SEVD-2022-256-01
Vulnerability from csaf_se - Published: 2022-09-13 05:45 - Updated: 2022-09-13 05:45Summary
EcoStruxure Machine SCADA Expert and Pro-face BLUE Open Studio
Notes
General Security Recommendations
We strongly recommend the following industry cybersecurity best practices.
https://www.se.com/us/en/download/document/7EN52-0390/
* Locate control and safety system networks and remote devices behind firewalls and isolate them from the business network.
* Install physical controls so no unauthorized personnel can access your industrial control and safety systems, components, peripheral equipment, and networks.
* Place all controllers in locked cabinets and never leave them in the “Program” mode.
* Never connect programming software to any network other than the network intended for that device.
* Scan all methods of mobile data exchange with the isolated network such as CDs, USB drives, etc. before use in the terminals or any node connected to these networks.
* Never allow mobile devices that have connected to any other network besides the intended network to connect to the safety or control networks without proper sanitation.
* Minimize network exposure for all control system devices and systems and ensure that they are not accessible from the Internet.
* When remote access is required, use secure methods, such as Virtual Private Networks (VPNs). Recognize that VPNs may have vulnerabilities and should be updated to the most current version available. Also, understand that VPNs are only as secure as the connected devices.
For more information refer to the Schneider Electric Recommended Cybersecurity Best Practices document.
For More Information
This document provides an overview of the identified vulnerability or vulnerabilities and actions required to mitigate. For more details and assistance on how to protect your installation, contact your local Schneider Electric representative or Schneider Electric Industrial Cybersecurity Services: https://www.se.com/ww/en/work/solutions/cybersecurity/. These organizations will be fully aware of this situation and can support you through the process.
For further information related to cybersecurity in Schneider Electric’s products, visit the company’s cybersecurity support portal page: https://www.se.com/ww/en/work/support/cybersecurity/overview.jsp
LEGAL DISCLAIMER
THIS NOTIFICATION DOCUMENT, THE INFORMATION CONTAINED HEREIN, AND ANY MATERIALS LINKED FROM IT (COLLECTIVELY, THIS “NOTIFICATION”) ARE INTENDED TO HELP PROVIDE AN OVERVIEW OF THE IDENTIFIED SITUATION AND SUGGESTED MITIGATION ACTIONS, REMEDIATION, FIX, AND/OR GENERAL SECURITY RECOMMENDATIONS AND IS PROVIDED ON AN “AS-IS” BASIS WITHOUT WARRANTY OR GUARANTEE OF ANY KIND. SCHNEIDER ELECTRIC DISCLAIMS ALL WARRANTIES RELATING TO THIS NOTIFICATION, EITHER EXPRESS OR IMPLIED, INCLUDING WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. SCHNEIDER ELECTRIC MAKES NO WARRANTY THAT THE NOTIFICATION WILL RESOLVE THE IDENTIFIED SITUATION. IN NO EVENT SHALL SCHNEIDER ELECTRIC BE LIABLE FOR ANY DAMAGES OR LOSSES WHATSOEVER IN CONNECTION WITH THIS NOTIFICATION, INCLUDING DIRECT, INDIRECT, INCIDENTAL, CONSEQUENTIAL, LOSS OF BUSINESS PROFITS OR SPECIAL DAMAGES, EVEN IF SCHNEIDER ELECTRIC HAS BEEN ADVISED OF THE POSSIBILITY OF SUCH DAMAGES. YOUR USE OF THIS NOTIFICATION IS AT YOUR OWN RISK, AND YOU ARE SOLELY LIABLE FOR ANY DAMAGES TO YOUR SYSTEMS OR ASSETS OR OTHER LOSSES THAT MAY RESULT FROM YOUR USE OF THIS NOTIFICATION. SCHNEIDER ELECTRIC RESERVES THE RIGHT TO UPDATE OR CHANGE THIS NOTIFICATION AT ANY TIME AND IN ITS SOLE DISCRETION
About Schneider Electric
At Schneider, we believe access to energy and digital is a basic human right. We empower all to do more with less, ensuring Life Is On everywhere, for everyone, at every moment.
We provide energy and automation digital solutions for efficiency and sustainability. We combine world-leading energy technologies, real-time automation, software and services into integrated solutions for Homes, Buildings, Data Centers, Infrastructure and Industries.
We are committed to unleash the infinite possibilities of an open, global, innovative community that is passionate with our Meaningful Purpose, Inclusive and Empowered values.
www.se.com
Overview
Schneider Electric is aware of multiple vulnerabilities in its EcoStruxure Machine SCADA Expert and Pro-face BLUE Open Studio products. EcoStruxure Machine SCADA Expert is a powerful software for developing HMI, SCADA, OEE and Dashboard projects dedicated to Line Management & Lite Supervision applications to run in Harmony Industrial PC and GTU Open Box. Pro-face BLUE Open Studio is a development and runtime software that incorporates all of the tools users need to create SCADA HMI applications, dashboards and OEE interfaces. Failure to apply the mitigations provided below may risk a modification of project files which could result in arbitrary code execution, information disclosure, or denial of service.
{
"document": {
"category": "csaf_security_advisory",
"csaf_version": "2.0",
"distribution": {
"text": "Public",
"tlp": {
"label": "WHITE"
}
},
"lang": "en-US",
"notes": [
{
"category": "general",
"text": "We strongly recommend the following industry cybersecurity best practices.\n\nhttps://www.se.com/us/en/download/document/7EN52-0390/\n* Locate control and safety system networks and remote devices behind firewalls and isolate them from the business network.\n* Install physical controls so no unauthorized personnel can access your industrial control and safety systems, components, peripheral equipment, and networks.\n* Place all controllers in locked cabinets and never leave them in the \u201cProgram\u201d mode.\n* Never connect programming software to any network other than the network intended for that device.\n* Scan all methods of mobile data exchange with the isolated network such as CDs, USB drives, etc. before use in the terminals or any node connected to these networks.\n* Never allow mobile devices that have connected to any other network besides the intended network to connect to the safety or control networks without proper sanitation.\n* Minimize network exposure for all control system devices and systems and ensure that they are not accessible from the Internet.\n* When remote access is required, use secure methods, such as Virtual Private Networks (VPNs). Recognize that VPNs may have vulnerabilities and should be updated to the most current version available. Also, understand that VPNs are only as secure as the connected devices.\nFor more information refer to the Schneider Electric Recommended Cybersecurity Best Practices document. \n",
"title": "General Security Recommendations"
},
{
"category": "general",
"text": "This document provides an overview of the identified vulnerability or vulnerabilities and actions required to mitigate. For more details and assistance on how to protect your installation, contact your local Schneider Electric representative or Schneider Electric Industrial Cybersecurity Services: https://www.se.com/ww/en/work/solutions/cybersecurity/. These organizations will be fully aware of this situation and can support you through the process.\nFor further information related to cybersecurity in Schneider Electric\u2019s products, visit the company\u2019s cybersecurity support portal page: https://www.se.com/ww/en/work/support/cybersecurity/overview.jsp",
"title": "For More Information"
},
{
"category": "legal_disclaimer",
"text": "THIS NOTIFICATION DOCUMENT, THE INFORMATION CONTAINED HEREIN, AND ANY MATERIALS LINKED FROM IT (COLLECTIVELY, THIS \u201cNOTIFICATION\u201d) ARE INTENDED TO HELP PROVIDE AN OVERVIEW OF THE IDENTIFIED SITUATION AND SUGGESTED MITIGATION ACTIONS, REMEDIATION, FIX, AND/OR GENERAL SECURITY RECOMMENDATIONS AND IS PROVIDED ON AN \u201cAS-IS\u201d BASIS WITHOUT WARRANTY OR GUARANTEE OF ANY KIND. SCHNEIDER ELECTRIC DISCLAIMS ALL WARRANTIES RELATING TO THIS NOTIFICATION, EITHER EXPRESS OR IMPLIED, INCLUDING WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. SCHNEIDER ELECTRIC MAKES NO WARRANTY THAT THE NOTIFICATION WILL RESOLVE THE IDENTIFIED SITUATION. IN NO EVENT SHALL SCHNEIDER ELECTRIC BE LIABLE FOR ANY DAMAGES OR LOSSES WHATSOEVER IN CONNECTION WITH THIS NOTIFICATION, INCLUDING DIRECT, INDIRECT, INCIDENTAL, CONSEQUENTIAL, LOSS OF BUSINESS PROFITS OR SPECIAL DAMAGES, EVEN IF SCHNEIDER ELECTRIC HAS BEEN ADVISED OF THE POSSIBILITY OF SUCH DAMAGES. YOUR USE OF THIS NOTIFICATION IS AT YOUR OWN RISK, AND YOU ARE SOLELY LIABLE FOR ANY DAMAGES TO YOUR SYSTEMS OR ASSETS OR OTHER LOSSES THAT MAY RESULT FROM YOUR USE OF THIS NOTIFICATION. SCHNEIDER ELECTRIC RESERVES THE RIGHT TO UPDATE OR CHANGE THIS NOTIFICATION AT ANY TIME AND IN ITS SOLE DISCRETION",
"title": "LEGAL DISCLAIMER"
},
{
"category": "general",
"text": "At Schneider, we believe access to energy and digital is a basic human right. We empower all to do more with less, ensuring Life Is On everywhere, for everyone, at every moment.\n\nWe provide energy and automation digital solutions for efficiency and sustainability. We combine world-leading energy technologies, real-time automation, software and services into integrated solutions for Homes, Buildings, Data Centers, Infrastructure and Industries.\n\nWe are committed to unleash the infinite possibilities of an open, global, innovative community that is passionate with our Meaningful Purpose, Inclusive and Empowered values.\n\nwww.se.com ",
"title": "About Schneider Electric"
},
{
"category": "summary",
"text": "Schneider Electric is aware of multiple vulnerabilities in its EcoStruxure Machine SCADA Expert and Pro-face BLUE Open Studio products. EcoStruxure Machine SCADA Expert is a powerful software for developing HMI, SCADA, OEE and Dashboard projects dedicated to Line Management \u0026 Lite Supervision applications to run in Harmony Industrial PC and GTU Open Box. Pro-face BLUE Open Studio is a development and runtime software that incorporates all of the tools users need to create SCADA HMI applications, dashboards and OEE interfaces. Failure to apply the mitigations provided below may risk a modification of project files which could result in arbitrary code execution, information disclosure, or denial of service.",
"title": "Overview"
}
],
"publisher": {
"category": "vendor",
"contact_details": "cybersecurity@se.com",
"name": "Schneider Electric CPCERT",
"namespace": "https://www.se.com/ww/en/work/support/cybersecurity/security-notifications.jsp"
},
"references": [
{
"category": "self",
"summary": "EcoStruxure Machine SCADA Expert Pro-face BLUE Open Studio - SEVD-2022-256-01 PDF Version",
"url": "https://download.schneider-electric.com/files?p_Doc_Ref=SEVD-2022-256-01\u0026p_enDocType=Security+and+Safety+Notice\u0026p_File_Name=SEVD-2022-256-01-EcoStruxure_Machine_SCADA_ExpertPro-face_BLUE_Open_Studio_Security_Notification.pdf"
},
{
"category": "self",
"summary": "EcoStruxure Machine SCADA Expert Pro-face BLUE Open Studio - SEVD-2022-256-01 CSAF Version",
"url": "https://download.schneider-electric.com/files?p_Doc_Ref=SEVD-2022-256-01\u0026p_enDocType=Security+and+Safety+Notice\u0026p_File_Name=sevd-2022-256-01.json"
},
{
"category": "external",
"summary": "Recommended Cybersecurity Best Practices",
"url": "https://www.se.com/us/en/download/document/7EN52-0390/"
}
],
"title": "EcoStruxure Machine SCADA Expert and Pro-face BLUE Open Studio",
"tracking": {
"current_release_date": "2022-09-13T05:45:41.000Z",
"generator": {
"date": "2022-09-12T14:34:22.255Z",
"engine": {
"name": "Schneider Electric CSAF Generator",
"version": "1.2"
}
},
"id": "SEVD-2022-256-01",
"initial_release_date": "2022-09-13T05:45:41.000Z",
"revision_history": [
{
"date": "2022-09-13T05:45:41.000Z",
"number": "1",
"summary": "Original Release"
}
],
"status": "final",
"version": "1"
}
},
"product_tree": {
"branches": [
{
"branches": [
{
"branches": [
{
"category": "product_version_range",
"name": "\u003c=20.0.2",
"product": {
"name": "Schneider Electric EcoStruxure Machine SCADA Expert 2020 Service Pack 2 version 20.0.2 and prior",
"product_id": "1"
}
}
],
"category": "product_name",
"name": "EcoStruxure Machine SCADA Expert 2020 Service Pack 2"
},
{
"branches": [
{
"category": "product_version",
"name": "HotFix 2020.2.00.40",
"product": {
"name": "Schneider Electric EcoStruxure Machine SCADA Expert 2020 Service Pack 2 Hot Fix 2020.2.00.40",
"product_id": "2"
}
}
],
"category": "product_name",
"name": "EcoStruxure Machine SCADA Expert 2020 Service Pack 2"
},
{
"branches": [
{
"category": "product_version_range",
"name": "\u003c=20.0.2",
"product": {
"name": "Schneider Electric BLUE Open Studio 2020 Service Pack 2 version 20.0.2 and prior",
"product_id": "3"
}
}
],
"category": "product_name",
"name": "BLUE Open Studio 2020 Service Pack 2"
},
{
"branches": [
{
"category": "product_version",
"name": "HotFix 2020.2.00.40",
"product": {
"name": "Schneider Electric BLUE Open Studio 2020 Service Pack 2 HotFix 2020.2.00.40",
"product_id": "4"
}
}
],
"category": "product_name",
"name": "BLUE Open Studio 2020 Service Pack 2"
}
],
"category": "vendor",
"name": "Schneider Electric"
}
]
},
"vulnerabilities": [
{
"acknowledgments": [
{
"names": [
"?"
],
"organization": "?"
}
],
"cwe": {
"id": "CWE-502",
"name": "Deserialization of Untrusted Data"
},
"notes": [
{
"category": "description",
"text": "CWE-502: Deserialization of Untrusted Datavulnerability exists that can lead to arbitrary code execution, information disclosure, or denial of services when the project file is loaded. Successful exploitation of the vulnerabilities requires user interaction and write access to HMI project file.",
"title": "CVE Description"
}
],
"product_status": {
"fixed": [
"2",
"4"
],
"known_affected": [
"1",
"3"
]
},
"remediations": [
{
"category": "vendor_fix",
"details": "Version 2020 Service Pack 2 Hot Fix 2020.2.00.40 of EcoStruxure Machine SCADA Expert includes a fix for this vulnerability. Please contact your Schneider Electric Customer Care Center to obtain the Hot Fix. For additional detail please refer to the supplied help file in Hot Fix2020.2.00.4",
"product_ids": [
"1"
],
"restart_required": {
"category": "none"
}
},
{
"category": "vendor_fix",
"details": "Version 2020 Service Pack 2 Hot Fix 2020.2.00.40 of BLUE Open Studio includes a fix for this vulnerability. Please contact your Pro-face Customer Care Center to obtain the Hot Fix. For additional detail please refer to the supplied help file in Hot Fix2020.2.00.40. ",
"product_ids": [
"3"
],
"restart_required": {
"category": "none"
}
},
{
"category": "mitigation",
"details": "In addition to applying the remediations provided above, the following general precautions should be taken throughout the lifetime of EcoStruxure Machine SCADA Expert projects and BLUE Open Studio projects: \r\n\u2022Access Control Lists should be applied to all folders where users will save and load projectfiles. \r\n\u2022Enforce a trusted chain-of-custody on project files, maintained during creation, modification, distribution, and use. \r\n\u2022Train users to always verify the source of a project is trusted before opening/executing it. ",
"product_ids": [
"1",
"3"
],
"restart_required": {
"category": "none"
}
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "LOCAL",
"availabilityImpact": "HIGH",
"baseScore": 7.8,
"baseSeverity": "HIGH",
"confidentialityImpact": "HIGH",
"integrityImpact": "HIGH",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"userInteraction": "REQUIRED",
"vectorString": "CVSS:3.1/AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H",
"version": "3.1"
},
"products": [
"1",
"3"
]
}
],
"title": "?"
}
]
}
Loading…
Loading…
Sightings
| Author | Source | Type | Date |
|---|
Nomenclature
- Seen: The vulnerability was mentioned, discussed, or observed by the user.
- Confirmed: The vulnerability has been validated from an analyst's perspective.
- Published Proof of Concept: A public proof of concept is available for this vulnerability.
- Exploited: The vulnerability was observed as exploited by the user who reported the sighting.
- Patched: The vulnerability was observed as successfully patched by the user who reported the sighting.
- Not exploited: The vulnerability was not observed as exploited by the user who reported the sighting.
- Not confirmed: The user expressed doubt about the validity of the vulnerability.
- Not patched: The vulnerability was not observed as successfully patched by the user who reported the sighting.
Loading…
Loading…