ICSA-22-354-04

Vulnerability from csaf_cisa - Published: 2022-12-20 00:00 - Updated: 2022-12-20 00:00
Summary
Rockwell Automation MicroLogix 1100 and 1400

Notes

CISA Disclaimer
This CSAF advisory was extracted from unstructured data and may contain inaccuracies. If you notice any errors, please reach out to the designated contact at CISA CSAF: central@cisa.dhs.gov
Legal Notice
All information products included in https://us-cert.cisa.gov/ics are provided "as is" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see https://us-cert.cisa.gov/tlp/.
Risk evaluation
Successful exploitation of these vulnerabilities could create a denial-of-service condition or allow for remote code execution.
Critical infrastructure sectors
Multiple
Countries/areas deployed
Worldwide
Company headquarters location
United States
Recommended Practices
CISA recommends users take defensive measures to minimize the risk of exploitation of these vulnerabilities. Specifically, users should:
Recommended Practices
CISA also provides a section for control systems security recommended practices on the ICS webpage at cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.
Recommended Practices
Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.
Exploitability
No known public exploits specifically target these vulnerabilities.

{
  "document": {
    "acknowledgments": [
      {
        "organization": "Rockwell Automation",
        "summary": "reporting these vulnerabilities to CISA"
      }
    ],
    "category": "csaf_security_advisory",
    "csaf_version": "2.0",
    "distribution": {
      "text": "Disclosure is not limited",
      "tlp": {
        "label": "WHITE",
        "url": "https://us-cert.cisa.gov/tlp/"
      }
    },
    "lang": "en-US",
    "notes": [
      {
        "category": "general",
        "text": "This CSAF advisory was extracted from unstructured data and may contain inaccuracies. If you notice any errors, please reach out to the designated contact at CISA CSAF: central@cisa.dhs.gov",
        "title": "CISA Disclaimer"
      },
      {
        "category": "legal_disclaimer",
        "text": "All information products included in https://us-cert.cisa.gov/ics are provided \"as is\" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see https://us-cert.cisa.gov/tlp/.",
        "title": "Legal Notice"
      },
      {
        "category": "summary",
        "text": "Successful exploitation of these vulnerabilities could create a denial-of-service condition or allow for remote code execution.",
        "title": "Risk evaluation"
      },
      {
        "category": "other",
        "text": " Multiple",
        "title": "Critical infrastructure sectors"
      },
      {
        "category": "other",
        "text": " Worldwide",
        "title": "Countries/areas deployed"
      },
      {
        "category": "other",
        "text": " United States",
        "title": "Company headquarters location"
      },
      {
        "category": "general",
        "text": "CISA recommends users take defensive measures to minimize the risk of exploitation of these vulnerabilities. Specifically, users should:",
        "title": "Recommended Practices"
      },
      {
        "category": "general",
        "text": "CISA also provides a section for control systems security recommended practices on the ICS webpage at cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.",
        "title": "Recommended Practices"
      },
      {
        "category": "general",
        "text": "Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.",
        "title": "Recommended Practices"
      },
      {
        "category": "other",
        "text": "No known public exploits specifically target these vulnerabilities.",
        "title": "Exploitability"
      }
    ],
    "publisher": {
      "category": "coordinator",
      "contact_details": "Email: CISAservicedesk@cisa.dhs.gov;\n Toll Free: 1-888-282-0870",
      "name": "CISA",
      "namespace": "https://www.cisa.gov/"
    },
    "references": [
      {
        "category": "self",
        "summary": "ICS Advisory ICSA-22-354-04 JSON",
        "url": "https://raw.githubusercontent.com/cisagov/CSAF/develop/csaf_files/OT/white/2022/icsa-22-354-04.json"
      },
      {
        "category": "self",
        "summary": "ICS Advisory ICSA-22-354-04 Web Version",
        "url": "https://www.cisa.gov/news-events/ics-advisories/icsa-22-354-04"
      },
      {
        "category": "external",
        "summary": "Recommended Practices",
        "url": "https://www.cisa.gov/uscert/ics/alerts/ICS-ALERT-10-301-01"
      },
      {
        "category": "external",
        "summary": "Recommended Practices",
        "url": "https://us-cert.cisa.gov/sites/default/files/recommended_practices/NCCIC_ICS-CERT_Defense_in_Depth_2016_S508C.pdf"
      }
    ],
    "title": "Rockwell Automation MicroLogix 1100 and 1400",
    "tracking": {
      "current_release_date": "2022-12-20T00:00:00.000000Z",
      "generator": {
        "engine": {
          "name": "CISA CSAF Generator",
          "version": "1.0.0"
        }
      },
      "id": "ICSA-22-354-04",
      "initial_release_date": "2022-12-20T00:00:00.000000Z",
      "revision_history": [
        {
          "date": "2022-12-20T00:00:00.000000Z",
          "legacy_version": "Initial",
          "number": "1",
          "summary": "Publication Date"
        }
      ],
      "status": "final",
      "version": "1"
    }
  },
  "product_tree": {
    "branches": [
      {
        "branches": [
          {
            "branches": [
              {
                "category": "product_version",
                "name": "vers:all/*",
                "product": {
                  "name": "MicroLogix 1100 and 1400: MicroLogix 1100: all versions",
                  "product_id": "CSAFPID-0001"
                }
              }
            ],
            "category": "product_name",
            "name": "MicroLogix 1100"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "\u003c= 7.000",
                "product": {
                  "name": "MicroLogix 1100 and 1400: MicroLogix 1400 A: Versions 7.000 and prior",
                  "product_id": "CSAFPID-0002"
                }
              }
            ],
            "category": "product_name",
            "name": "MicroLogix 1400 A"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "\u003c= 21.007",
                "product": {
                  "name": "MicroLogix 1100 and 1400: MicroLogix 1400 B/C: Versions 21.007 and prior",
                  "product_id": "CSAFPID-0003"
                }
              }
            ],
            "category": "product_name",
            "name": "MicroLogix 1400 B/C"
          }
        ],
        "category": "vendor",
        "name": "Rockwell Automation"
      }
    ]
  },
  "vulnerabilities": [
    {
      "cve": "CVE-2022-46670",
      "cwe": {
        "id": "CWE-79",
        "name": "Improper Neutralization of Input During Web Page Generation (\u0027Cross-site Scripting\u0027)"
      },
      "notes": [
        {
          "category": "summary",
          "text": "The affected products have an unauthenticated stored cross-site scripting vulnerability in the embedded webserver. The payload is transferred to the controller over simple network management protocol (SNMP) and is rendered on the homepage of the embedded website. Exploitation of this vulnerability could result in unauthenticated remote code execution.CVE-2022-46670 has been assigned to this vulnerability. A CVSS v3 base score of 7.1 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:R/S:C/C:L/I:L/A:L).",
          "title": "Vulnerability Summary"
        }
      ],
      "product_status": {
        "known_affected": [
          "CSAFPID-0001",
          "CSAFPID-0002",
          "CSAFPID-0003"
        ]
      },
      "references": [
        {
          "category": "external",
          "summary": "web.nvd.nist.gov",
          "url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2022-46670"
        },
        {
          "category": "external",
          "summary": "www.first.org",
          "url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:R/S:C/C:L/I:L/A:L"
        }
      ],
      "remediations": [
        {
          "category": "mitigation",
          "details": "Disable the web server, if possible (This component is an optional feature and disabling it will not disrupt the intended use of the device)",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        },
        {
          "category": "mitigation",
          "details": "Configure firewalls to disallow network communication through HTTP/Port 802",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        },
        {
          "category": "mitigation",
          "details": "Upgrade to the MicroLogix 800 or MicroLogix 850 as this device does not have the web server component",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        },
        {
          "category": "mitigation",
          "details": "Rockwell Automation also recommends users to employ cybersecurity best practices, as outlined in their Knowledgebase article.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ],
          "url": "https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/1085012"
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "baseScore": 7.1,
            "baseSeverity": "HIGH",
            "vectorString": "CVSS:3.0/AV:N/AC:L/PR:N/UI:R/S:C/C:L/I:L/A:L",
            "version": "3.0"
          },
          "products": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        }
      ]
    },
    {
      "cve": "CVE-2022-3166",
      "cwe": {
        "id": "CWE-1021",
        "name": "Improper Restriction of Rendered UI Layers or Frames"
      },
      "notes": [
        {
          "category": "summary",
          "text": "The affected products have a clickjacking vulnerability where an attacker with network access to the affected systems could send TCP packets to the webserver, closing it abruptly. This could cause a denial-of-service condition for the web server application on the device.CVE-2022-3166 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).",
          "title": "Vulnerability Summary"
        }
      ],
      "product_status": {
        "known_affected": [
          "CSAFPID-0001",
          "CSAFPID-0002",
          "CSAFPID-0003"
        ]
      },
      "references": [
        {
          "category": "external",
          "summary": "web.nvd.nist.gov",
          "url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2022-3166"
        },
        {
          "category": "external",
          "summary": "www.first.org",
          "url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H"
        }
      ],
      "remediations": [
        {
          "category": "mitigation",
          "details": "Disable the web server, if possible (This component is an optional feature and disabling it will not disrupt the intended use of the device)",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        },
        {
          "category": "mitigation",
          "details": "Configure firewalls to disallow network communication through HTTP/Port 802",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        },
        {
          "category": "mitigation",
          "details": "Upgrade to the MicroLogix 800 or MicroLogix 850 as this device does not have the web server component",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        },
        {
          "category": "mitigation",
          "details": "Rockwell Automation also recommends users to employ cybersecurity best practices, as outlined in their Knowledgebase article.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ],
          "url": "https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/1085012"
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "baseScore": 7.5,
            "baseSeverity": "HIGH",
            "vectorString": "CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H",
            "version": "3.0"
          },
          "products": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        }
      ]
    }
  ]
}


Log in or create an account to share your comment.




Tags
Taxonomy of the tags.


Loading…

Loading…

Loading…

Sightings

Author Source Type Date

Nomenclature

  • Seen: The vulnerability was mentioned, discussed, or observed by the user.
  • Confirmed: The vulnerability has been validated from an analyst's perspective.
  • Published Proof of Concept: A public proof of concept is available for this vulnerability.
  • Exploited: The vulnerability was observed as exploited by the user who reported the sighting.
  • Patched: The vulnerability was observed as successfully patched by the user who reported the sighting.
  • Not exploited: The vulnerability was not observed as exploited by the user who reported the sighting.
  • Not confirmed: The user expressed doubt about the validity of the vulnerability.
  • Not patched: The vulnerability was not observed as successfully patched by the user who reported the sighting.


Loading…

Detection rules are retrieved from Rulezet.

Loading…

Loading…