icsa-18-254-04
Vulnerability from csaf_cisa
Published
2018-09-11 00:00
Modified
2018-09-11 00:00
Summary
Siemens SIMATIC WinCC OA
Notes
CISA Disclaimer
This CSAF advisory was extracted from unstructured data and may contain inaccuracies. If you notice any errors, please reach out to the designated contact at CISA CSAF: central@cisa.dhs.gov
Legal Notice
All information products included in https://us-cert.cisa.gov/ics are provided "as is" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see https://us-cert.cisa.gov/tlp/.
Risk evaluation
Successful exploitation of this vulnerability could allow an unauthenticated remote user to escalate their privileges in the context of the program.
Critical infrastructure sectors
Chemical, Energy, Food and Agriculture, and Water and Wastewater Systems
Countries/areas deployed
Worldwide
Company headquarters location
Germany
Recommended Practices
NCCIC recommends users take defensive measures to minimize the risk of exploitation of this vulnerability. Specifically, users should:
Recommended Practices
NCCIC reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.NCCIC also provides a section for control systems security recommended practices on the ICS-CERT web page. Several recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.
Recommended Practices
Additional mitigation guidance and recommended practices are publicly available on the ICS-CERT website in the Technical Information Paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.Organizations observing any suspected malicious activity should follow their established internal procedures and report their findings to NCCIC for tracking and correlation against other incidents.
Additional Resources
For further inquiries on security vulnerabilities in Siemens products and
solutions, please contact the Siemens ProductCERT:
https://www.siemens.com/cert/advisories
Additional Resources
For further inquiries on security vulnerabilities in Siemens products and solutions, please contact the Siemens ProductCERT: https://www.siemens.com/cert/advisories
Exploitability
No known public exploits specifically target this vulnerability.
{ "document": { "acknowledgments": [ { "organization": "Siemens", "summary": "reporting this vulnerability to NCCIC" } ], "category": "csaf_security_advisory", "csaf_version": "2.0", "distribution": { "text": "Disclosure is not limited", "tlp": { "label": "WHITE", "url": "https://us-cert.cisa.gov/tlp/" } }, "lang": "en-US", "notes": [ { "category": "general", "text": "This CSAF advisory was extracted from unstructured data and may contain inaccuracies. If you notice any errors, please reach out to the designated contact at CISA CSAF: central@cisa.dhs.gov", "title": "CISA Disclaimer" }, { "category": "legal_disclaimer", "text": "All information products included in https://us-cert.cisa.gov/ics are provided \"as is\" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see https://us-cert.cisa.gov/tlp/.", "title": "Legal Notice" }, { "category": "summary", "text": "Successful exploitation of this vulnerability could allow an unauthenticated remote user to escalate their privileges in the context of the program.", "title": "Risk evaluation" }, { "category": "other", "text": "Chemical, Energy, Food and Agriculture, and Water and Wastewater Systems", "title": "Critical infrastructure sectors" }, { "category": "other", "text": "Worldwide", "title": "Countries/areas deployed" }, { "category": "other", "text": "Germany", "title": "Company headquarters location" }, { "category": "general", "text": "NCCIC recommends users take defensive measures to minimize the risk of exploitation of this vulnerability. Specifically, users should:", "title": "Recommended Practices" }, { "category": "general", "text": "NCCIC reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.NCCIC also provides a section for control systems security recommended practices on the ICS-CERT web page. Several recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.", "title": "Recommended Practices" }, { "category": "general", "text": "Additional mitigation guidance and recommended practices are publicly available on the ICS-CERT website in the Technical Information Paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.Organizations observing any suspected malicious activity should follow their established internal procedures and report their findings to NCCIC for tracking and correlation against other incidents.", "title": "Recommended Practices" }, { "category": "general", "text": "For further inquiries on security vulnerabilities in Siemens products and \nsolutions, please contact the Siemens ProductCERT:\n\nhttps://www.siemens.com/cert/advisories", "title": "Additional Resources" }, { "category": "general", "text": "For further inquiries on security vulnerabilities in Siemens products and solutions, please contact the Siemens ProductCERT: https://www.siemens.com/cert/advisories", "title": "Additional Resources" }, { "category": "other", "text": "No known public exploits specifically target this vulnerability.", "title": "Exploitability" } ], "publisher": { "category": "coordinator", "contact_details": "Email: CISAservicedesk@cisa.dhs.gov;\n Toll Free: 1-888-282-0870", "name": "CISA", "namespace": "https://www.cisa.gov/" }, "references": [ { "category": "self", "summary": "ICS Advisory ICSA-18-254-04 JSON", "url": "https://raw.githubusercontent.com/cisagov/CSAF/develop/csaf_files/OT/white/2018/icsa-18-254-04.json" }, { "category": "self", "summary": "ICS Advisory ICSA-18-254-04 Web Version", "url": "https://www.cisa.gov/news-events/ics-advisories/icsa-18-254-04" }, { "category": "external", "summary": "Recommended Practices", "url": "https://www.cisa.gov/uscert/ics/alerts/ICS-ALERT-10-301-01" }, { "category": "external", "summary": "Recommended Practices", "url": "https://www.cisa.gov/uscert/sites/default/files/recommended_practices/NCCIC_ICS-CERT_Defense_in_Depth_2016_S508C.pdf" }, { "category": "external", "summary": "Recommended Practices", "url": "https://www.cisa.gov/uscert/ics/tips/ICS-TIP-12-146-01B" }, { "category": "external", "summary": "SSA-496604: SSA-346256: Vulnerability in SIMATIC WinCC OA V3.14 and prior - TXT Version", "url": "https://cert-portal.siemens.com/productcert/txt/SSA-346256.txt" } ], "title": "Siemens SIMATIC WinCC OA", "tracking": { "current_release_date": "2018-09-11T00:00:00.000000Z", "generator": { "engine": { "name": "CISA CSAF Generator", "version": "1.0.0" } }, "id": "ICSA-18-254-04", "initial_release_date": "2018-09-11T00:00:00.000000Z", "revision_history": [ { "date": "2018-09-11T00:00:00.000000Z", "legacy_version": "Initial", "number": "1", "summary": "ICSA-18-254-04 Siemens SIMATIC WinCC OA" } ], "status": "final", "version": "1" } }, "product_tree": { "branches": [ { "branches": [ { "branches": [ { "category": "product_version_range", "name": "All versions \u003c V3.14-P021", "product": { "name": "SIMATIC WinCC OA V3.14 and prior: All versions \u003c V3.14-P021", "product_id": "CSAFPID-0001" } } ], "category": "product_name", "name": "SIMATIC WinCC OA V3.14 and prior" } ], "category": "vendor", "name": "Siemens" } ] }, "vulnerabilities": [ { "cve": "CVE-2018-13799", "cwe": { "id": "CWE-284", "name": "Improper Access Control" }, "notes": [ { "category": "summary", "text": "Improper access control to a data point of the affected product could allow an unauthenticated remote user to escalate its privileges in the context of SIMATIC WinCC OA V3.14.", "title": "Summary" }, { "category": "summary", "text": "This vulnerability could be exploited by an attacker with network access to port 5678/TCP of the SIMATIC WinCC OA V3.14 server. Successful exploitation requires no user privileges and no user interaction. This vulnerability could allow an attacker to compromise integrity and availability of the SIMATIC WinCC OA system.", "title": "Summary" }, { "category": "summary", "text": "At the time of advisory publication no public exploitation of this vulnerability was known.", "title": "Summary" } ], "product_status": { "known_affected": [ "CSAFPID-0001" ] }, "references": [ { "category": "external", "summary": "https://portal.etm.at/index.php?option=com_content\u0026view=category\u0026id=67\u0026layout=blog\u0026Itemid=80", "url": "https://portal.etm.at/index.php?option=com_content\u0026view=category\u0026id=67\u0026layout=blog\u0026Itemid=80" }, { "category": "external", "summary": "web.nvd.nist.gov", "url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2018-13799" }, { "category": "external", "summary": "www.first.org", "url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:H/A:H" } ], "remediations": [ { "category": "vendor_fix", "details": "The steps described at\nhttps://portal.etm.at/patchdownload.php?fp=version_3.14/win64vc12/ReadmeP021.txt\nallow manual remediation of the vulnerability fixed by WinCC OA\nV3.14-P021.", "product_ids": [ "CSAFPID-0001" ] }, { "category": "vendor_fix", "details": "Follow the SIMATIC WinCC OA Security Guideline (available at\nhttps://portal.etm.at/index.php?option=com_phocadownload\u0026view=category\u0026id=52:security\u0026Itemid=81)\nfor maintaining a secured SIMATIC WinCC OA environment.", "product_ids": [ "CSAFPID-0001" ] }, { "category": "vendor_fix", "details": "Apply Defense-in-Depth:\nhttps://www.siemens.com/cert/operational-guidelines-industrial-security", "product_ids": [ "CSAFPID-0001" ] }, { "category": "vendor_fix", "details": "Update to V3.14-P021 and follow the steps at https://portal.etm.at/patchdownload.php?fp=version_3.14/win64vc12/ReadmeP021.txt for adding of modifying WinCC OA users in AD environments. - Download: https://portal.etm.at/index.php?option=com_content\u0026view=category\u0026id=67\u0026layout=blog\u0026Itemid=80 ", "product_ids": [ "CSAFPID-0001" ], "url": "https://portal.etm.at/index.php?option=com_content\u0026view=category\u0026id=67\u0026layout=blog\u0026Itemid=80" }, { "category": "mitigation", "details": "As a general security measure, Siemens strongly recommends to protect network access to devices with appropriate mechanisms. In order to operate the devices in a protected IT environment, Siemens recommends to configure the environment according to Siemens\u0027 operational guidelines for Industrial Security (Download: https://www.siemens.com/cert/operational-guidelines-industrial-security), and to follow the recommendations in the product manuals. Additional information on Industrial Security by Siemens can be found at: https://www.siemens.com/industrialsecurity", "product_ids": [ "CSAFPID-0001" ] } ], "scores": [ { "cvss_v3": { "baseScore": 9.1, "baseSeverity": "CRITICAL", "vectorString": "CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:H/A:H/E:P/RL:O/RC:C", "version": "3.0" }, "products": [ "CSAFPID-0001" ] } ] } ] }
Loading...
Loading...
Sightings
Author | Source | Type | Date |
---|
Nomenclature
- Seen: The vulnerability was mentioned, discussed, or seen somewhere by the user.
- Confirmed: The vulnerability is confirmed from an analyst perspective.
- Exploited: This vulnerability was exploited and seen by the user reporting the sighting.
- Patched: This vulnerability was successfully patched by the user reporting the sighting.
- Not exploited: This vulnerability was not exploited or seen by the user reporting the sighting.
- Not confirmed: The user expresses doubt about the veracity of the vulnerability.
- Not patched: This vulnerability was not successfully patched by the user reporting the sighting.