-0009",
            "CSAFPID-0010"
          ],
          "url": "https://support.industry.siemens.com/cs/ww/en/view/109738470"
        },
        {
          "category": "mitigation",
          "details": "BATCH: Update to BATCH V8.1 SP1 Update 11 (https://support.industry.siemens.com/cs/ww/en/view/109738678)",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005",
            "CSAFPID-0006",
            "CSAFPID-0007",
            "CSAFPID-0008",
            "CSAFPID-0009",
            "CSAFPID-0010"
          ],
          "url": "https://support.industry.siemens.com/cs/ww/en/view/109738678"
        },
        {
          "category": "mitigation",
          "details": "Route Control: Update to Route Control V8.1 Update 2 (https://support.industry.siemens.com/cs/ww/en/view/109738678)",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005",
            "CSAFPID-0006",
            "CSAFPID-0007",
            "CSAFPID-0008",
            "CSAFPID-0009",
            "CSAFPID-0010"
          ],
          "url": "https://support.industry.siemens.com/cs/ww/en/view/109738678"
        },
        {
          "category": "mitigation",
          "details": "OpenPCS 7: Update to OpenPCS 7 V8.1 Update 3 (https://support.industry.siemens.com/cs/ww/en/view/109738678)",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005",
            "CSAFPID-0006",
            "CSAFPID-0007",
            "CSAFPID-0008",
            "CSAFPID-0009",
            "CSAFPID-0010"
          ],
          "url": "https://support.industry.siemens.com/cs/ww/en/view/109738678"
        },
        {
          "category": "mitigation",
          "details": "SIMATIC PCS 7 V8.2: WinCC: Update to WinCC V7.4 Update 1 (https://support.industry.siemens.com/cs/ww/de/view/109738653)",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005",
            "CSAFPID-0006",
            "CSAFPID-0007",
            "CSAFPID-0008",
            "CSAFPID-0009",
            "CSAFPID-0010"
          ],
          "url": "https://support.industry.siemens.com/cs/ww/de/view/109738653"
        },
        {
          "category": "mitigation",
          "details": "BATCH: Update to BATCH V8.2 Update 1 (https://support.industry.siemens.com/cs/ww/en/view/109738678)",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005",
            "CSAFPID-0006",
            "CSAFPID-0007",
            "CSAFPID-0008",
            "CSAFPID-0009",
            "CSAFPID-0010"
          ],
          "url": "https://support.industry.siemens.com/cs/ww/en/view/109738678"
        },
        {
          "category": "mitigation",
          "details": "Route Control: Update to Route Control V8.2 Update 1 (https://support.industry.siemens.com/cs/ww/en/view/109738678)",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005",
            "CSAFPID-0006",
            "CSAFPID-0007",
            "CSAFPID-0008",
            "CSAFPID-0009",
            "CSAFPID-0010"
          ],
          "url": "https://support.industry.siemens.com/cs/ww/en/view/109738678"
        },
        {
          "category": "mitigation",
          "details": "OpenPCS 7: Update to OpenPCS7 V8.2 Update 1",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005",
            "CSAFPID-0006",
            "CSAFPID-0007",
            "CSAFPID-0008",
            "CSAFPID-0009",
            "CSAFPID-0010"
          ]
        },
        {
          "category": "mitigation",
          "details": "Contact Customer Support: (https://support.industry.siemens.com/cs/de/en/)",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005",
            "CSAFPID-0006",
            "CSAFPID-0007",
            "CSAFPID-0008",
            "CSAFPID-0009",
            "CSAFPID-0010"
          ],
          "url": "https://support.industry.siemens.com/cs/de/en/"
        },
        {
          "category": "mitigation",
          "details": "SIMATIC WinCC Runtime Professional V13: Update to WinCC Runtime Professional V13 SP1 Update 9: (https://support.industry.siemens.com/cs/ww/en/view/109311724)",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005",
            "CSAFPID-0006",
            "CSAFPID-0007",
            "CSAFPID-0008",
            "CSAFPID-0009",
            "CSAFPID-0010"
          ],
          "url": "https://support.industry.siemens.com/cs/ww/en/view/109311724"
        },
        {
          "category": "mitigation",
          "details": "Until updates can be applied, Siemens recommends the following steps to mitigate the risk: Always run WinCC, WinCC Runtime Professional, and PCS 7 stations within a trusted network.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005",
            "CSAFPID-0006",
            "CSAFPID-0007",
            "CSAFPID-0008",
            "CSAFPID-0009",
            "CSAFPID-0010"
          ]
        },
        {
          "category": "mitigation",
          "details": "Ensure that WinCC, WinCC Runtime Professional, and PCS 7 stations communicate via encrypted channels only (e.g., activate feature \u201cEncrypted Communications\u201d in WinCC V7.3 and PCS 7 V8.1 SP1, or establish a VPN tunnel).",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005",
            "CSAFPID-0006",
            "CSAFPID-0007",
            "CSAFPID-0008",
            "CSAFPID-0009",
            "CSAFPID-0010"
          ]
        },
        {
          "category": "mitigation",
          "details": "Restrict access to the WinCC, WinCC Runtime Professional and PCS 7 stations to trusted entities.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005",
            "CSAFPID-0006",
            "CSAFPID-0007",
            "CSAFPID-0008",
            "CSAFPID-0009",
            "CSAFPID-0010"
          ]
        },
        {
          "category": "mitigation",
          "details": "Apply up-to-date application whitelisting software and virus scanners.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005",
            "CSAFPID-0006",
            "CSAFPID-0007",
            "CSAFPID-0008",
            "CSAFPID-0009",
            "CSAFPID-0010"
          ]
        },
        {
          "category": "mitigation",
          "details": "For more information on these vulnerabilities and more detailed mitigation instructions, please see Siemens Security Advisory SSA-378531 at the following location: (http://www.siemens.com/cert/en/cert-security-advisories.htm)",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005",
            "CSAFPID-0006",
            "CSAFPID-0007",
            "CSAFPID-0008",
            "CSAFPID-0009",
            "CSAFPID-0010"
          ],
          "url": "http://www.siemens.com/cert/en/cert-security-advisories.htm"
        },
        {
          "category": "mitigation",
          "details": "As a general security measure Siemens strongly recommends protecting network access to the WinCC and PCS 7 stations with appropriate mechanisms. Siemens advises configuring the environment according to Siemens operational guidelines in order to run the devices in a protected IT environment. (https://www.siemens.com/cert/operational-guidelines-industrial-security)",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005",
            "CSAFPID-0006",
            "CSAFPID-0007",
            "CSAFPID-0008",
            "CSAFPID-0009",
            "CSAFPID-0010"
          ],
          "url": "https://www.siemens.com/cert/operational-guidelines-industrial-security"
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "baseScore": 9.8,
            "baseSeverity": "CRITICAL",
            "vectorString": "CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H",
            "version": "3.0"
          },
          "products": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005",
            "CSAFPID-0006",
            "CSAFPID-0007",
            "CSAFPID-0008",
            "CSAFPID-0009",
            "CSAFPID-0010"
          ]
        }
      ]
    },
    {
      "cve": "CVE-2016-5744",
      "cwe": {
        "id": "CWE-20",
        "name": "Improper Input Validation"
      },
      "notes": [
        {
          "category": "summary",
          "text": "Siemens SIMATIC WinCC 7.0 through SP3 and 7.2 allows remote attackers to read arbitrary WinCC station files via crafted packets.",
          "title": "Vulnerability Summary"
        }
      ],
      "product_status": {
        "known_affected": [
          "CSAFPID-0001",
          "CSAFPID-0002",
          "CSAFPID-0003",
          "CSAFPID-0004",
          "CSAFPID-0005",
          "CSAFPID-0006",
          "CSAFPID-0007",
          "CSAFPID-0008",
          "CSAFPID-0009",
          "CSAFPID-0010"
        ]
      },
      "remediations": [
        {
          "category": "mitigation",
          "details": "Siemens has produced updates for the following products and strongly encourages users to upgrade to the new versions as soon as possible: SIMATIC WinCC V7.0 SP2: Update to V7.0 SP2 Update 12 (https://support.industry.siemens.com/cs/ww/en/view/109741519)",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005",
            "CSAFPID-0006",
            "CSAFPID-0007",
            "CSAFPID-0008",
            "CSAFPID-0009",
            "CSAFPID-0010"
          ],
          "url": "https://support.industry.siemens.com/cs/ww/en/view/109741519"
        },
        {
          "category": "mitigation",
          "details": "SIMATIC WinCC V7.0 SP3:: Update to V7.0 SP3 Update 8 (https://support.industry.siemens.com/cs/ww/en/view/109741127)",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005",
            "CSAFPID-0006",
            "CSAFPID-0007",
            "CSAFPID-0008",
            "CSAFPID-0009",
            "CSAFPID-0010"
          ],
          "url": "https://support.industry.siemens.com/cs/ww/en/view/109741127"
        },
        {
          "category": "mitigation",
          "details": "SIMATIC WinCC V7.2: Update to WinCC V7.2 Update 13 (https://support.industry.siemens.com/cs/ww/en/view/109739416)",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005",
            "CSAFPID-0006",
            "CSAFPID-0007",
            "CSAFPID-0008",
            "CSAFPID-0009",
            "CSAFPID-0010"
          ],
          "url": "https://support.industry.siemens.com/cs/ww/en/view/109739416"
        },
        {
          "category": "mitigation",
          "details": "SIMATIC WinCC V7.3: Update to WinCC V7.3 Update 10 (https://support.industry.siemens.com/cs/ww/en/view/109738470)",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005",
            "CSAFPID-0006",
            "CSAFPID-0007",
            "CSAFPID-0008",
            "CSAFPID-0009",
            "CSAFPID-0010"
          ],
          "url": "https://support.industry.siemens.com/cs/ww/en/view/109738470"
        },
        {
          "category": "mitigation",
          "details": "SIMATIC WinCC V7.4: Update to WinCC V7.4 Update 1 (https://support.industry.siemens.com/cs/ww/de/view/109738653)",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005",
            "CSAFPID-0006",
            "CSAFPID-0007",
            "CSAFPID-0008",
            "CSAFPID-0009",
            "CSAFPID-0010"
          ],
          "url": "https://support.industry.siemens.com/cs/ww/de/view/109738653"
        },
        {
          "category": "mitigation",
          "details": "SIMATIC PCS 7 V7.1 SP4 and earlier versions: WinCC: Update to WinCC V7.0 SP2 Update 12 (https://support.industry.siemens.com/cs/ww/en/view/109741519)",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005",
            "CSAFPID-0006",
            "CSAFPID-0007",
            "CSAFPID-0008",
            "CSAFPID-0009",
            "CSAFPID-0010"
          ],
          "url": "https://support.industry.siemens.com/cs/ww/en/view/109741519"
        },
        {
          "category": "mitigation",
          "details": "BATCH: Update to BATCH V7.1 SP1 Update 21 (https://support.industry.siemens.com/cs/ww/en/view/109738681)",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005",
            "CSAFPID-0006",
            "CSAFPID-0007",
            "CSAFPID-0008",
            "CSAFPID-0009",
            "CSAFPID-0010"
          ],
          "url": "https://support.industry.siemens.com/cs/ww/en/view/109738681"
        },
        {
          "category": "mitigation",
          "details": "BATCH: Update to BATCH V7.1 SP2 Update 11 (https://support.industry.siemens.com/cs/ww/en/view/109738681)",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005",
            "CSAFPID-0006",
            "CSAFPID-0007",
            "CSAFPID-0008",
            "CSAFPID-0009",
            "CSAFPID-0010"
          ],
          "url": "https://support.industry.siemens.com/cs/ww/en/view/109738681"
        },
        {
          "category": "mitigation",
          "details": "Route Control: Update to Route Control V7.1 SP2 Update 6 (https://support.industry.siemens.com/cs/ww/en/view/109738681)",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005",
            "CSAFPID-0006",
            "CSAFPID-0007",
            "CSAFPID-0008",
            "CSAFPID-0009",
            "CSAFPID-0010"
          ],
          "url": "https://support.industry.siemens.com/cs/ww/en/view/109738681"
        },
        {
          "category": "mitigation",
          "details": "OpenPCS 7: Update to OpenPCS 7 V7.1 SP4 Update 2 (https://support.industry.siemens.com/cs/ww/en/view/109738681)",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005",
            "CSAFPID-0006",
            "CSAFPID-0007",
            "CSAFPID-0008",
            "CSAFPID-0009",
            "CSAFPID-0010"
          ],
          "url": "https://support.industry.siemens.com/cs/ww/en/view/109738681"
        },
        {
          "category": "mitigation",
          "details": "SIMATIC PCS 7 V8.0 SP2: WinCC: Update to WinCC V7.2 Update 13 (https://support.industry.siemens.com/cs/ww/en/view/109739416)",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005",
            "CSAFPID-0006",
            "CSAFPID-0007",
            "CSAFPID-0008",
            "CSAFPID-0009",
            "CSAFPID-0010"
          ],
          "url": "https://support.industry.siemens.com/cs/ww/en/view/109739416"
        },
        {
          "category": "mitigation",
          "details": "BATCH: Update to BATCH V8.0 SP1 Update 17 (https://support.industry.siemens.com/cs/ww/en/view/109738680)",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005",
            "CSAFPID-0006",
            "CSAFPID-0007",
            "CSAFPID-0008",
            "CSAFPID-0009",
            "CSAFPID-0010"
          ],
          "url": "https://support.industry.siemens.com/cs/ww/en/view/109738680"
        },
        {
          "category": "mitigation",
          "details": "Route Control: Update to Route Control V8.0 SP1 Update 6 (https://support.industry.siemens.com/cs/ww/en/view/109738680)",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005",
            "CSAFPID-0006",
            "CSAFPID-0007",
            "CSAFPID-0008",
            "CSAFPID-0009",
            "CSAFPID-0010"
          ],
          "url": "https://support.industry.siemens.com/cs/ww/en/view/109738680"
        },
        {
          "category": "mitigation",
          "details": "OpenPCS 7: Update to OpenPCS 7 V8.0 SP1 Update 8 (https://support.industry.siemens.com/cs/ww/en/view/109738680)",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005",
            "CSAFPID-0006",
            "CSAFPID-0007",
            "CSAFPID-0008",
            "CSAFPID-0009",
            "CSAFPID-0010"
          ],
          "url": "https://support.industry.siemens.com/cs/ww/en/view/109738680"
        },
        {
          "category": "mitigation",
          "details": "SIMATIC PCS 7 V8.1 SP1: WinCC: Update to WinCC V7.3 Update 10 (https://support.industry.siemens.com/cs/ww/en/view/109738470)",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005",
            "CSAFPID-0006",
            "CSAFPID-0007",
            "CSAFPID-0008",
            "CSAFPID-0009",
            "CSAFPID-0010"
          ],
          "url": "https://support.industry.siemens.com/cs/ww/en/view/109738470"
        },
        {
          "category": "mitigation",
          "details": "BATCH: Update to BATCH V8.1 SP1 Update 11 (https://support.industry.siemens.com/cs/ww/en/view/109738678)",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005",
            "CSAFPID-0006",
            "CSAFPID-0007",
            "CSAFPID-0008",
            "CSAFPID-0009",
            "CSAFPID-0010"
          ],
          "url": "https://support.industry.siemens.com/cs/ww/en/view/109738678"
        },
        {
          "category": "mitigation",
          "details": "Route Control: Update to Route Control V8.1 Update 2 (https://support.industry.siemens.com/cs/ww/en/view/109738678)",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005",
            "CSAFPID-0006",
            "CSAFPID-0007",
            "CSAFPID-0008",
            "CSAFPID-0009",
            "CSAFPID-0010"
          ],
          "url": "https://support.industry.siemens.com/cs/ww/en/view/109738678"
        },
        {
          "category": "mitigation",
          "details": "OpenPCS 7: Update to OpenPCS 7 V8.1 Update 3 (https://support.industry.siemens.com/cs/ww/en/view/109738678)",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005",
            "CSAFPID-0006",
            "CSAFPID-0007",
            "CSAFPID-0008",
            "CSAFPID-0009",
            "CSAFPID-0010"
          ],
          "url": "https://support.industry.siemens.com/cs/ww/en/view/109738678"
        },
        {
          "category": "mitigation",
          "details": "SIMATIC PCS 7 V8.2: WinCC: Update to WinCC V7.4 Update 1 (https://support.industry.siemens.com/cs/ww/de/view/109738653)",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005",
            "CSAFPID-0006",
            "CSAFPID-0007",
            "CSAFPID-0008",
            "CSAFPID-0009",
            "CSAFPID-0010"
          ],
          "url": "https://support.industry.siemens.com/cs/ww/de/view/109738653"
        },
        {
          "category": "mitigation",
          "details": "BATCH: Update to BATCH V8.2 Update 1 (https://support.industry.siemens.com/cs/ww/en/view/109738678)",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005",
            "CSAFPID-0006",
            "CSAFPID-0007",
            "CSAFPID-0008",
            "CSAFPID-0009",
            "CSAFPID-0010"
          ],
          "url": "https://support.industry.siemens.com/cs/ww/en/view/109738678"
        },
        {
          "category": "mitigation",
          "details": "Route Control: Update to Route Control V8.2 Update 1 (https://support.industry.siemens.com/cs/ww/en/view/109738678)",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005",
            "CSAFPID-0006",
            "CSAFPID-0007",
            "CSAFPID-0008",
            "CSAFPID-0009",
            "CSAFPID-0010"
          ],
          "url": "https://support.industry.siemens.com/cs/ww/en/view/109738678"
        },
        {
          "category": "mitigation",
          "details": "OpenPCS 7: Update to OpenPCS7 V8.2 Update 1",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005",
            "CSAFPID-0006",
            "CSAFPID-0007",
            "CSAFPID-0008",
            "CSAFPID-0009",
            "CSAFPID-0010"
          ]
        },
        {
          "category": "mitigation",
          "details": "Contact Customer Support: (https://support.industry.siemens.com/cs/de/en/)",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005",
            "CSAFPID-0006",
            "CSAFPID-0007",
            "CSAFPID-0008",
            "CSAFPID-0009",
            "CSAFPID-0010"
          ],
          "url": "https://support.industry.siemens.com/cs/de/en/"
        },
        {
          "category": "mitigation",
          "details": "SIMATIC WinCC Runtime Professional V13: Update to WinCC Runtime Professional V13 SP1 Update 9: (https://support.industry.siemens.com/cs/ww/en/view/109311724)",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005",
            "CSAFPID-0006",
            "CSAFPID-0007",
            "CSAFPID-0008",
            "CSAFPID-0009",
            "CSAFPID-0010"
          ],
          "url": "https://support.industry.siemens.com/cs/ww/en/view/109311724"
        },
        {
          "category": "mitigation",
          "details": "Until updates can be applied, Siemens recommends the following steps to mitigate the risk: Always run WinCC, WinCC Runtime Professional, and PCS 7 stations within a trusted network.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005",
            "CSAFPID-0006",
            "CSAFPID-0007",
            "CSAFPID-0008",
            "CSAFPID-0009",
            "CSAFPID-0010"
          ]
        },
        {
          "category": "mitigation",
          "details": "Ensure that WinCC, WinCC Runtime Professional, and PCS 7 stations communicate via encrypted channels only (e.g., activate feature \u201cEncrypted Communications\u201d in WinCC V7.3 and PCS 7 V8.1 SP1, or establish a VPN tunnel).",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005",
            "CSAFPID-0006",
            "CSAFPID-0007",
            "CSAFPID-0008",
            "CSAFPID-0009",
            "CSAFPID-0010"
          ]
        },
        {
          "category": "mitigation",
          "details": "Restrict access to the WinCC, WinCC Runtime Professional and PCS 7 stations to trusted entities.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005",
            "CSAFPID-0006",
            "CSAFPID-0007",
            "CSAFPID-0008",
            "CSAFPID-0009",
            "CSAFPID-0010"
          ]
        },
        {
          "category": "mitigation",
          "details": "Apply up-to-date application whitelisting software and virus scanners.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005",
            "CSAFPID-0006",
            "CSAFPID-0007",
            "CSAFPID-0008",
            "CSAFPID-0009",
            "CSAFPID-0010"
          ]
        },
        {
          "category": "mitigation",
          "details": "For more information on these vulnerabilities and more detailed mitigation instructions, please see Siemens Security Advisory SSA-378531 at the following location: (http://www.siemens.com/cert/en/cert-security-advisories.htm)",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005",
            "CSAFPID-0006",
            "CSAFPID-0007",
            "CSAFPID-0008",
            "CSAFPID-0009",
            "CSAFPID-0010"
          ],
          "url": "http://www.siemens.com/cert/en/cert-security-advisories.htm"
        },
        {
          "category": "mitigation",
          "details": "As a general security measure Siemens strongly recommends protecting network access to the WinCC and PCS 7 stations with appropriate mechanisms. Siemens advises configuring the environment according to Siemens operational guidelines in order to run the devices in a protected IT environment. (https://www.siemens.com/cert/operational-guidelines-industrial-security)",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005",
            "CSAFPID-0006",
            "CSAFPID-0007",
            "CSAFPID-0008",
            "CSAFPID-0009",
            "CSAFPID-0010"
          ],
          "url": "https://www.siemens.com/cert/operational-guidelines-industrial-security"
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "baseScore": 7.5,
            "baseSeverity": "HIGH",
            "vectorString": "CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N",
            "version": "3.0"
          },
          "products": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005",
            "CSAFPID-0006",
            "CSAFPID-0007",
            "CSAFPID-0008",
            "CSAFPID-0009",
            "CSAFPID-0010"
          ]
        }
      ]
    }
  ]
}


Log in or create an account to share your comment.




Tags
Taxonomy of the tags.


Loading…

Loading…

Loading…

Sightings

Author Source Type Date

Nomenclature

  • Seen: The vulnerability was mentioned, discussed, or seen somewhere by the user.
  • Confirmed: The vulnerability is confirmed from an analyst perspective.
  • Exploited: This vulnerability was exploited and seen by the user reporting the sighting.
  • Patched: This vulnerability was successfully patched by the user reporting the sighting.
  • Not exploited: This vulnerability was not exploited or seen by the user reporting the sighting.
  • Not confirmed: The user expresses doubt about the veracity of the vulnerability.
  • Not patched: This vulnerability was not successfully patched by the user reporting the sighting.


Loading…

Loading…