icsa-19-094-04
Vulnerability from csaf_cisa
Published
2019-04-04 00:00
Modified
2019-04-04 00:00
Summary
Rockwell Automation Stratix 5950

Notes

CISA Disclaimer
This CSAF advisory was extracted from unstructured data and may contain inaccuracies. If you notice any errors, please reach out to the designated contact at CISA CSAF: central@cisa.dhs.gov
Legal Notice
All information products included in https://us-cert.cisa.gov/ics are provided "as is" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see https://us-cert.cisa.gov/tlp/.
Risk evaluation
Successful exploitation of this vulnerability could allow a remote attacker to cause an affected device to reload.
Critical infrastructure sectors
Critical Manufacturing, Energy, Water and Wastewater Systems
Countries/areas deployed
Worldwide
Company headquarters location
United States
Recommended Practices
NCCIC reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.
Recommended Practices
NCCIC also provides a section for control systems security recommended practices on the ICS-CERT web page. Several recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.
Recommended Practices
Additional mitigation guidance and recommended practices are publicly available on the ICS-CERT website in the Technical Information Paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.Organizations observing any suspected malicious activity should follow their established internal procedures and report their findings to NCCIC for tracking and correlation against other incidents.
Exploitability
No known public exploits specifically target this vulnerability.



{
  "document": {
    "acknowledgments": [
      {
        "organization": "Rockwell Automation",
        "summary": "reporting this vulnerability to NCCIC"
      }
    ],
    "category": "csaf_security_advisory",
    "csaf_version": "2.0",
    "distribution": {
      "text": "Disclosure is not limited",
      "tlp": {
        "label": "WHITE",
        "url": "https://us-cert.cisa.gov/tlp/"
      }
    },
    "lang": "en-US",
    "notes": [
      {
        "category": "general",
        "text": "This CSAF advisory was extracted from unstructured data and may contain inaccuracies. If you notice any errors, please reach out to the designated contact at CISA CSAF: central@cisa.dhs.gov",
        "title": "CISA Disclaimer"
      },
      {
        "category": "legal_disclaimer",
        "text": "All information products included in https://us-cert.cisa.gov/ics are provided \"as is\" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see https://us-cert.cisa.gov/tlp/.",
        "title": "Legal Notice"
      },
      {
        "category": "summary",
        "text": "Successful exploitation of this vulnerability could allow a remote attacker to cause an affected device to reload.",
        "title": "Risk evaluation"
      },
      {
        "category": "other",
        "text": "Critical Manufacturing, Energy, Water and Wastewater Systems",
        "title": "Critical infrastructure sectors"
      },
      {
        "category": "other",
        "text": "Worldwide",
        "title": "Countries/areas deployed"
      },
      {
        "category": "other",
        "text": "United States",
        "title": "Company headquarters location"
      },
      {
        "category": "general",
        "text": "NCCIC reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.",
        "title": "Recommended Practices"
      },
      {
        "category": "general",
        "text": "NCCIC also provides a section for control systems security recommended practices on the ICS-CERT web page. Several recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.",
        "title": "Recommended Practices"
      },
      {
        "category": "general",
        "text": "Additional mitigation guidance and recommended practices are publicly available on the ICS-CERT website in the Technical Information Paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.Organizations observing any suspected malicious activity should follow their established internal procedures and report their findings to NCCIC for tracking and correlation against other incidents.",
        "title": "Recommended Practices"
      },
      {
        "category": "other",
        "text": "No known public exploits specifically target this vulnerability.",
        "title": "Exploitability"
      }
    ],
    "publisher": {
      "category": "coordinator",
      "contact_details": "Email: CISAservicedesk@cisa.dhs.gov;\n Toll Free: 1-888-282-0870",
      "name": "CISA",
      "namespace": "https://www.cisa.gov/"
    },
    "references": [
      {
        "category": "self",
        "summary": "ICS Advisory ICSA-19-094-04 JSON",
        "url": "https://raw.githubusercontent.com/cisagov/CSAF/develop/csaf_files/OT/white/2019/icsa-19-094-04.json"
      },
      {
        "category": "self",
        "summary": "ICS Advisory ICSA-19-094-04 Web Version",
        "url": "https://www.cisa.gov/news-events/ics-advisories/icsa-19-094-04"
      },
      {
        "category": "external",
        "summary": "Recommended Practices",
        "url": "https://www.cisa.gov/news-events/ics-advisories/icsa-19-094-04"
      },
      {
        "category": "external",
        "summary": "Recommended Practices",
        "url": "https://www.cisa.gov/uscert/sites/default/files/recommended_practices/NCCIC_ICS-CERT_Defense_in_Depth_2016_S508C.pdf"
      },
      {
        "category": "external",
        "summary": "Recommended Practices",
        "url": "https://www.cisa.gov/uscert/ics/tips/ICS-TIP-12-146-01B"
      }
    ],
    "title": "Rockwell Automation Stratix 5950",
    "tracking": {
      "current_release_date": "2019-04-04T00:00:00.000000Z",
      "generator": {
        "engine": {
          "name": "CISA CSAF Generator",
          "version": "1.0.0"
        }
      },
      "id": "ICSA-19-094-04",
      "initial_release_date": "2019-04-04T00:00:00.000000Z",
      "revision_history": [
        {
          "date": "2019-04-04T00:00:00.000000Z",
          "legacy_version": "Initial",
          "number": "1",
          "summary": "ICSA-19-094-04 Rockwell Automation Stratix 5950"
        }
      ],
      "status": "final",
      "version": "1"
    }
  },
  "product_tree": {
    "branches": [
      {
        "branches": [
          {
            "branches": [
              {
                "category": "product_version",
                "name": "1783-SAD4T0SBK9",
                "product": {
                  "name": "Allen-Bradley Stratix 5950: 1783-SAD4T0SBK9",
                  "product_id": "CSAFPID-0001"
                }
              }
            ],
            "category": "product_name",
            "name": "Allen-Bradley Stratix 5950"
          },
          {
            "branches": [
              {
                "category": "product_version",
                "name": "1783-SAD2T2SBK9",
                "product": {
                  "name": "Allen-Bradley Stratix 5950: 1783-SAD2T2SBK9",
                  "product_id": "CSAFPID-0002"
                }
              }
            ],
            "category": "product_name",
            "name": "Allen-Bradley Stratix 5950"
          },
          {
            "branches": [
              {
                "category": "product_version",
                "name": "1783-SAD4T0SPK9",
                "product": {
                  "name": "Allen-Bradley Stratix 5950: 1783-SAD4T0SPK9",
                  "product_id": "CSAFPID-0003"
                }
              }
            ],
            "category": "product_name",
            "name": "Allen-Bradley Stratix 5950"
          },
          {
            "branches": [
              {
                "category": "product_version",
                "name": "1783-SAD2T2SPK9",
                "product": {
                  "name": "Allen-Bradley Stratix 5950: 1783-SAD2T2SPK9",
                  "product_id": "CSAFPID-0004"
                }
              }
            ],
            "category": "product_name",
            "name": "Allen-Bradley Stratix 5950"
          }
        ],
        "category": "vendor",
        "name": "Rockwell Automation"
      }
    ]
  },
  "vulnerabilities": [
    {
      "cve": "CVE-2018-0472",
      "cwe": {
        "id": "CWE-20",
        "name": "Improper Input Validation"
      },
      "notes": [
        {
          "category": "summary",
          "text": "Sending malformed IPsec packets to an affected device could allow an unauthenticated remote attacker to cause the device to reload. IPsec is disabled by default in the Allen-Bradley Stratix 5950 devices.CVE-2018-0472 has been assigned to this vulnerability. A CVSS v3 base score of 8.6 has been assigned; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:C/C:N/I:N/A:H).",
          "title": "Vulnerability Summary"
        }
      ],
      "product_status": {
        "known_affected": [
          "CSAFPID-0001",
          "CSAFPID-0002",
          "CSAFPID-0003",
          "CSAFPID-0004"
        ]
      },
      "references": [
        {
          "category": "external",
          "summary": "web.nvd.nist.gov",
          "url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2018-0472"
        },
        {
          "category": "external",
          "summary": "www.first.org",
          "url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:C/C:N/I:N/A:H"
        }
      ],
      "remediations": [
        {
          "category": "vendor_fix",
          "details": "IPsec is disabled by default in the Allen-Bradley Stratix 5950 devices.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004"
          ]
        },
        {
          "category": "mitigation",
          "details": "Rockwell Automation recommends that users not use any IPsec virtual private network (VPN) connections",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004"
          ]
        },
        {
          "category": "mitigation",
          "details": "LAN-to-LAN IPsec VPN",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004"
          ]
        },
        {
          "category": "mitigation",
          "details": "Remote-access VPN using the IPsec VPN client",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004"
          ]
        },
        {
          "category": "mitigation",
          "details": "Layer 2 tunneling protocol (L2TP)-over-IPsec VPN connections",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004"
          ]
        },
        {
          "category": "mitigation",
          "details": "Utilize proper network infrastructure controls, such as firewalls, to help ensure that requests from unauthorized sources are blocked and the controls are isolated from the business network.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004"
          ]
        },
        {
          "category": "mitigation",
          "details": "Consult the product documentation for specific features, such as access control lists and deep pack inspection, which may be used to block unauthorized changes, etc.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004"
          ]
        },
        {
          "category": "mitigation",
          "details": "Block all traffic to EtherNet/IP, or other CIP protocol-based devices, from outside the manufacturing zone by blocking or restricting access to TCP and UDP Port 2222 and Port 44818 using proper network infrastructure controls, such as firewalls, UTM devices, or other security appliances. For more information on TCP/UDP ports used by Rockwell Automation Products, see Knowledgebase Article ID 898270.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004"
          ]
        },
        {
          "category": "mitigation",
          "details": "Minimize network exposure for all control system devices and/or systems and ensure that they are not accessible from the Internet",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004"
          ]
        },
        {
          "category": "mitigation",
          "details": "For additional information, see Rockwell Automation\u0027s security advisory",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004"
          ],
          "url": "https://rockwellautomation.custhelp.com/app/answers/detail/a_id/1082688"
        },
        {
          "category": "mitigation",
          "details": "Cisco\u0027s security disclosure for this vulnerability is available ",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004"
          ],
          "url": "https://tools.cisco.com/security/center/content/CiscoSecurityAdvisory/cisco-sa-20180926-ipsec"
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "baseScore": 8.6,
            "baseSeverity": "HIGH",
            "vectorString": "CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:C/C:N/I:N/A:H",
            "version": "3.0"
          },
          "products": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004"
          ]
        }
      ]
    }
  ]
}


Log in or create an account to share your comment.