icsa-23-136-02
Vulnerability from csaf_cisa
Published
2023-05-18 19:01
Modified
2023-05-18 19:01
Summary
Rockwell ArmorStart
Notes
CISA Disclaimer
This CSAF advisory was extracted from unstructured data and may contain inaccuracies. If you notice any errors, please reach out to the designated contact at CISA CSAF: central@cisa.dhs.gov
Legal Notice
All information products included in https://us-cert.cisa.gov/ics are provided "as is" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see https://us-cert.cisa.gov/tlp/.
Risk evaluation
Successful exploitation of these vulnerabilities could allow a malicious user to view and modify sensitive data or make the web page unavailable.
Critical infrastructure sectors
Critical Manufacturer
Countries/areas deployed
Worldwide
Company headquarters location
United States
Recommended Practices
CISA recommends users take defensive measures to minimize the risk of exploitation of this (these) vulnerability(ies). Specifically, users should:
Recommended Practices
Locate control system networks and remote devices behind firewalls and isolate them from business networks.
Recommended Practices
When remote access is required, use secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize VPN is only as secure as its connected devices.
Recommended Practices
CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.
Recommended Practices
CISA also provides a section for control systems security recommended practices on the ICS webpage at cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.
Recommended Practices
Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.
Recommended Practices
Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.
Recommended Practices
CISA also recommends users take the following measures to protect themselves from social engineering attacks:
Recommended Practices
Do not click web links or open attachments in unsolicited email messages.
Recommended Practices
Refer to Recognizing and Avoiding Email Scams for more information on avoiding email scams.
Recommended Practices
Refer to Avoiding Social Engineering and Phishing Attacks for more information on social engineering attacks.
Recommended Practices
No known public exploits specifically target these vulnerabilities.
{ "document": { "acknowledgments": [ { "organization": "Rockwell Automation", "summary": "reporting these vulnerabilities to CISA" } ], "category": "csaf_security_advisory", "csaf_version": "2.0", "distribution": { "text": "Disclosure is not limited", "tlp": { "label": "WHITE", "url": "https://us-cert.cisa.gov/tlp/" } }, "lang": "en-US", "notes": [ { "category": "general", "text": "This CSAF advisory was extracted from unstructured data and may contain inaccuracies. If you notice any errors, please reach out to the designated contact at CISA CSAF: central@cisa.dhs.gov", "title": "CISA Disclaimer" }, { "category": "legal_disclaimer", "text": "All information products included in https://us-cert.cisa.gov/ics are provided \"as is\" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see https://us-cert.cisa.gov/tlp/.", "title": "Legal Notice" }, { "category": "summary", "text": "Successful exploitation of these vulnerabilities could allow a malicious user to view and modify sensitive data or make the web page unavailable.", "title": "Risk evaluation" }, { "category": "other", "text": "Critical Manufacturer", "title": "Critical infrastructure sectors" }, { "category": "other", "text": "Worldwide", "title": "Countries/areas deployed" }, { "category": "other", "text": "United States", "title": "Company headquarters location" }, { "category": "general", "text": "CISA recommends users take defensive measures to minimize the risk of exploitation of this (these) vulnerability(ies). Specifically, users should:", "title": "Recommended Practices" }, { "category": "general", "text": "Locate control system networks and remote devices behind firewalls and isolate them from business networks.", "title": "Recommended Practices" }, { "category": "general", "text": "When remote access is required, use secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize VPN is only as secure as its connected devices.", "title": "Recommended Practices" }, { "category": "general", "text": "CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.", "title": "Recommended Practices" }, { "category": "general", "text": "CISA also provides a section for control systems security recommended practices on the ICS webpage at cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.", "title": "Recommended Practices" }, { "category": "general", "text": "Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.", "title": "Recommended Practices" }, { "category": "general", "text": "Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.", "title": "Recommended Practices" }, { "category": "general", "text": "CISA also recommends users take the following measures to protect themselves from social engineering attacks:", "title": "Recommended Practices" }, { "category": "general", "text": "Do not click web links or open attachments in unsolicited email messages.", "title": "Recommended Practices" }, { "category": "general", "text": "Refer to Recognizing and Avoiding Email Scams for more information on avoiding email scams.", "title": "Recommended Practices" }, { "category": "general", "text": "Refer to Avoiding Social Engineering and Phishing Attacks for more information on social engineering attacks.", "title": "Recommended Practices" }, { "category": "general", "text": "No known public exploits specifically target these vulnerabilities.", "title": "Recommended Practices" } ], "publisher": { "category": "coordinator", "contact_details": "Email: CISAservicedesk@cisa.dhs.gov;\n Toll Free: 1-888-282-0870", "name": "CISA", "namespace": "https://www.cisa.gov/" }, "references": [ { "category": "self", "summary": "ICS Advisory ICSA-23-136-02 JSON", "url": "https://raw.githubusercontent.com/cisagov/CSAF/develop/csaf_files/OT/white/2023/icsa-23-136-02.json" }, { "category": "self", "summary": "ICS Advisory ICSA-23-136-02 Web Version", "url": "https://www.cisa.gov/news-events/ics-advisories/icsa-23-136-02" }, { "category": "external", "summary": "Recommended Practices", "url": "https://us-cert.cisa.gov/ics/Recommended-Practices" }, { "category": "external", "summary": "Recommended Practices", "url": "https://cisa.gov/ics" }, { "category": "external", "summary": "Recommended Practices", "url": "https://www.cisa.gov/uscert/sites/default/files/publications/emailscams0905.pdf" }, { "category": "external", "summary": "Recommended Practices", "url": "https://www.cisa.gov/uscert/ncas/tips/ST04-014" } ], "title": "Rockwell ArmorStart", "tracking": { "current_release_date": "2023-05-18T19:01:59.428226Z", "generator": { "engine": { "name": "CISA CSAF Generator", "version": "1.0.0" } }, "id": "ICSA-23-136-02", "initial_release_date": "2023-05-18T19:01:59.428226Z", "revision_history": [ { "date": "2023-05-18T19:01:59.428226Z", "legacy_version": "1", "number": "1", "summary": "CSAF Creation Date" } ], "status": "final", "version": "1" } }, "product_tree": { "branches": [ { "branches": [ { "branches": [ { "category": "product_version_range", "name": "\u003e= 2.004.06", "product": { "name": "ArmorStart ST281E: \u003e= 2.004.06", "product_id": "CSAFPID-0001" } } ], "category": "product_name", "name": "ArmorStart ST281E" }, { "branches": [ { "category": "product_version_range", "name": "vers:all/*", "product": { "name": "ArmorStart ST284E: *", "product_id": "CSAFPID-0002" } } ], "category": "product_name", "name": "ArmorStart ST284E" }, { "branches": [ { "category": "product_version_range", "name": "vers:all/*", "product": { "name": "ArmorStart ST280E: *", "product_id": "CSAFPID-0003" } } ], "category": "product_name", "name": "ArmorStart ST280E" } ], "category": "vendor", "name": "Rockwell Automation" } ] }, "vulnerabilities": [ { "cve": "CVE-2023-29031", "cwe": { "id": "CWE-20", "name": "Improper Input Validation" }, "notes": [ { "category": "summary", "text": "A cross site scripting vulnerability was discovered that could potentially allow a malicious user to view and modify sensitive data or make the web page unavailable. User interaction, such as a phishing attack, is required for successful exploitation of this vulnerability.", "title": "Vulnerability Summary" } ], "product_status": { "known_affected": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003" ] }, "references": [ { "category": "external", "summary": "web.nvd.nist.gov", "url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2023-29031" }, { "category": "external", "summary": "www.first.org", "url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:L/AC:H/PR:N/UI:R/S:U/C:H/I:H/A:H" } ], "remediations": [ { "category": "vendor_fix", "details": "Rockwell Automation recommends users take the following measures to mitigate the risk of these vulnerabilities:", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003" ] }, { "category": "vendor_fix", "details": "Disable the webserver during normal use. The webserver is disabled by default and should only be enabled to modify configurations. After modifying configurations, the web server should be disabled.", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003" ] }, { "category": "vendor_fix", "details": "For information on how to mitigate security risks on industrial automation control systems (IACS) networks see the following publications:", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003" ] }, { "category": "vendor_fix", "details": "System Security Design Guidelines Reference Manual publication, SECURE-RM001", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003" ], "url": "https://manuals.plus/m/034dd41130c94a4265d75b89b1ae8c6cca6223ea538a03c3dd7660487fb74a8a" }, { "category": "vendor_fix", "details": "Configure System Security Features User Manual, SECURE-UM001", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003" ], "url": "https://pdf4pro.com/view/configure-system-security-features-user-manual-5f8cd0.html" }, { "category": "vendor_fix", "details": "Additionally, Rockwell Automation encourages customers to implement their suggested Security Best Practices to minimize the risk of the vulnerabilities.", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003" ], "url": "https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/1085012/loc/en_US#__highlight" } ], "scores": [ { "cvss_v3": { "baseScore": 7.0, "baseSeverity": "HIGH", "vectorString": "CVSS:3.0/AV:L/AC:H/PR:N/UI:R/S:U/C:H/I:H/A:H", "version": "3.0" }, "products": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003" ] } ] }, { "cve": "CVE-2023-29030", "cwe": { "id": "CWE-20", "name": "Improper Input Validation" }, "notes": [ { "category": "summary", "text": "A cross site scripting vulnerability was discovered that could potentially allow a malicious user to view and modify sensitive data or make the web page unavailable. User interaction, such as a phishing attack, is required for successful exploitation of this vulnerability.", "title": "Vulnerability Summary" } ], "product_status": { "known_affected": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003" ] }, "references": [ { "category": "external", "summary": "web.nvd.nist.gov", "url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2023-29030" }, { "category": "external", "summary": "www.first.org", "url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:L/AC:H/PR:N/UI:R/S:U/C:H/I:H/A:H" } ], "remediations": [ { "category": "vendor_fix", "details": "Rockwell Automation recommends users take the following measures to mitigate the risk of these vulnerabilities:", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003" ] }, { "category": "vendor_fix", "details": "Disable the webserver during normal use. The webserver is disabled by default and should only be enabled to modify configurations. After modifying configurations, the web server should be disabled.", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003" ] }, { "category": "vendor_fix", "details": "For information on how to mitigate security risks on industrial automation control systems (IACS) networks see the following publications:", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003" ] }, { "category": "vendor_fix", "details": "System Security Design Guidelines Reference Manual publication, SECURE-RM001", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003" ], "url": "https://manuals.plus/m/034dd41130c94a4265d75b89b1ae8c6cca6223ea538a03c3dd7660487fb74a8a" }, { "category": "vendor_fix", "details": "Configure System Security Features User Manual, SECURE-UM001", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003" ], "url": "https://pdf4pro.com/view/configure-system-security-features-user-manual-5f8cd0.html" }, { "category": "vendor_fix", "details": "Additionally, Rockwell Automation encourages customers to implement their suggested Security Best Practices to minimize the risk of the vulnerabilities.", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003" ], "url": "https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/1085012/loc/en_US#__highlight" } ], "scores": [ { "cvss_v3": { "baseScore": 7.0, "baseSeverity": "HIGH", "vectorString": "CVSS:3.0/AV:L/AC:H/PR:N/UI:R/S:U/C:H/I:H/A:H", "version": "3.0" }, "products": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003" ] } ] }, { "cve": "CVE-2023-29023", "cwe": { "id": "CWE-20", "name": "Improper Input Validation" }, "notes": [ { "category": "summary", "text": "A cross site scripting vulnerability was discovered that could potentially allow a malicious user to view and modify sensitive data or make the web page unavailable. User interaction, such as a phishing attack, is required for successful exploitation of this vulnerability.", "title": "Vulnerability Summary" } ], "product_status": { "known_affected": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003" ] }, "references": [ { "category": "external", "summary": "web.nvd.nist.gov", "url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2023-29023" }, { "category": "external", "summary": "www.first.org", "url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:L/AC:H/PR:N/UI:R/S:U/C:H/I:H/A:H" } ], "remediations": [ { "category": "vendor_fix", "details": "Rockwell Automation recommends users take the following measures to mitigate the risk of these vulnerabilities:", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003" ] }, { "category": "vendor_fix", "details": "Disable the webserver during normal use. The webserver is disabled by default and should only be enabled to modify configurations. After modifying configurations, the web server should be disabled.", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003" ] }, { "category": "vendor_fix", "details": "For information on how to mitigate security risks on industrial automation control systems (IACS) networks see the following publications:", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003" ] }, { "category": "vendor_fix", "details": "System Security Design Guidelines Reference Manual publication, SECURE-RM001", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003" ], "url": "https://manuals.plus/m/034dd41130c94a4265d75b89b1ae8c6cca6223ea538a03c3dd7660487fb74a8a" }, { "category": "vendor_fix", "details": "Configure System Security Features User Manual, SECURE-UM001", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003" ], "url": "https://pdf4pro.com/view/configure-system-security-features-user-manual-5f8cd0.html" }, { "category": "vendor_fix", "details": "Additionally, Rockwell Automation encourages customers to implement their suggested Security Best Practices to minimize the risk of the vulnerabilities.", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003" ], "url": "https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/1085012/loc/en_US#__highlight" } ], "scores": [ { "cvss_v3": { "baseScore": 7.0, "baseSeverity": "HIGH", "vectorString": "CVSS:3.0/AV:L/AC:H/PR:N/UI:R/S:U/C:H/I:H/A:H", "version": "3.0" }, "products": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003" ] } ] }, { "cve": "CVE-2023-29024", "cwe": { "id": "CWE-20", "name": "Improper Input Validation" }, "notes": [ { "category": "summary", "text": "A cross site scripting vulnerability was discovered that could potentially allow a malicious user to view and modify sensitive data or make the web page unavailable. User interaction, such as a phishing attack, is required for successful exploitation of this vulnerability.", "title": "Vulnerability Summary" } ], "product_status": { "known_affected": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003" ] }, "references": [ { "category": "external", "summary": "web.nvd.nist.gov", "url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2023-29024" }, { "category": "external", "summary": "www.first.org", "url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:L/UI:R/S:U/C:L/I:L/A:L" } ], "remediations": [ { "category": "vendor_fix", "details": "Rockwell Automation recommends users take the following measures to mitigate the risk of these vulnerabilities:", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003" ] }, { "category": "vendor_fix", "details": "Disable the webserver during normal use. The webserver is disabled by default and should only be enabled to modify configurations. After modifying configurations, the web server should be disabled.", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003" ] }, { "category": "vendor_fix", "details": "For information on how to mitigate security risks on industrial automation control systems (IACS) networks see the following publications:", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003" ] }, { "category": "vendor_fix", "details": "System Security Design Guidelines Reference Manual publication, SECURE-RM001", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003" ], "url": "https://manuals.plus/m/034dd41130c94a4265d75b89b1ae8c6cca6223ea538a03c3dd7660487fb74a8a" }, { "category": "vendor_fix", "details": "Configure System Security Features User Manual, SECURE-UM001", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003" ], "url": "https://pdf4pro.com/view/configure-system-security-features-user-manual-5f8cd0.html" }, { "category": "vendor_fix", "details": "Additionally, Rockwell Automation encourages customers to implement their suggested Security Best Practices to minimize the risk of the vulnerabilities.", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003" ], "url": "https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/1085012/loc/en_US#__highlight" } ], "scores": [ { "cvss_v3": { "baseScore": 5.5, "baseSeverity": "MEDIUM", "vectorString": "CVSS:3.0/AV:N/AC:L/PR:L/UI:R/S:U/C:L/I:L/A:L", "version": "3.0" }, "products": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003" ] } ] }, { "cve": "CVE-2023-29025", "cwe": { "id": "CWE-20", "name": "Improper Input Validation" }, "notes": [ { "category": "summary", "text": "A cross site scripting vulnerability was discovered that could potentially allow a malicious user with admin privileges and network access to view user data and modify the web interface. Additionally, a malicious user could potentially cause interruptions to the availability of the web page.", "title": "Vulnerability Summary" } ], "product_status": { "known_affected": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003" ] }, "references": [ { "category": "external", "summary": "web.nvd.nist.gov", "url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2023-29025" }, { "category": "external", "summary": "www.first.org", "url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:H/UI:N/S:U/C:L/I:L/A:L" } ], "remediations": [ { "category": "vendor_fix", "details": "Rockwell Automation recommends users take the following measures to mitigate the risk of these vulnerabilities:", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003" ] }, { "category": "vendor_fix", "details": "Disable the webserver during normal use. The webserver is disabled by default and should only be enabled to modify configurations. After modifying configurations, the web server should be disabled.", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003" ] }, { "category": "vendor_fix", "details": "For information on how to mitigate security risks on industrial automation control systems (IACS) networks see the following publications:", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003" ] }, { "category": "vendor_fix", "details": "System Security Design Guidelines Reference Manual publication, SECURE-RM001", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003" ], "url": "https://manuals.plus/m/034dd41130c94a4265d75b89b1ae8c6cca6223ea538a03c3dd7660487fb74a8a" }, { "category": "vendor_fix", "details": "Configure System Security Features User Manual, SECURE-UM001", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003" ], "url": "https://pdf4pro.com/view/configure-system-security-features-user-manual-5f8cd0.html" }, { "category": "vendor_fix", "details": "Additionally, Rockwell Automation encourages customers to implement their suggested Security Best Practices to minimize the risk of the vulnerabilities.", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003" ], "url": "https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/1085012/loc/en_US#__highlight" } ], "scores": [ { "cvss_v3": { "baseScore": 4.7, "baseSeverity": "MEDIUM", "vectorString": "CVSS:3.0/AV:N/AC:L/PR:H/UI:N/S:U/C:L/I:L/A:L", "version": "3.0" }, "products": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003" ] } ] }, { "cve": "CVE-2023-29026", "cwe": { "id": "CWE-20", "name": "Improper Input Validation" }, "notes": [ { "category": "summary", "text": "A cross site scripting vulnerability was discovered that could potentially allow a malicious user with admin privileges and network access to view user data and modify the web interface. Additionally, a malicious user could potentially cause interruptions to the availability of the web page.", "title": "Vulnerability Summary" } ], "product_status": { "known_affected": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003" ] }, "references": [ { "category": "external", "summary": "web.nvd.nist.gov", "url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2023-29026" }, { "category": "external", "summary": "www.first.org", "url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:H/UI:N/S:U/C:L/I:L/A:L" } ], "remediations": [ { "category": "vendor_fix", "details": "Rockwell Automation recommends users take the following measures to mitigate the risk of these vulnerabilities:", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003" ] }, { "category": "vendor_fix", "details": "Disable the webserver during normal use. The webserver is disabled by default and should only be enabled to modify configurations. After modifying configurations, the web server should be disabled.", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003" ] }, { "category": "vendor_fix", "details": "For information on how to mitigate security risks on industrial automation control systems (IACS) networks see the following publications:", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003" ] }, { "category": "vendor_fix", "details": "System Security Design Guidelines Reference Manual publication, SECURE-RM001", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003" ], "url": "https://manuals.plus/m/034dd41130c94a4265d75b89b1ae8c6cca6223ea538a03c3dd7660487fb74a8a" }, { "category": "vendor_fix", "details": "Configure System Security Features User Manual, SECURE-UM001", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003" ], "url": "https://pdf4pro.com/view/configure-system-security-features-user-manual-5f8cd0.html" }, { "category": "vendor_fix", "details": "Additionally, Rockwell Automation encourages customers to implement their suggested Security Best Practices to minimize the risk of the vulnerabilities.", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003" ], "url": "https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/1085012/loc/en_US#__highlight" } ], "scores": [ { "cvss_v3": { "baseScore": 4.7, "baseSeverity": "MEDIUM", "vectorString": "CVSS:3.0/AV:N/AC:L/PR:H/UI:N/S:U/C:L/I:L/A:L", "version": "3.0" }, "products": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003" ] } ] }, { "cve": "CVE-2023-29027", "cwe": { "id": "CWE-20", "name": "Improper Input Validation" }, "notes": [ { "category": "summary", "text": "A cross site scripting vulnerability was discovered that could potentially allow a malicious user with admin privileges and network access to view user data and modify the web interface. Additionally, a malicious user could potentially cause interruptions to the availability of the web page.", "title": "Vulnerability Summary" } ], "product_status": { "known_affected": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003" ] }, "references": [ { "category": "external", "summary": "web.nvd.nist.gov", "url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2023-29027" }, { "category": "external", "summary": "www.first.org", "url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:H/UI:N/S:U/C:L/I:L/A:L" } ], "remediations": [ { "category": "vendor_fix", "details": "Rockwell Automation recommends users take the following measures to mitigate the risk of these vulnerabilities:", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003" ] }, { "category": "vendor_fix", "details": "Disable the webserver during normal use. The webserver is disabled by default and should only be enabled to modify configurations. After modifying configurations, the web server should be disabled.", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003" ] }, { "category": "vendor_fix", "details": "For information on how to mitigate security risks on industrial automation control systems (IACS) networks see the following publications:", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003" ] }, { "category": "vendor_fix", "details": "System Security Design Guidelines Reference Manual publication, SECURE-RM001", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003" ], "url": "https://manuals.plus/m/034dd41130c94a4265d75b89b1ae8c6cca6223ea538a03c3dd7660487fb74a8a" }, { "category": "vendor_fix", "details": "Configure System Security Features User Manual, SECURE-UM001", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003" ], "url": "https://pdf4pro.com/view/configure-system-security-features-user-manual-5f8cd0.html" }, { "category": "vendor_fix", "details": "Additionally, Rockwell Automation encourages customers to implement their suggested Security Best Practices to minimize the risk of the vulnerabilities.", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003" ], "url": "https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/1085012/loc/en_US#__highlight" } ], "scores": [ { "cvss_v3": { "baseScore": 4.7, "baseSeverity": "MEDIUM", "vectorString": "CVSS:3.0/AV:N/AC:L/PR:H/UI:N/S:U/C:L/I:L/A:L", "version": "3.0" }, "products": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003" ] } ] }, { "cve": "CVE-2023-29028", "cwe": { "id": "CWE-20", "name": "Improper Input Validation" }, "notes": [ { "category": "summary", "text": "A cross site scripting vulnerability was discovered that could potentially allow a malicious user with admin privileges and network access to view user data and modify the web interface. Additionally, a malicious user could potentially cause interruptions to the availability of the web page.", "title": "Vulnerability Summary" } ], "product_status": { "known_affected": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003" ] }, "references": [ { "category": "external", "summary": "web.nvd.nist.gov", "url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2023-29028" }, { "category": "external", "summary": "www.first.org", "url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:H/UI:N/S:U/C:L/I:L/A:L" } ], "remediations": [ { "category": "vendor_fix", "details": "Rockwell Automation recommends users take the following measures to mitigate the risk of these vulnerabilities:", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003" ] }, { "category": "vendor_fix", "details": "Disable the webserver during normal use. The webserver is disabled by default and should only be enabled to modify configurations. After modifying configurations, the web server should be disabled.", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003" ] }, { "category": "vendor_fix", "details": "For information on how to mitigate security risks on industrial automation control systems (IACS) networks see the following publications:", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003" ] }, { "category": "vendor_fix", "details": "System Security Design Guidelines Reference Manual publication, SECURE-RM001", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003" ], "url": "https://manuals.plus/m/034dd41130c94a4265d75b89b1ae8c6cca6223ea538a03c3dd7660487fb74a8a" }, { "category": "vendor_fix", "details": "Configure System Security Features User Manual, SECURE-UM001", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003" ], "url": "https://pdf4pro.com/view/configure-system-security-features-user-manual-5f8cd0.html" }, { "category": "vendor_fix", "details": "Additionally, Rockwell Automation encourages customers to implement their suggested Security Best Practices to minimize the risk of the vulnerabilities.", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003" ], "url": "https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/1085012/loc/en_US#__highlight" } ], "scores": [ { "cvss_v3": { "baseScore": 4.7, "baseSeverity": "MEDIUM", "vectorString": "CVSS:3.0/AV:N/AC:L/PR:H/UI:N/S:U/C:L/I:L/A:L", "version": "3.0" }, "products": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003" ] } ] }, { "cve": "CVE-2023-29029", "cwe": { "id": "CWE-20", "name": "Improper Input Validation" }, "notes": [ { "category": "summary", "text": "A cross site scripting vulnerability was discovered that could potentially allow a malicious user with admin privileges and network access to view user data and modify the web interface. Additionally, a malicious user could potentially cause interruptions to the availability of the web page.", "title": "Vulnerability Summary" } ], "product_status": { "known_affected": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003" ] }, "references": [ { "category": "external", "summary": "web.nvd.nist.gov", "url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2023-29029" }, { "category": "external", "summary": "www.first.org", "url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:H/UI:N/S:U/C:L/I:L/A:L" } ], "remediations": [ { "category": "vendor_fix", "details": "Rockwell Automation recommends users take the following measures to mitigate the risk of these vulnerabilities:", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003" ] }, { "category": "vendor_fix", "details": "Disable the webserver during normal use. The webserver is disabled by default and should only be enabled to modify configurations. After modifying configurations, the web server should be disabled.", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003" ] }, { "category": "vendor_fix", "details": "For information on how to mitigate security risks on industrial automation control systems (IACS) networks see the following publications:", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003" ] }, { "category": "vendor_fix", "details": "System Security Design Guidelines Reference Manual publication, SECURE-RM001", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003" ], "url": "https://manuals.plus/m/034dd41130c94a4265d75b89b1ae8c6cca6223ea538a03c3dd7660487fb74a8a" }, { "category": "vendor_fix", "details": "Configure System Security Features User Manual, SECURE-UM001", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003" ], "url": "https://pdf4pro.com/view/configure-system-security-features-user-manual-5f8cd0.html" }, { "category": "vendor_fix", "details": "Additionally, Rockwell Automation encourages customers to implement their suggested Security Best Practices to minimize the risk of the vulnerabilities.", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003" ], "url": "https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/1085012/loc/en_US#__highlight" } ], "scores": [ { "cvss_v3": { "baseScore": 4.7, "baseSeverity": "MEDIUM", "vectorString": "CVSS:3.0/AV:N/AC:L/PR:H/UI:N/S:U/C:L/I:L/A:L", "version": "3.0" }, "products": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003" ] } ] }, { "cve": "CVE-2023-29022", "cwe": { "id": "CWE-20", "name": "Improper Input Validation" }, "notes": [ { "category": "summary", "text": "A cross site scripting vulnerability was discovered that could potentially allow a malicious user with admin privileges and network access to view user data and modify the web interface. Additionally, a malicious user could potentially cause interruptions to the availability of the web page.", "title": "Vulnerability Summary" } ], "product_status": { "known_affected": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003" ] }, "references": [ { "category": "external", "summary": "web.nvd.nist.gov", "url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2023-29022" }, { "category": "external", "summary": "www.first.org", "url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:H/UI:N/S:U/C:L/I:L/A:L" } ], "remediations": [ { "category": "vendor_fix", "details": "Rockwell Automation recommends users take the following measures to mitigate the risk of these vulnerabilities:", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003" ] }, { "category": "vendor_fix", "details": "Disable the webserver during normal use. The webserver is disabled by default and should only be enabled to modify configurations. After modifying configurations, the web server should be disabled.", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003" ] }, { "category": "vendor_fix", "details": "For information on how to mitigate security risks on industrial automation control systems (IACS) networks see the following publications:", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003" ] }, { "category": "vendor_fix", "details": "System Security Design Guidelines Reference Manual publication, SECURE-RM001", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003" ], "url": "https://manuals.plus/m/034dd41130c94a4265d75b89b1ae8c6cca6223ea538a03c3dd7660487fb74a8a" }, { "category": "vendor_fix", "details": "Configure System Security Features User Manual, SECURE-UM001", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003" ], "url": "https://pdf4pro.com/view/configure-system-security-features-user-manual-5f8cd0.html" }, { "category": "vendor_fix", "details": "Additionally, Rockwell Automation encourages customers to implement their suggested Security Best Practices to minimize the risk of the vulnerabilities.", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003" ], "url": "https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/1085012/loc/en_US#__highlight" } ], "scores": [ { "cvss_v3": { "baseScore": 4.7, "baseSeverity": "MEDIUM", "vectorString": "CVSS:3.0/AV:N/AC:L/PR:H/UI:N/S:U/C:L/I:L/A:L", "version": "3.0" }, "products": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003" ] } ] } ] }
Loading...
Loading...
Sightings
Author | Source | Type | Date |
---|
Nomenclature
- Seen: The vulnerability was mentioned, discussed, or seen somewhere by the user.
- Confirmed: The vulnerability is confirmed from an analyst perspective.
- Exploited: This vulnerability was exploited and seen by the user reporting the sighting.
- Patched: This vulnerability was successfully patched by the user reporting the sighting.
- Not exploited: This vulnerability was not exploited or seen by the user reporting the sighting.
- Not confirmed: The user expresses doubt about the veracity of the vulnerability.
- Not patched: This vulnerability was not successfully patched by the user reporting the sighting.