icsa-21-285-02
Vulnerability from csaf_cisa
Published
2021-10-12 00:00
Modified
2021-10-12 00:00
Summary
Advantech WebAccess

Notes

CISA Disclaimer
This CSAF advisory was extracted from unstructured data and may contain inaccuracies. If you notice any errors, please reach out to the designated contact at CISA CSAF: central@cisa.dhs.gov
Legal Notice
All information products included in https://us-cert.cisa.gov/ics are provided "as is" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see https://us-cert.cisa.gov/tlp/.
Risk evaluation
Successful exploitation of these vulnerabilities could allow an attacker to gain remote code execution.
Critical infrastructure sectors
Critical Manufacturing, Energy, Water and Wastewater Systems
Countries/areas deployed
East Asia, Europe, United States
Company headquarters location
Taiwan
Recommended Practices
CISA recommends users take defensive measures to minimize the risk of exploitation of these vulnerabilities. Specifically, users should:
Recommended Practices
CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures. CISA also provides a section for control systems security recommended practices on the ICS webpage onus-cert.cisa.gov. Several recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.
Recommended Practices
Additional mitigation guidance and recommended practices are publicly available on the ICS webpage on us-cert.cisa.gov in the Technical Information Paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies. Organizations observing any suspected malicious activity should follow their established internal procedures and report their findings to CISA for tracking and correlation against other incidents.
Exploitability
No known public exploits specifically target these vulnerabilities.



{
  "document": {
    "acknowledgments": [
      {
        "names": [
          "Natnael Samson (NattiSamson)"
        ],
        "organization": "Trend Micro \u0027s Zero Day Initiative",
        "summary": "reporting these vulnerabilities to CISA"
      }
    ],
    "category": "csaf_security_advisory",
    "csaf_version": "2.0",
    "distribution": {
      "text": "Disclosure is not limited",
      "tlp": {
        "label": "WHITE",
        "url": "https://us-cert.cisa.gov/tlp/"
      }
    },
    "lang": "en-US",
    "notes": [
      {
        "category": "general",
        "text": "This CSAF advisory was extracted from unstructured data and may contain inaccuracies. If you notice any errors, please reach out to the designated contact at CISA CSAF: central@cisa.dhs.gov",
        "title": "CISA Disclaimer"
      },
      {
        "category": "legal_disclaimer",
        "text": "All information products included in https://us-cert.cisa.gov/ics are provided \"as is\" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see https://us-cert.cisa.gov/tlp/.",
        "title": "Legal Notice"
      },
      {
        "category": "summary",
        "text": "Successful exploitation of these vulnerabilities could allow an attacker to gain remote code execution.",
        "title": "Risk evaluation"
      },
      {
        "category": "other",
        "text": "Critical Manufacturing, Energy, Water and Wastewater Systems",
        "title": "Critical infrastructure sectors"
      },
      {
        "category": "other",
        "text": "East Asia, Europe, United States",
        "title": "Countries/areas deployed"
      },
      {
        "category": "other",
        "text": "Taiwan",
        "title": "Company headquarters location"
      },
      {
        "category": "general",
        "text": "CISA recommends users take defensive measures to minimize the risk of exploitation of these vulnerabilities. Specifically, users should:",
        "title": "Recommended Practices"
      },
      {
        "category": "general",
        "text": "CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.\nCISA also provides a section for control systems security recommended practices on the ICS webpage onus-cert.cisa.gov. Several recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.",
        "title": "Recommended Practices"
      },
      {
        "category": "general",
        "text": "Additional mitigation guidance and recommended practices are publicly available on the ICS webpage on us-cert.cisa.gov in the Technical Information Paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.\nOrganizations observing any suspected malicious activity should follow their established internal procedures and report their findings to CISA for tracking and correlation against other incidents.",
        "title": "Recommended Practices"
      },
      {
        "category": "other",
        "text": "No known public exploits specifically target these vulnerabilities.",
        "title": "Exploitability"
      }
    ],
    "publisher": {
      "category": "coordinator",
      "contact_details": "Email: CISAservicedesk@cisa.dhs.gov;\n Toll Free: 1-888-282-0870",
      "name": "CISA",
      "namespace": "https://www.cisa.gov/"
    },
    "references": [
      {
        "category": "self",
        "summary": "ICS Advisory ICSA-21-285-02 JSON",
        "url": "https://raw.githubusercontent.com/cisagov/CSAF/develop/csaf_files/OT/white/2021/icsa-21-285-02.json"
      },
      {
        "category": "self",
        "summary": "ICS Advisory ICSA-21-285-02 Web Version",
        "url": "https://www.cisa.gov/news-events/ics-advisories/icsa-21-285-02"
      },
      {
        "category": "external",
        "summary": "Recommended Practices",
        "url": "https://us-cert.cisa.gov/ics/alerts/ICS-ALERT-10-301-01"
      },
      {
        "category": "external",
        "summary": "Recommended Practices",
        "url": "https://us-cert.cisa.gov/sites/default/files/recommended_practices/NCCIC_ICS-CERT_Defense_in_Depth_2016_S508C.pdf"
      },
      {
        "category": "external",
        "summary": "Recommended Practices",
        "url": "https://us-cert.cisa.gov/ics/tips/ICS-TIP-12-146-01B"
      }
    ],
    "title": "Advantech WebAccess",
    "tracking": {
      "current_release_date": "2021-10-12T00:00:00.000000Z",
      "generator": {
        "engine": {
          "name": "CISA CSAF Generator",
          "version": "1.0.0"
        }
      },
      "id": "ICSA-21-285-02",
      "initial_release_date": "2021-10-12T00:00:00.000000Z",
      "revision_history": [
        {
          "date": "2021-10-12T00:00:00.000000Z",
          "legacy_version": "Initial",
          "number": "1",
          "summary": "ICSA-21-285-02 Advantech WebAccess"
        }
      ],
      "status": "final",
      "version": "1"
    }
  },
  "product_tree": {
    "branches": [
      {
        "branches": [
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "\u003c= 9.02",
                "product": {
                  "name": "WebAccess: Versions 9.02 and prior",
                  "product_id": "CSAFPID-0001"
                }
              }
            ],
            "category": "product_name",
            "name": "WebAccess"
          }
        ],
        "category": "vendor",
        "name": "Advantech"
      }
    ]
  },
  "vulnerabilities": [
    {
      "cve": "CVE-2021-33023",
      "cwe": {
        "id": "CWE-122",
        "name": "Heap-based Buffer Overflow"
      },
      "notes": [
        {
          "category": "summary",
          "text": "The affected product is vulnerable to a heap-based buffer overflow, which may allow an attacker to remotely execute code.CVE-2021-33023 has been assigned to this vulnerability. A CVSS v3 base score of 9.8 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).",
          "title": "Vulnerability Summary"
        }
      ],
      "product_status": {
        "known_affected": [
          "CSAFPID-0001"
        ]
      },
      "references": [
        {
          "category": "external",
          "summary": "web.nvd.nist.gov",
          "url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2021-33023"
        },
        {
          "category": "external",
          "summary": "www.first.org",
          "url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H"
        }
      ],
      "remediations": [
        {
          "category": "mitigation",
          "details": "Advantech has released Version 9.1.1 to address the stack-based buffer overflow vulnerability.",
          "product_ids": [
            "CSAFPID-0001"
          ],
          "url": "https://www.advantech.com/support/details/installation?id=1-MS9MJV"
        },
        {
          "category": "vendor_fix",
          "details": "In order to address the heap-based buffer overflow vulnerability, Advantech recommends users directly add the remote access code to avoid being attacked by unknown requests. This is the remote access code established during installation of the Advantech WebAccess SCADA software (SCADA node, project node, or OPC Service) on the OPC Server computer. The access code you enter here must match the remote access code established during installation on the OPC Server. This prevents unauthorized users from accessing the OPC Server data using the Advantech WebAccess SCADA OPC Service.",
          "product_ids": [
            "CSAFPID-0001"
          ]
        },
        {
          "category": "mitigation",
          "details": "If you have forgotten the remote access code using during software installation on the OPC Server node, you have two options:",
          "product_ids": [
            "CSAFPID-0001"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "Re-install the Advantech WebAccess SCADA software on the OPC Server node to change it and edit it to match in your database.",
          "product_ids": [
            "CSAFPID-0001"
          ],
          "url": "http://220.130.135.6/broadWeb/engman/20.5_UPDATE.htm"
        },
        {
          "category": "mitigation",
          "details": "Edit the BWSERVER.INI file on the OPC Server node and edit it to match in your database using UPDATE.",
          "product_ids": [
            "CSAFPID-0001"
          ],
          "url": "http://220.130.135.6/broadWeb/engman/25.5_BWSERVER.INI.htm"
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "baseScore": 9.8,
            "baseSeverity": "CRITICAL",
            "vectorString": "CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H",
            "version": "3.0"
          },
          "products": [
            "CSAFPID-0001"
          ]
        }
      ]
    },
    {
      "cve": "CVE-2021-38389",
      "cwe": {
        "id": "CWE-121",
        "name": "Stack-based Buffer Overflow"
      },
      "notes": [
        {
          "category": "summary",
          "text": "The affected product is vulnerable to a stack-based buffer overflow, which may allow an attacker to remotely execute code.CVE-2021-38389 has been assigned to this vulnerability. A CVSS v3 base score of 9.8 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).",
          "title": "Vulnerability Summary"
        }
      ],
      "product_status": {
        "known_affected": [
          "CSAFPID-0001"
        ]
      },
      "references": [
        {
          "category": "external",
          "summary": "web.nvd.nist.gov",
          "url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2021-38389"
        },
        {
          "category": "external",
          "summary": "www.first.org",
          "url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H"
        }
      ],
      "remediations": [
        {
          "category": "mitigation",
          "details": "Advantech has released Version 9.1.1 to address the stack-based buffer overflow vulnerability.",
          "product_ids": [
            "CSAFPID-0001"
          ],
          "url": "https://www.advantech.com/support/details/installation?id=1-MS9MJV"
        },
        {
          "category": "vendor_fix",
          "details": "In order to address the heap-based buffer overflow vulnerability, Advantech recommends users directly add the remote access code to avoid being attacked by unknown requests. This is the remote access code established during installation of the Advantech WebAccess SCADA software (SCADA node, project node, or OPC Service) on the OPC Server computer. The access code you enter here must match the remote access code established during installation on the OPC Server. This prevents unauthorized users from accessing the OPC Server data using the Advantech WebAccess SCADA OPC Service.",
          "product_ids": [
            "CSAFPID-0001"
          ]
        },
        {
          "category": "mitigation",
          "details": "If you have forgotten the remote access code using during software installation on the OPC Server node, you have two options:",
          "product_ids": [
            "CSAFPID-0001"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "Re-install the Advantech WebAccess SCADA software on the OPC Server node to change it and edit it to match in your database.",
          "product_ids": [
            "CSAFPID-0001"
          ],
          "url": "http://220.130.135.6/broadWeb/engman/20.5_UPDATE.htm"
        },
        {
          "category": "mitigation",
          "details": "Edit the BWSERVER.INI file on the OPC Server node and edit it to match in your database using UPDATE.",
          "product_ids": [
            "CSAFPID-0001"
          ],
          "url": "http://220.130.135.6/broadWeb/engman/25.5_BWSERVER.INI.htm"
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "baseScore": 9.8,
            "baseSeverity": "CRITICAL",
            "vectorString": "CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H",
            "version": "3.0"
          },
          "products": [
            "CSAFPID-0001"
          ]
        }
      ]
    }
  ]
}


Log in or create an account to share your comment.




Tags
Taxonomy of the tags.


Loading...

Loading...

Loading...

Sightings

Author Source Type Date

Nomenclature

  • Seen: The vulnerability was mentioned, discussed, or seen somewhere by the user.
  • Confirmed: The vulnerability is confirmed from an analyst perspective.
  • Exploited: This vulnerability was exploited and seen by the user reporting the sighting.
  • Patched: This vulnerability was successfully patched by the user reporting the sighting.
  • Not exploited: This vulnerability was not exploited or seen by the user reporting the sighting.
  • Not confirmed: The user expresses doubt about the veracity of the vulnerability.
  • Not patched: This vulnerability was not successfully patched by the user reporting the sighting.