icsa-22-314-07
Vulnerability from csaf_cisa
Published
2022-11-10 00:00
Modified
2022-11-10 00:00
Summary
Omron NJ/NX-series Machine Automation Controllers
Notes
CISA Disclaimer
This CSAF advisory was extracted from unstructured data and may contain inaccuracies. If you notice any errors, please reach out to the designated contact at CISA CSAF: central@cisa.dhs.gov
Legal Notice
All information products included in https://us-cert.cisa.gov/ics are provided "as is" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see https://us-cert.cisa.gov/tlp/.
Risk evaluation
Successful exploitation of this vulnerability could allow an attacker to obtain unauthorized access to the device and cause the device to be in an out of service state or execute a malicious program on the device.
Critical infrastructure sectors
Critical Manufacturing
Countries/areas deployed
Worldwide
Company headquarters location
Japan
Recommended Practices
This vulnerability and countermeasures correspond to the those reported in the CISA ICS Alert: APT Cyber Tools Targeting ICS/SCADA Devices.
Recommended Practices
CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.
Recommended Practices
CISA also provides a section for control systems security recommended practices on the ICS webpage at cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.
Recommended Practices
Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.
Recommended Practices
Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.
Exploitability
This vulnerability has a high attack complexity.
{ "document": { "acknowledgments": [ { "names": [ "Reid Wightman" ], "organization": "Dragos", "summary": "reporting this vulnerability to CISA" } ], "category": "csaf_security_advisory", "csaf_version": "2.0", "distribution": { "text": "Disclosure is not limited", "tlp": { "label": "WHITE", "url": "https://us-cert.cisa.gov/tlp/" } }, "lang": "en-US", "notes": [ { "category": "general", "text": "This CSAF advisory was extracted from unstructured data and may contain inaccuracies. If you notice any errors, please reach out to the designated contact at CISA CSAF: central@cisa.dhs.gov", "title": "CISA Disclaimer" }, { "category": "legal_disclaimer", "text": "All information products included in https://us-cert.cisa.gov/ics are provided \"as is\" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see https://us-cert.cisa.gov/tlp/.", "title": "Legal Notice" }, { "category": "summary", "text": "Successful exploitation of this vulnerability could allow an attacker to obtain unauthorized access to the device and cause the device to be in an out of service state or execute a malicious program on the device.", "title": "Risk evaluation" }, { "category": "other", "text": "Critical Manufacturing", "title": "Critical infrastructure sectors" }, { "category": "other", "text": "Worldwide", "title": "Countries/areas deployed" }, { "category": "other", "text": "Japan", "title": "Company headquarters location" }, { "category": "general", "text": "This vulnerability and countermeasures correspond to the those reported in the CISA ICS Alert: APT Cyber Tools Targeting ICS/SCADA Devices.", "title": "Recommended Practices" }, { "category": "general", "text": "CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.", "title": "Recommended Practices" }, { "category": "general", "text": "CISA also provides a section for control systems security recommended practices on the ICS webpage at cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.", "title": "Recommended Practices" }, { "category": "general", "text": "Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.", "title": "Recommended Practices" }, { "category": "general", "text": "Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.", "title": "Recommended Practices" }, { "category": "other", "text": "This vulnerability has a high attack complexity.", "title": "Exploitability" } ], "publisher": { "category": "coordinator", "contact_details": "Email: CISAservicedesk@cisa.dhs.gov;\n Toll Free: 1-888-282-0870", "name": "CISA", "namespace": "https://www.cisa.gov/" }, "references": [ { "category": "self", "summary": "ICS Advisory ICSA-22-314-07 JSON", "url": "https://raw.githubusercontent.com/cisagov/CSAF/develop/csaf_files/OT/white/2022/icsa-22-314-07.json" }, { "category": "self", "summary": "ICS Advisory ICSA-22-314-07 Web Version", "url": "https://www.cisa.gov/news-events/ics-advisories/icsa-22-314-07" }, { "category": "external", "summary": "Recommended Practices", "url": "https://www.cisa.gov/uscert/ncas/alerts/aa22-103a" }, { "category": "external", "summary": "Recommended Practices", "url": "https://www.cisa.gov/news-events/ics-advisories/icsa-22-314-07" }, { "category": "external", "summary": "Recommended Practices", "url": "https://us-cert.cisa.gov/sites/default/files/recommended_practices/NCCIC_ICS-CERT_Defense_in_Depth_2016_S508C.pdf" } ], "title": "Omron NJ/NX-series Machine Automation Controllers", "tracking": { "current_release_date": "2022-11-10T00:00:00.000000Z", "generator": { "engine": { "name": "CISA CSAF Generator", "version": "1.0.0" } }, "id": "ICSA-22-314-07", "initial_release_date": "2022-11-10T00:00:00.000000Z", "revision_history": [ { "date": "2022-11-10T00:00:00.000000Z", "legacy_version": "Initial", "number": "1", "summary": "Publication Date" } ], "status": "final", "version": "1" } }, "product_tree": { "branches": [ { "branches": [ { "branches": [ { "category": "product_version_range", "name": "\u003c= 1.28", "product": { "name": "NJ/NX-series Machine Automation Controllers - NX7-series Machine Automation Controller (All Models): Versions 1.28 and prior", "product_id": "CSAFPID-0001" } } ], "category": "product_name", "name": "NJ/NX-series Machine Automation Controllers" }, { "branches": [ { "category": "product_version_range", "name": "\u003c= 1.48", "product": { "name": "NJ/NX-series Machine Automation Controllers - NX1-series Machine Automation Controller (All Models): Versions 1.48 and prior", "product_id": "CSAFPID-0002" } } ], "category": "product_name", "name": "NJ/NX-series Machine Automation Controllers" }, { "branches": [ { "category": "product_version_range", "name": "\u003c= 1.48", "product": { "name": "NJ/NX-series Machine Automation Controllers - NJ-series Machine Automation Controller (All Models): Versions 1.48 and prior", "product_id": "CSAFPID-0003" } } ], "category": "product_name", "name": "NJ/NX-series Machine Automation Controllers" } ], "category": "vendor", "name": "Omron" } ] }, "vulnerabilities": [ { "cve": "CVE-2022-33971", "cwe": { "id": "CWE-489", "name": "Active Debug Code" }, "notes": [ { "category": "summary", "text": "An attacker who can analyze the communication of the affected product and perform capture-replay can find unintended entry points into the affected product and cause a denial-of-service condition or execute a malicious program.CVE-2022-33971 has been assigned to this vulnerability. A CVSS v3 base score of 8.3 has been calculated; the CVSS vector string is (AV:N/AC:H/PR:N/UI:R/S:C/C:H/I:H/A:H).", "title": "Vulnerability Summary" } ], "product_status": { "known_affected": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003" ] }, "references": [ { "category": "external", "summary": "web.nvd.nist.gov", "url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2022-33971" }, { "category": "external", "summary": "www.first.org", "url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:H/PR:N/UI:R/S:C/C:H/I:H/A:H" } ], "remediations": [ { "category": "mitigation", "details": "Omron recommends updating versions of NJ/NX-series machine automation controllers to address this vulnerability. These updates are available to users by contacting their Omron or distributors:", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003" ], "url": "https://www.ia.omron.com/global_network/index.html" }, { "category": "mitigation", "details": "NX7-series Machine Automation Controller (All Models): Versions 1.29 or higher", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003" ] }, { "category": "mitigation", "details": "NX1-series Machine Automation Controller (All Models): Versions 1.50 or higher", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003" ] }, { "category": "mitigation", "details": "NJ-series Machine Automation Controller (NJ501-1300, NJ501-1400, NJ501-1500): Versions 1.49 or higher", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003" ] }, { "category": "mitigation", "details": "NJ-series Machine Automation Controller (All other Models): Versions 1.50 or higher", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003" ] }, { "category": "mitigation", "details": "Enable antivirus protection:", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003" ] }, { "category": "mitigation", "details": "Protect any PC with access to the control system against malware by ensuring the installation and maintenance of up-to-date commercial grade antivirus software protection.", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003" ] }, { "category": "mitigation", "details": "Implement security measures to prevent unauthorized access:", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003" ] }, { "category": "mitigation", "details": "Minimize connection of control systems and equipment to open networks preventing untrusted devices from accessing them.", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003" ] }, { "category": "mitigation", "details": "Implement firewalls by shutting down unused communications ports, limiting communications between hosts, and isolate affected systems from the IT network.", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003" ] }, { "category": "mitigation", "details": "Use a virtual private network (VPN) for remote access to control systems and equipment.", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003" ] }, { "category": "mitigation", "details": "Use strong passwords and change passwords frequently.", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003" ] }, { "category": "mitigation", "details": "Install physical controls that only permit authorized personnel access to control systems and equipment.", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003" ] }, { "category": "mitigation", "details": "Scan USB drives or similar devices for viruses and malware to ensure the devices are safe before connecting them to systems and devices.", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003" ] }, { "category": "mitigation", "details": "When possible, enforce multifactor authentication (MFA) on all devices with remote access to control systems and equipment.", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003" ] }, { "category": "mitigation", "details": "Protect data input and output:", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003" ] }, { "category": "mitigation", "details": "Perform process validation, such as backup validation or range checks, to cope with unintentional modification of input/output data to control systems and devices.", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003" ] }, { "category": "mitigation", "details": "Use data recovery:", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003" ] }, { "category": "mitigation", "details": "Conduct periodical data backups and maintenance to prepare for potential data loss.", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003" ] }, { "category": "mitigation", "details": "For more information see Omron\u0027s advisory: OMSR-2022-002", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003" ], "url": "https://www.ia.omron.com/product/vulnerability/OMSR-2022-002_en.pdf" } ], "scores": [ { "cvss_v3": { "baseScore": 8.3, "baseSeverity": "HIGH", "vectorString": "CVSS:3.0/AV:N/AC:H/PR:N/UI:R/S:C/C:H/I:H/A:H", "version": "3.0" }, "products": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003" ] } ] } ] }
Loading...
Loading...
Sightings
Author | Source | Type | Date |
---|
Nomenclature
- Seen: The vulnerability was mentioned, discussed, or seen somewhere by the user.
- Confirmed: The vulnerability is confirmed from an analyst perspective.
- Exploited: This vulnerability was exploited and seen by the user reporting the sighting.
- Patched: This vulnerability was successfully patched by the user reporting the sighting.
- Not exploited: This vulnerability was not exploited or seen by the user reporting the sighting.
- Not confirmed: The user expresses doubt about the veracity of the vulnerability.
- Not patched: This vulnerability was not successfully patched by the user reporting the sighting.