VDE-2025-094

Vulnerability from csaf_janitzaelectronicsgmbh - Published: 2025-11-24 12:00 - Updated: 2025-11-24 12:00
Summary
Janitza: Vulnerability in Modbus interface of UMG 96-PA and UMG 96-PA-MID+
Severity
Medium
Notes
Summary: A vulnerability in the devices UMG 96-PA and UMG 96-PA-MID+ enables an unauthenticated remote attacker to cause the device to become unavailable.
Impact: When exploiting the vulnerability the device becomes unavailable. It will not continue to work as expected including not responding to further requests. Additionally it's measurement functionalities stop working effectively making the device unavailable until the next restart.
Mitigation: It is strongly advised to operate the device in a closed network protected by a suitable firewall. Network access to the device should be limited to only enable necessary components to access it. Special focus should be on the Modbus protocol as the core communication protocol of the device.
Remediation: It is strongly advised to update to the newest version. The vulnerability is fixed in version 3.54.

An unauthenticated remote attacker can send a specially crafted Modbus read command to the device which leads to a denial of service.

CWE-1287 - Improper Validation of Specified Type of Input
Mitigation It is strongly advised to operate the device in a closed network protected by a suitable firewall. Network access to the device should be limited to only enable necessary components to access it. Special focus should be on the Modbus protocol as the core communication protocol of the device.
Vendor Fix It is strongly advised to update to the newest version. The vulnerability is fixed in version 3.54.
Acknowledgments
Milence - Commercial Vehicle Charging Europe B.V.

{
  "document": {
    "acknowledgments": [
      {
        "organization": "CERTVDE",
        "summary": "Coordination",
        "urls": [
          "https://certvde.com/en/"
        ]
      },
      {
        "organization": "Milence - Commercial Vehicle Charging Europe B.V.",
        "summary": "Reporting"
      }
    ],
    "aggregate_severity": {
      "namespace": "https://www.first.org/cvss/v3.1/specification-document#Qualitative-Severity-Rating-Scale",
      "text": "Medium"
    },
    "category": "csaf_security_advisory",
    "csaf_version": "2.0",
    "distribution": {
      "tlp": {
        "label": "WHITE",
        "url": "https://www.first.org/tlp/"
      }
    },
    "lang": "en-GB",
    "notes": [
      {
        "category": "summary",
        "text": "A vulnerability in the devices UMG 96-PA and UMG 96-PA-MID+ enables an unauthenticated remote attacker to cause the device to become unavailable.",
        "title": "Summary"
      },
      {
        "category": "description",
        "text": "When exploiting the vulnerability the device becomes unavailable. It will not continue to work as expected including not responding to further requests. Additionally it\u0027s measurement functionalities stop working effectively making the device unavailable until the next restart.",
        "title": "Impact"
      },
      {
        "category": "description",
        "text": "It is strongly advised to operate the device in a closed network protected by a suitable firewall. Network access to the device should be limited to only enable necessary components to access it. Special focus should be on the Modbus protocol as the core communication protocol of the device.",
        "title": "Mitigation"
      },
      {
        "category": "description",
        "text": "It is strongly advised to update to the newest version. The vulnerability is fixed in version 3.54.",
        "title": "Remediation"
      }
    ],
    "publisher": {
      "category": "vendor",
      "contact_details": "security@janitza.de",
      "name": "Janitza electronics GmbH",
      "namespace": "https://www.janitza.com"
    },
    "references": [
      {
        "category": "external",
        "summary": "Janitza PSIRT contact",
        "url": "https://www.janitza.com/de-de/service-support/security-issue-ticket"
      },
      {
        "category": "external",
        "summary": "Janitza advisory overview at CERT@VDE",
        "url": "https://certvde.com/de/advisories/vendor/janitza/"
      },
      {
        "category": "self",
        "summary": "VDE-2025-094: Janitza: Vulnerability in Modbus interface of UMG 96-PA and UMG 96-PA-MID+ - HTML",
        "url": "https://certvde.com/en/advisories/VDE-2025-094"
      },
      {
        "category": "self",
        "summary": "VDE-2025-094: Janitza: Vulnerability in Modbus interface of UMG 96-PA and UMG 96-PA-MID+ - CSAF",
        "url": "https://janitza.csaf-tp.certvde.com/.well-known/csaf/white/2025/vde-2025-094.json"
      }
    ],
    "title": "Janitza: Vulnerability in Modbus interface of UMG 96-PA and UMG 96-PA-MID+",
    "tracking": {
      "aliases": [
        "VDE-2025-094"
      ],
      "current_release_date": "2025-11-24T12:00:00.000Z",
      "generator": {
        "date": "2025-11-24T11:11:03.153Z",
        "engine": {
          "name": "Secvisogram",
          "version": "2.5.40"
        }
      },
      "id": "VDE-2025-094",
      "initial_release_date": "2025-11-24T12:00:00.000Z",
      "revision_history": [
        {
          "date": "2025-11-24T12:00:00.000Z",
          "number": "1.0.0",
          "summary": "Initial release."
        }
      ],
      "status": "final",
      "version": "1.0.0"
    }
  },
  "product_tree": {
    "branches": [
      {
        "branches": [
          {
            "branches": [
              {
                "category": "product_name",
                "name": "UMG 96-PA",
                "product": {
                  "name": "UMG 96-PA",
                  "product_id": "CSAFPID-11001",
                  "product_identification_helper": {
                    "model_numbers": [
                      "1761.8057"
                    ]
                  }
                }
              },
              {
                "category": "product_name",
                "name": "UMG 96-PA-MID+",
                "product": {
                  "name": "UMG 96-PA-MID+",
                  "product_id": "CSAFPID-11002"
                }
              }
            ],
            "category": "product_family",
            "name": "Hardware"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "\u003c3.54",
                "product": {
                  "name": "Firmware \u003c3.54",
                  "product_id": "CSAFPID-21001"
                }
              },
              {
                "category": "product_version",
                "name": "3.54",
                "product": {
                  "name": "Firmware 3.54",
                  "product_id": "CSAFPID-22001"
                }
              }
            ],
            "category": "product_family",
            "name": "Firmware"
          }
        ],
        "category": "vendor",
        "name": "Janitza"
      }
    ],
    "relationships": [
      {
        "category": "installed_on",
        "full_product_name": {
          "name": "Firmware \u003c3.54 installed on UMG 96-PA",
          "product_id": "CSAFPID-31001"
        },
        "product_reference": "CSAFPID-21001",
        "relates_to_product_reference": "CSAFPID-11001"
      },
      {
        "category": "installed_on",
        "full_product_name": {
          "name": "Firmware 3.54 installed on UMG 96-PA",
          "product_id": "CSAFPID-32001"
        },
        "product_reference": "CSAFPID-22001",
        "relates_to_product_reference": "CSAFPID-11001"
      },
      {
        "category": "installed_on",
        "full_product_name": {
          "name": "Firmware \u003c3.54 installed on UMG 96-PA-MID+",
          "product_id": "CSAFPID-31002"
        },
        "product_reference": "CSAFPID-21001",
        "relates_to_product_reference": "CSAFPID-11002"
      },
      {
        "category": "installed_on",
        "full_product_name": {
          "name": "Firmware 3.54 installed on UMG 96-PA-MID+",
          "product_id": "CSAFPID-32002"
        },
        "product_reference": "CSAFPID-22001",
        "relates_to_product_reference": "CSAFPID-11002"
      }
    ]
  },
  "vulnerabilities": [
    {
      "cve": "CVE-2025-41729",
      "cwe": {
        "id": "CWE-1287",
        "name": "Improper Validation of Specified Type of Input"
      },
      "notes": [
        {
          "category": "description",
          "text": "An unauthenticated remote attacker can send a specially crafted Modbus read command to the device which leads to a denial of service.",
          "title": "Description"
        }
      ],
      "product_status": {
        "fixed": [
          "CSAFPID-32001",
          "CSAFPID-32002"
        ],
        "known_affected": [
          "CSAFPID-31001",
          "CSAFPID-31002"
        ]
      },
      "remediations": [
        {
          "category": "mitigation",
          "details": "It is strongly advised to operate the device in a closed network protected by a suitable firewall. Network access to the device should be limited to only enable necessary components to access it. Special focus should be on the Modbus protocol as the core communication protocol of the device.",
          "product_ids": [
            "CSAFPID-31001",
            "CSAFPID-31002"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "It is strongly advised to update to the newest version. The vulnerability is fixed in version 3.54.",
          "product_ids": [
            "CSAFPID-21001"
          ]
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "attackComplexity": "LOW",
            "attackVector": "NETWORK",
            "availabilityImpact": "HIGH",
            "baseScore": 7.5,
            "baseSeverity": "HIGH",
            "confidentialityImpact": "NONE",
            "environmentalScore": 7.5,
            "environmentalSeverity": "HIGH",
            "integrityImpact": "NONE",
            "privilegesRequired": "NONE",
            "scope": "UNCHANGED",
            "temporalScore": 7.5,
            "temporalSeverity": "HIGH",
            "userInteraction": "NONE",
            "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H",
            "version": "3.1"
          },
          "products": [
            "CSAFPID-31001",
            "CSAFPID-31002"
          ]
        }
      ],
      "title": "DoS via Modbus Read Command"
    }
  ]
}


Log in or create an account to share your comment.




Tags
Taxonomy of the tags.


Loading…

Loading…

Loading…

Sightings

Author Source Type Date

Nomenclature

  • Seen: The vulnerability was mentioned, discussed, or observed by the user.
  • Confirmed: The vulnerability has been validated from an analyst's perspective.
  • Published Proof of Concept: A public proof of concept is available for this vulnerability.
  • Exploited: The vulnerability was observed as exploited by the user who reported the sighting.
  • Patched: The vulnerability was observed as successfully patched by the user who reported the sighting.
  • Not exploited: The vulnerability was not observed as exploited by the user who reported the sighting.
  • Not confirmed: The user expressed doubt about the validity of the vulnerability.
  • Not patched: The vulnerability was not observed as successfully patched by the user who reported the sighting.


Loading…

Detection rules are retrieved from Rulezet.

Loading…

Loading…