icsa-20-294-02
Vulnerability from csaf_cisa
Published
2020-10-20 00:00
Modified
2020-10-20 00:00
Summary
Hitachi ABB Power Grids XMC20 Multiservice-Multiplexer
Notes
CISA Disclaimer
This CSAF advisory was extracted from unstructured data and may contain inaccuracies. If you notice any errors, please reach out to the designated contact at CISA CSAF: central@cisa.dhs.gov
Legal Notice
All information products included in https://us-cert.cisa.gov/ics are provided "as is" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see https://us-cert.cisa.gov/tlp/.
Risk evaluation
Successful exploitation of this vulnerability could allow an attacker to remotely take control of the product.
Critical infrastructure sectors
Energy Sector
Countries/areas deployed
Worldwide
Company headquarters location
Switzerland
Recommended Practices
CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.
CISA also provides a section for control systems security recommended practices on the ICS webpage onus-cert.cisa.gov. Several recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.
Recommended Practices
Additional mitigation guidance and recommended practices are publicly available on the ICS webpage on us-cert.cisa.gov in the Technical Information Paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.
Organizations observing any suspected malicious activity should follow their established internal procedures and report their findings to CISA for tracking and correlation against other incidents.
Exploitability
No known public exploits specifically target this vulnerability.
{ "document": { "acknowledgments": [ { "organization": "Hitachi ABB Power Grids", "summary": "reporting this vulnerability to CISA" } ], "category": "csaf_security_advisory", "csaf_version": "2.0", "distribution": { "text": "Disclosure is not limited", "tlp": { "label": "WHITE", "url": "https://us-cert.cisa.gov/tlp/" } }, "lang": "en-US", "notes": [ { "category": "general", "text": "This CSAF advisory was extracted from unstructured data and may contain inaccuracies. If you notice any errors, please reach out to the designated contact at CISA CSAF: central@cisa.dhs.gov", "title": "CISA Disclaimer" }, { "category": "legal_disclaimer", "text": "All information products included in https://us-cert.cisa.gov/ics are provided \"as is\" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see https://us-cert.cisa.gov/tlp/.", "title": "Legal Notice" }, { "category": "summary", "text": "Successful exploitation of this vulnerability could allow an attacker to remotely take control of the product.", "title": "Risk evaluation" }, { "category": "other", "text": "Energy Sector", "title": "Critical infrastructure sectors" }, { "category": "other", "text": "Worldwide", "title": "Countries/areas deployed" }, { "category": "other", "text": "Switzerland", "title": "Company headquarters location" }, { "category": "general", "text": "CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.\nCISA also provides a section for control systems security recommended practices on the ICS webpage onus-cert.cisa.gov. Several recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.", "title": "Recommended Practices" }, { "category": "general", "text": "Additional mitigation guidance and recommended practices are publicly available on the ICS webpage on us-cert.cisa.gov in the Technical Information Paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.\nOrganizations observing any suspected malicious activity should follow their established internal procedures and report their findings to CISA for tracking and correlation against other incidents.", "title": "Recommended Practices" }, { "category": "other", "text": "No known public exploits specifically target this vulnerability.", "title": "Exploitability" } ], "publisher": { "category": "coordinator", "contact_details": "Email: CISAservicedesk@cisa.dhs.gov;\n Toll Free: 1-888-282-0870", "name": "CISA", "namespace": "https://www.cisa.gov/" }, "references": [ { "category": "self", "summary": "ICS Advisory ICSA-20-294-02 JSON", "url": "https://raw.githubusercontent.com/cisagov/CSAF/develop/csaf_files/OT/white/2020/icsa-20-294-02.json" }, { "category": "self", "summary": "ICS Advisory ICSA-20-294-02 Web Version", "url": "https://www.cisa.gov/news-events/ics-advisories/icsa-20-294-02" }, { "category": "external", "summary": "Recommended Practices", "url": "https://www.us-cert.cisa.gov/sites/default/files/recommended_practices/NCCIC_ICS-CERT_Defense_in_Depth_2016_S508C.pdf" }, { "category": "external", "summary": "Recommended Practices", "url": "https://www.us-cert.gov/ics/tips/ICS-TIP-12-146-01B" } ], "title": "Hitachi ABB Power Grids XMC20 Multiservice-Multiplexer", "tracking": { "current_release_date": "2020-10-20T00:00:00.000000Z", "generator": { "engine": { "name": "CISA CSAF Generator", "version": "1.0.0" } }, "id": "ICSA-20-294-02", "initial_release_date": "2020-10-20T00:00:00.000000Z", "revision_history": [ { "date": "2020-10-20T00:00:00.000000Z", "legacy_version": "Initial", "number": "1", "summary": "ICSA-20-294-02 Hitachi ABB Power Grids XMC20 Multiservice-Multiplexer" } ], "status": "final", "version": "1" } }, "product_tree": { "branches": [ { "branches": [ { "branches": [ { "category": "product_version_range", "name": "\u003c co5ne_r2d14_03.esw", "product": { "name": "XMC20 R6 using COGE5: versions older than co5ne_r2d14_03.esw", "product_id": "CSAFPID-0001" } } ], "category": "product_name", "name": "XMC20 R6 using COGE5" }, { "branches": [ { "category": "product_version_range", "name": "\u003cco5ne_r1h07_12.esw", "product": { "name": "XMC20 R4 using COGE5: versions older than co5ne_r1h07_12.esw", "product_id": "CSAFPID-0002" } } ], "category": "product_name", "name": "XMC20 R4 using COGE5" } ], "category": "vendor", "name": "Hitachi Energy" } ] }, "vulnerabilities": [ { "cve": "CVE-2018-10933", "cwe": { "id": "CWE-287", "name": "Improper Authentication" }, "notes": [ { "category": "summary", "text": "A vulnerability exists in a specific library included in these products. An attacker could exploit the vulnerability by sending a specially crafted message to the XMC20 node to open a communication channel without first performing authentication, resulting in unauthorized access.CVE-2018-10933 has been assigned to this vulnerability. A CVSS v3 base score of 9.1 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:N).", "title": "Vulnerability Summary" } ], "product_status": { "known_affected": [ "CSAFPID-0001", "CSAFPID-0002" ] }, "references": [ { "category": "external", "summary": "web.nvd.nist.gov", "url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2018-10933" }, { "category": "external", "summary": "www.first.org", "url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:N" } ], "remediations": [ { "category": "mitigation", "details": "Hitachi ABB Power Grids has corrected the problem in the following product versions and recommends users apply the firmware update at the earliest availability", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002" ] }, { "category": "mitigation", "details": "XMC20 R4: COGE5 Version co5ne_r1h07_12.esw (and newer)", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002" ] }, { "category": "mitigation", "details": "XMC20 R6: COGE5 Version co5ne_r2d14_03.esw (and newer)", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002" ] }, { "category": "mitigation", "details": "For additional information and support please contact a product provider or a Hitachi ABB Power Grids service organization.", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002" ], "url": "https://www.hitachiabb-powergrids.com/contact-us/" }, { "category": "mitigation", "details": "Hitachi ABB Power Grids published cybersecurity advisory PGVU-PGGA-XMC20-2020034 to give users more information about this issue.", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002" ], "url": "https://search.abb.com/library/Download.aspx?DocumentID=9AKK107991A2862\u0026LanguageCode=en\u0026DocumentPartId=\u0026Action=Launch" }, { "category": "mitigation", "details": "Physically protect process control systems from direct access by unauthorized personnel.", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002" ] }, { "category": "mitigation", "details": "Do not directly connect control systems to the Internet.", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002" ] }, { "category": "mitigation", "details": "Separate control systems from other networks by means of a firewall system that has a minimal number of ports exposed.", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002" ] }, { "category": "mitigation", "details": "Do not use control systems networks for Internet browsing, instant messaging, or receiving e-mails.", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002" ] }, { "category": "mitigation", "details": "Portable computers and removable storage media should be carefully scanned for viruses before they are connected to a control system.", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002" ] } ], "scores": [ { "cvss_v3": { "baseScore": 9.1, "baseSeverity": "CRITICAL", "vectorString": "CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:N", "version": "3.0" }, "products": [ "CSAFPID-0001", "CSAFPID-0002" ] } ] } ] }
Loading...
Loading...
Sightings
Author | Source | Type | Date |
---|
Nomenclature
- Seen: The vulnerability was mentioned, discussed, or seen somewhere by the user.
- Confirmed: The vulnerability is confirmed from an analyst perspective.
- Exploited: This vulnerability was exploited and seen by the user reporting the sighting.
- Patched: This vulnerability was successfully patched by the user reporting the sighting.
- Not exploited: This vulnerability was not exploited or seen by the user reporting the sighting.
- Not confirmed: The user expresses doubt about the veracity of the vulnerability.
- Not patched: This vulnerability was not successfully patched by the user reporting the sighting.