icsa-17-243-01
Vulnerability from csaf_cisa
Published
2017-08-31 00:00
Modified
2022-04-14 00:00
Summary
Siemens OPC UA Protocol Stack Discovery Service (Update E)

Notes

CISA Disclaimer
This CSAF advisory was extracted from unstructured data and may contain inaccuracies. If you notice any errors, please reach out to the designated contact at CISA CSAF: central@cisa.dhs.gov
Legal Notice
All information products included in https://us-cert.cisa.gov/ics are provided "as is" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see https://us-cert.cisa.gov/tlp/.
Risk evaluation
Successful exploitation of this vulnerability may allow an attacker to access various resources.
Critical infrastructure sectors
Chemical, Energy, Food and Agriculture, Water and Wastewater Systems
Countries/areas deployed
Worldwide
Company headquarters location
Germany
Recommended Practices
CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures. CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov. Several recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.
Recommended Practices
Additional mitigation guidance and recommended practices are publicly available on the ICS webpage on cisa.gov in the Technical Information Paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies. Organizations observing any suspected malicious activity should follow their established internal procedures and report their findings to CISA for tracking and correlation against other incidents.
Additional Resources
For further inquiries on security vulnerabilities in Siemens products and solutions, please contact the Siemens ProductCERT: https://www.siemens.com/cert/advisories
Exploitability
No known public exploits specifically target this vulnerability.



{
  "document": {
    "acknowledgments": [
      {
        "names": [
          "Sergey Temnikov"
        ],
        "organization": "Kaspersky Lab",
        "summary": "reporting this vulnerability to Siemens"
      }
    ],
    "category": "csaf_security_advisory",
    "csaf_version": "2.0",
    "distribution": {
      "text": "Disclosure is not limited",
      "tlp": {
        "label": "WHITE",
        "url": "https://us-cert.cisa.gov/tlp/"
      }
    },
    "lang": "en-US",
    "notes": [
      {
        "category": "general",
        "text": "This CSAF advisory was extracted from unstructured data and may contain inaccuracies. If you notice any errors, please reach out to the designated contact at CISA CSAF: central@cisa.dhs.gov",
        "title": "CISA Disclaimer"
      },
      {
        "category": "legal_disclaimer",
        "text": "All information products included in https://us-cert.cisa.gov/ics are provided \"as is\" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see https://us-cert.cisa.gov/tlp/.",
        "title": "Legal Notice"
      },
      {
        "category": "summary",
        "text": "Successful exploitation of this vulnerability may allow an attacker to access various resources.",
        "title": "Risk evaluation"
      },
      {
        "category": "other",
        "text": "Chemical, Energy, Food and Agriculture, Water and Wastewater Systems",
        "title": "Critical infrastructure sectors"
      },
      {
        "category": "other",
        "text": "Worldwide",
        "title": "Countries/areas deployed"
      },
      {
        "category": "other",
        "text": "Germany",
        "title": "Company headquarters location"
      },
      {
        "category": "general",
        "text": "CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.\nCISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov. Several recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.",
        "title": "Recommended Practices"
      },
      {
        "category": "general",
        "text": "Additional mitigation guidance and recommended practices are publicly available on the ICS webpage on cisa.gov in the Technical Information Paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.\nOrganizations observing any suspected malicious activity should follow their established internal procedures and report their findings to CISA for tracking and correlation against other incidents.",
        "title": "Recommended Practices"
      },
      {
        "category": "general",
        "text": "For further inquiries on security vulnerabilities in Siemens products and solutions, please contact the Siemens ProductCERT: https://www.siemens.com/cert/advisories",
        "title": "Additional Resources"
      },
      {
        "category": "other",
        "text": "No known public exploits specifically target this vulnerability.",
        "title": "Exploitability"
      }
    ],
    "publisher": {
      "category": "coordinator",
      "contact_details": "Email: CISAservicedesk@cisa.dhs.gov;\n Toll Free: 1-888-282-0870",
      "name": "CISA",
      "namespace": "https://www.cisa.gov/"
    },
    "references": [
      {
        "category": "external",
        "summary": "SSA-535640: Vulnerability in Industrial Products - CSAF Version",
        "url": "https://cert-portal.siemens.com/productcert/csaf/ssa-535640.json"
      },
      {
        "category": "self",
        "summary": "ICS Advisory ICSA-17-243-01 JSON",
        "url": "https://raw.githubusercontent.com/cisagov/CSAF/develop/csaf_files/OT/white/2017/icsa-17-243-01.json"
      },
      {
        "category": "self",
        "summary": "ICS Advisory ICSA-17-243-01 Web Version",
        "url": "https://www.cisa.gov/news-events/ics-advisories/icsa-17-243-01"
      },
      {
        "category": "external",
        "summary": "Recommended Practices",
        "url": "https://www.cisa.gov/uscert/sites/default/files/recommended_practices/NCCIC_ICS-CERT_Defense_in_Depth_2016_S508C.pdf"
      },
      {
        "category": "external",
        "summary": "Recommended Practices",
        "url": "https://www.cisa.gov/uscert/ics/tips/ICS-TIP-12-146-01B"
      },
      {
        "category": "external",
        "summary": "SSA-535640: Vulnerability in Industrial Products - PDF Version",
        "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-535640.pdf"
      },
      {
        "category": "external",
        "summary": "SSA-535640: Vulnerability in Industrial Products - TXT Version",
        "url": "https://cert-portal.siemens.com/productcert/txt/ssa-535640.txt"
      }
    ],
    "title": "Siemens OPC UA Protocol Stack Discovery Service (Update E)",
    "tracking": {
      "current_release_date": "2022-04-14T00:00:00.000000Z",
      "generator": {
        "engine": {
          "name": "CISA CSAF Generator",
          "version": "1.0.0"
        }
      },
      "id": "ICSA-17-243-01",
      "initial_release_date": "2017-08-31T00:00:00.000000Z",
      "revision_history": [
        {
          "date": "2017-08-31T00:00:00.000000Z",
          "legacy_version": "Initial",
          "number": "1",
          "summary": "ICSA-17-243-01 Siemens OPC UA Protocol Stack Discovery Service"
        },
        {
          "date": "2017-10-03T00:00:00.000000Z",
          "legacy_version": "A",
          "number": "2",
          "summary": "ICSA-17-243-01A Siemens Industrial products using the Discovery Service of the OPC UA protocol stack by the OPC foundation (Update A)"
        },
        {
          "date": "2017-11-30T00:00:00.000000Z",
          "legacy_version": "B",
          "number": "3",
          "summary": "ICSA-17-243-01B Siemens Industrial products using the Discovery Service of the OPC UA protocol stack by the OPC foundation (Update B)"
        },
        {
          "date": "2019-02-05T00:00:00.000000Z",
          "legacy_version": "C",
          "number": "4",
          "summary": "ICSA-17-243-01 Siemens Discovery Service of OPC UA Protocol (Update C)"
        },
        {
          "date": "2020-08-11T00:00:00.000000Z",
          "legacy_version": "D",
          "number": "5",
          "summary": "ICSA-17-243-01 Siemens OPC UA Protocol Stack Discovery Service (Update D)"
        },
        {
          "date": "2022-04-14T00:00:00.000000Z",
          "legacy_version": "E",
          "number": "6",
          "summary": "ICSA-17-243-01 Siemens OPC UA Protocol Stack Discovery Service (Update E)"
        }
      ],
      "status": "final",
      "version": "6"
    }
  },
  "product_tree": {
    "branches": [
      {
        "branches": [
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "All Versions \u003e= V6.5 and \u003c V7.1",
                "product": {
                  "name": "SIMATIC IT Production Suite",
                  "product_id": "CSAFPID-0001"
                }
              }
            ],
            "category": "product_name",
            "name": "SIMATIC IT Production Suite"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "\u003c V14 SP1 Update 14",
                "product": {
                  "name": "SIMATIC NET PC Software V14",
                  "product_id": "CSAFPID-0002"
                }
              }
            ],
            "category": "product_name",
            "name": "SIMATIC NET PC Software V14"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "Versions V8.0, V8.1",
                "product": {
                  "name": "SIMATIC PCS 7",
                  "product_id": "CSAFPID-0003"
                }
              }
            ],
            "category": "product_name",
            "name": "SIMATIC PCS 7"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "All Versions \u003c V7.2",
                "product": {
                  "name": "SIMATIC WinCC",
                  "product_id": "CSAFPID-0004"
                }
              }
            ],
            "category": "product_name",
            "name": "SIMATIC WinCC"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "All Versions",
                "product": {
                  "name": "SIMATIC WinCC Runtime Professional V13",
                  "product_id": "CSAFPID-0005"
                }
              }
            ],
            "category": "product_name",
            "name": "SIMATIC WinCC Runtime Professional V13"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "All Versions \u003c V14 SP1",
                "product": {
                  "name": "SIMATIC WinCC Runtime Professional V14",
                  "product_id": "CSAFPID-0006"
                }
              }
            ],
            "category": "product_name",
            "name": "SIMATIC WinCC Runtime Professional V14"
          }
        ],
        "category": "vendor",
        "name": "Siemens"
      }
    ]
  },
  "vulnerabilities": [
    {
      "cve": "CVE-2017-12069",
      "cwe": {
        "id": "CWE-611",
        "name": "Improper Restriction of XML External Entity Reference"
      },
      "notes": [
        {
          "category": "summary",
          "text": "By sending specially crafted packets to the OPC Discovery Server at port 4840/tcp, an attacker might cause the system to access various resources chosen by the attacker. To execute the attack, the attacker must have network access to the affected devices.",
          "title": "Summary"
        }
      ],
      "product_status": {
        "known_affected": [
          "CSAFPID-0001",
          "CSAFPID-0002",
          "CSAFPID-0003",
          "CSAFPID-0004",
          "CSAFPID-0005",
          "CSAFPID-0006"
        ]
      },
      "references": [
        {
          "summary": "CVE-2017-12069 - SIMATIC NET PC Software V14",
          "url": "https://support.industry.siemens.com/cs/ww/en/view/109807351/"
        },
        {
          "summary": "CVE-2017-12069 - SIMATIC WinCC Runtime Professional V14",
          "url": "https://support.industry.siemens.com/cs/ww/en/view/109746276"
        },
        {
          "summary": "CVE-2017-12069 Mitre 5.0 json",
          "url": "https://cert-portal.siemens.com/productcert/mitre/CVE-2017-12069.json"
        },
        {
          "category": "external",
          "summary": "web.nvd.nist.gov",
          "url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2017-12069"
        },
        {
          "category": "external",
          "summary": "www.first.org",
          "url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:N/A:H"
        }
      ],
      "remediations": [
        {
          "category": "vendor_fix",
          "details": "Update to V7.1 or later version",
          "product_ids": [
            "CSAFPID-0001"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "Update to V14 SP1 Update 14 or later version",
          "product_ids": [
            "CSAFPID-0002"
          ],
          "url": "https://support.industry.siemens.com/cs/ww/en/view/109807351/"
        },
        {
          "category": "no_fix_planned",
          "details": "Currently no fix is planned",
          "product_ids": [
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "Update to V14 SP1 or later version",
          "product_ids": [
            "CSAFPID-0006"
          ],
          "url": "https://support.industry.siemens.com/cs/ww/en/view/109746276"
        },
        {
          "category": "mitigation",
          "details": "Turn off the Discovery Service after commissioning or block it on the local firewall: https://support.industry.siemens.com/cs/ww/en/view/109749461",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005",
            "CSAFPID-0006"
          ]
        },
        {
          "category": "mitigation",
          "details": "Use VPN for protecting network communication between cells",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005",
            "CSAFPID-0006"
          ]
        },
        {
          "category": "mitigation",
          "details": "As a general security measure, Siemens strongly recommends to protect network access to devices with appropriate mechanisms. In order to operate the devices in a protected IT environment, Siemens recommends to configure the environment according to Siemens\u0027 operational guidelines for Industrial Security (Download: https://www.siemens.com/cert/operational-guidelines-industrial-security), and to follow the recommendations in the product manuals.\n\nAdditional information on Industrial Security by Siemens can be found at: https://www.siemens.com/industrialsecurity",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005",
            "CSAFPID-0006"
          ]
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "baseScore": 8.2,
            "baseSeverity": "HIGH",
            "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:N/A:H/E:P/RL:O/RC:C",
            "version": "3.1"
          },
          "products": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005",
            "CSAFPID-0006"
          ]
        }
      ],
      "title": "CVE-2017-12069"
    }
  ]
}


Log in or create an account to share your comment.




Tags
Taxonomy of the tags.


Loading...

Loading...

Loading...

Sightings

Author Source Type Date

Nomenclature

  • Seen: The vulnerability was mentioned, discussed, or seen somewhere by the user.
  • Confirmed: The vulnerability is confirmed from an analyst perspective.
  • Exploited: This vulnerability was exploited and seen by the user reporting the sighting.
  • Patched: This vulnerability was successfully patched by the user reporting the sighting.
  • Not exploited: This vulnerability was not exploited or seen by the user reporting the sighting.
  • Not confirmed: The user expresses doubt about the veracity of the vulnerability.
  • Not patched: This vulnerability was not successfully patched by the user reporting the sighting.