Vulnerability from csaf_siemens - Published: 2023-04-11 00:00 - Updated: 2023-04-11 00:00Summary
SSA-472454: Command Injection Vulnerability in CPCI85 Firmware of SICAM A8000 Devices
Notes
Summary
The CPCI85 firmware of SICAM A8000 CP-8031 and CP-8050 is affected by unauthenticated command injection vulnerability. This could allow an attacker to perfom remote code execution.
Siemens has released updates for the affected products and recommends to update to the latest versions.
General Recommendations
Operators of critical power systems (e.g. TSOs or DSOs) worldwide are usually required by regulations to build resilience into the power grids by applying multi-level redundant secondary protection schemes. It is therefore recommended that the operators check whether appropriate resilient protection measures are in place. The risk of cyber incidents impacting the grid's reliability can thus be minimized by virtue of the grid design.
Siemens strongly recommends applying the provided security updates using the corresponding tooling and documented procedures made available with the product. If supported by the product, an automated means to apply the security updates across multiple product instances may be used. Siemens strongly recommends prior validation of any security update before being applied, and supervision by trained staff of the update process in the target environment.
As a general security measure Siemens strongly recommends to protect network access with appropriate mechanisms (e.g. firewalls, segmentation, VPN). It is advised to configure the environment according to our operational guidelines in order to run the devices in a protected IT environment.
Recommended security guidelines can be found at:
https://www.siemens.com/gridsecurity
Additional Resources
For further inquiries on security vulnerabilities in Siemens products and solutions, please contact the Siemens ProductCERT: https://www.siemens.com/cert/advisories
Terms of Use
Siemens Security Advisories are subject to the terms and conditions contained in Siemens' underlying license terms or other applicable agreements previously agreed to with Siemens (hereinafter "License Terms"). To the extent applicable to information, software or documentation made available in or through a Siemens Security Advisory, the Terms of Use of Siemens' Global Website (https://www.siemens.com/terms_of_use, hereinafter "Terms of Use"), in particular Sections 8-10 of the Terms of Use, shall apply additionally. In case of conflicts, the License Terms shall prevail over the Terms of Use.
{
"document": {
"category": "csaf_security_advisory",
"csaf_version": "2.0",
"distribution": {
"text": "Disclosure is not limited. (TLPv2: TLP:CLEAR)",
"tlp": {
"label": "WHITE"
}
},
"lang": "en",
"notes": [
{
"category": "summary",
"text": "The CPCI85 firmware of SICAM A8000 CP-8031 and CP-8050 is affected by unauthenticated command injection vulnerability. This could allow an attacker to perfom remote code execution.\n\nSiemens has released updates for the affected products and recommends to update to the latest versions.",
"title": "Summary"
},
{
"category": "general",
"text": "Operators of critical power systems (e.g. TSOs or DSOs) worldwide are usually required by regulations to build resilience into the power grids by applying multi-level redundant secondary protection schemes. It is therefore recommended that the operators check whether appropriate resilient protection measures are in place. The risk of cyber incidents impacting the grid\u0027s reliability can thus be minimized by virtue of the grid design.\nSiemens strongly recommends applying the provided security updates using the corresponding tooling and documented procedures made available with the product. If supported by the product, an automated means to apply the security updates across multiple product instances may be used. Siemens strongly recommends prior validation of any security update before being applied, and supervision by trained staff of the update process in the target environment. \nAs a general security measure Siemens strongly recommends to protect network access with appropriate mechanisms (e.g. firewalls, segmentation, VPN). It is advised to configure the environment according to our operational guidelines in order to run the devices in a protected IT environment.\n\nRecommended security guidelines can be found at:\n\nhttps://www.siemens.com/gridsecurity",
"title": "General Recommendations"
},
{
"category": "general",
"text": "For further inquiries on security vulnerabilities in Siemens products and solutions, please contact the Siemens ProductCERT: https://www.siemens.com/cert/advisories",
"title": "Additional Resources"
},
{
"category": "legal_disclaimer",
"text": "Siemens Security Advisories are subject to the terms and conditions contained in Siemens\u0027 underlying license terms or other applicable agreements previously agreed to with Siemens (hereinafter \"License Terms\"). To the extent applicable to information, software or documentation made available in or through a Siemens Security Advisory, the Terms of Use of Siemens\u0027 Global Website (https://www.siemens.com/terms_of_use, hereinafter \"Terms of Use\"), in particular Sections 8-10 of the Terms of Use, shall apply additionally. In case of conflicts, the License Terms shall prevail over the Terms of Use.",
"title": "Terms of Use"
}
],
"publisher": {
"category": "vendor",
"contact_details": "productcert@siemens.com",
"name": "Siemens ProductCERT",
"namespace": "https://www.siemens.com"
},
"references": [
{
"category": "self",
"summary": "SSA-472454: Command Injection Vulnerability in CPCI85 Firmware of SICAM A8000 Devices - HTML Version",
"url": "https://cert-portal.siemens.com/productcert/html/ssa-472454.html"
},
{
"category": "self",
"summary": "SSA-472454: Command Injection Vulnerability in CPCI85 Firmware of SICAM A8000 Devices - CSAF Version",
"url": "https://cert-portal.siemens.com/productcert/csaf/ssa-472454.json"
},
{
"category": "self",
"summary": "SSA-472454: Command Injection Vulnerability in CPCI85 Firmware of SICAM A8000 Devices - PDF Version",
"url": "https://cert-portal.siemens.com/productcert/pdf/ssa-472454.pdf"
},
{
"category": "self",
"summary": "SSA-472454: Command Injection Vulnerability in CPCI85 Firmware of SICAM A8000 Devices - TXT Version",
"url": "https://cert-portal.siemens.com/productcert/txt/ssa-472454.txt"
}
],
"title": "SSA-472454: Command Injection Vulnerability in CPCI85 Firmware of SICAM A8000 Devices",
"tracking": {
"current_release_date": "2023-04-11T00:00:00Z",
"generator": {
"engine": {
"name": "Siemens ProductCERT CSAF Generator",
"version": "1"
}
},
"id": "SSA-472454",
"initial_release_date": "2023-04-11T00:00:00Z",
"revision_history": [
{
"date": "2023-04-11T00:00:00Z",
"legacy_version": "1.0",
"number": "1",
"summary": "Publication Date"
}
],
"status": "interim",
"version": "1"
}
},
"product_tree": {
"branches": [
{
"branches": [
{
"branches": [
{
"category": "product_version_range",
"name": "vers:all/\u003cCPCI85 V05",
"product": {
"name": "CP-8031 MASTER MODULE (6MF2803-1AA00)",
"product_id": "1",
"product_identification_helper": {
"model_numbers": [
"6MF2803-1AA00"
]
}
}
}
],
"category": "product_name",
"name": "CP-8031 MASTER MODULE (6MF2803-1AA00)"
},
{
"branches": [
{
"category": "product_version_range",
"name": "vers:all/\u003cCPCI85 V05",
"product": {
"name": "CP-8050 MASTER MODULE (6MF2805-0AA00)",
"product_id": "2",
"product_identification_helper": {
"model_numbers": [
"6MF2805-0AA00"
]
}
}
}
],
"category": "product_name",
"name": "CP-8050 MASTER MODULE (6MF2805-0AA00)"
}
],
"category": "vendor",
"name": "Siemens"
}
]
},
"vulnerabilities": [
{
"cve": "CVE-2023-28489",
"cwe": {
"id": "CWE-77",
"name": "Improper Neutralization of Special Elements used in a Command (\u0027Command Injection\u0027)"
},
"notes": [
{
"category": "summary",
"text": "Affected devices are vulnerable to command injection via the web server port 443/tcp, if the parameter \u201cRemote Operation\u201d is enabled. The parameter is disabled by default.\r\nThe vulnerability could allow an unauthenticated remote attacker to perform arbitrary code execution on the device.",
"title": "Summary"
}
],
"product_status": {
"known_affected": [
"1",
"2"
]
},
"remediations": [
{
"category": "mitigation",
"details": "Limit access to the web server on port 80/TCP and 443/TCP with an external firewall.",
"product_ids": [
"1",
"2"
]
},
{
"category": "vendor_fix",
"details": "Update to CPCI85 V05 or later version",
"product_ids": [
"1"
],
"url": "https://support.industry.siemens.com/cs/ww/en/view/109804985/"
},
{
"category": "vendor_fix",
"details": "Update to CPCI85 V05 or later version",
"product_ids": [
"2"
],
"url": "https://support.industry.siemens.com/cs/ww/en/view/109804985/"
}
],
"scores": [
{
"cvss_v3": {
"baseScore": 9.8,
"baseSeverity": "CRITICAL",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H/E:P/RL:O/RC:C",
"version": "3.1"
},
"products": [
"1",
"2"
]
}
],
"title": "CVE-2023-28489"
}
]
}
Loading…
Loading…
Sightings
| Author | Source | Type | Date |
|---|
Nomenclature
- Seen: The vulnerability was mentioned, discussed, or observed by the user.
- Confirmed: The vulnerability has been validated from an analyst's perspective.
- Published Proof of Concept: A public proof of concept is available for this vulnerability.
- Exploited: The vulnerability was observed as exploited by the user who reported the sighting.
- Patched: The vulnerability was observed as successfully patched by the user who reported the sighting.
- Not exploited: The vulnerability was not observed as exploited by the user who reported the sighting.
- Not confirmed: The user expressed doubt about the validity of the vulnerability.
- Not patched: The vulnerability was not observed as successfully patched by the user who reported the sighting.