Action not permitted
Modal body text goes here.
cve-2023-38640
Vulnerability from cvelistv5
▼ | Vendor | Product |
---|---|---|
Siemens | SICAM PAS/PQS |
{ "containers": { "adp": [ { "metrics": [ { "other": { "content": { "id": "CVE-2023-38640", "options": [ { "Exploitation": "none" }, { "Automatable": "no" }, { "Technical Impact": "partial" } ], "role": "CISA Coordinator", "timestamp": "2024-06-11T15:00:52.018807Z", "version": "2.0.3" }, "type": "ssvc" } } ], "providerMetadata": { "dateUpdated": "2024-06-11T15:01:07.657Z", "orgId": "134c704f-9b21-4f2e-91b3-4a467353bcc0", "shortName": "CISA-ADP" }, "title": "CISA ADP Vulnrichment" }, { "providerMetadata": { "dateUpdated": "2024-08-02T17:46:56.933Z", "orgId": "af854a3a-2127-422b-91ae-364da2661108", "shortName": "CVE" }, "references": [ { "tags": [ "x_transferred" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-035466.pdf" }, { "tags": [ "x_transferred" ], "url": "https://cert-portal.siemens.com/productcert/html/ssa-035466.html" } ], "title": "CVE Program Container" } ], "cna": { "affected": [ { "defaultStatus": "unknown", "product": "SICAM PAS/PQS", "vendor": "Siemens", "versions": [ { "lessThan": "V8.22", "status": "affected", "version": "V8.00", "versionType": "custom" } ] } ], "descriptions": [ { "lang": "en", "value": "A vulnerability has been identified in SICAM PAS/PQS (All versions \u003e= V8.00 \u003c V8.22). The affected application is installed with specific files and folders with insecure permissions. This could allow an authenticated local attacker to read and modify configuration data in the context of the application process." } ], "metrics": [ { "cvssV3_1": { "baseScore": 6.6, "baseSeverity": "MEDIUM", "vectorString": "CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:L/I:L/A:H/E:P/RL:O/RC:C", "version": "3.1" } } ], "problemTypes": [ { "descriptions": [ { "cweId": "CWE-732", "description": "CWE-732: Incorrect Permission Assignment for Critical Resource", "lang": "en", "type": "CWE" } ] } ], "providerMetadata": { "dateUpdated": "2024-06-11T14:20:03.897Z", "orgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77", "shortName": "siemens" }, "references": [ { "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-035466.pdf" }, { "url": "https://cert-portal.siemens.com/productcert/html/ssa-035466.html" } ] } }, "cveMetadata": { "assignerOrgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77", "assignerShortName": "siemens", "cveId": "CVE-2023-38640", "datePublished": "2023-10-10T10:21:25.048Z", "dateReserved": "2023-07-21T10:49:35.681Z", "dateUpdated": "2024-08-02T17:46:56.933Z", "state": "PUBLISHED" }, "dataType": "CVE_RECORD", "dataVersion": "5.1", "meta": { "nvd": "{\"cve\":{\"id\":\"CVE-2023-38640\",\"sourceIdentifier\":\"productcert@siemens.com\",\"published\":\"2023-10-10T11:15:12.063\",\"lastModified\":\"2024-06-11T09:15:13.423\",\"vulnStatus\":\"Modified\",\"descriptions\":[{\"lang\":\"en\",\"value\":\"A vulnerability has been identified in SICAM PAS/PQS (All versions \u003e= V8.00 \u003c V8.22). The affected application is installed with specific files and folders with insecure permissions. This could allow an authenticated local attacker to read and modify configuration data in the context of the application process.\"},{\"lang\":\"es\",\"value\":\"Se ha identificado una vulnerabilidad en SICAM PAS/PQS (Todas las versiones \u0026gt;= V8.00 \u0026lt; V8.22). La aplicaci\u00f3n afectada se instala con archivos y carpetas espec\u00edficos con permisos inseguros. Esto podr\u00eda permitir que un atacante local autenticado lea y modifique datos de configuraci\u00f3n en el contexto del proceso de solicitud.\"}],\"metrics\":{\"cvssMetricV31\":[{\"source\":\"nvd@nist.gov\",\"type\":\"Primary\",\"cvssData\":{\"version\":\"3.1\",\"vectorString\":\"CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:L/I:L/A:N\",\"attackVector\":\"LOCAL\",\"attackComplexity\":\"LOW\",\"privilegesRequired\":\"LOW\",\"userInteraction\":\"NONE\",\"scope\":\"UNCHANGED\",\"confidentialityImpact\":\"LOW\",\"integrityImpact\":\"LOW\",\"availabilityImpact\":\"NONE\",\"baseScore\":4.4,\"baseSeverity\":\"MEDIUM\"},\"exploitabilityScore\":1.8,\"impactScore\":2.5},{\"source\":\"productcert@siemens.com\",\"type\":\"Secondary\",\"cvssData\":{\"version\":\"3.1\",\"vectorString\":\"CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:L/I:L/A:H\",\"attackVector\":\"LOCAL\",\"attackComplexity\":\"LOW\",\"privilegesRequired\":\"LOW\",\"userInteraction\":\"NONE\",\"scope\":\"UNCHANGED\",\"confidentialityImpact\":\"LOW\",\"integrityImpact\":\"LOW\",\"availabilityImpact\":\"HIGH\",\"baseScore\":6.6,\"baseSeverity\":\"MEDIUM\"},\"exploitabilityScore\":1.8,\"impactScore\":4.7}]},\"weaknesses\":[{\"source\":\"productcert@siemens.com\",\"type\":\"Primary\",\"description\":[{\"lang\":\"en\",\"value\":\"CWE-732\"}]}],\"configurations\":[{\"nodes\":[{\"operator\":\"OR\",\"negate\":false,\"cpeMatch\":[{\"vulnerable\":true,\"criteria\":\"cpe:2.3:a:siemens:sicam_pas\\\\/pqs:*:*:*:*:*:*:*:*\",\"versionStartIncluding\":\"8.00\",\"versionEndExcluding\":\"8.22\",\"matchCriteriaId\":\"9F7F0A64-D3B9-483E-ABB5-86479D276D07\"}]}]}],\"references\":[{\"url\":\"https://cert-portal.siemens.com/productcert/html/ssa-035466.html\",\"source\":\"productcert@siemens.com\"},{\"url\":\"https://cert-portal.siemens.com/productcert/pdf/ssa-035466.pdf\",\"source\":\"productcert@siemens.com\",\"tags\":[\"Patch\",\"Vendor Advisory\"]}]}}" } }
ssa-035466
Vulnerability from csaf_siemens
Notes
{ "document": { "category": "csaf_security_advisory", "csaf_version": "2.0", "distribution": { "text": "Disclosure is not limited. (TLPv2: TLP:CLEAR)", "tlp": { "label": "WHITE" } }, "lang": "en", "notes": [ { "category": "summary", "text": "SICAM PAS/PQS is affected by insecure permission assignments in application folders that could allow an authenticated local attacker to read and modify configuration data or to escalate privileges. \n\nSiemens has released a new version for SICAM PAS/PQS and recommends to update to the latest version.\nSiemens has also released a security patch that can be applied to previous versions to fix the permissions of the impacted folders. See also chapter \nAdditional Information.", "title": "Summary" }, { "category": "general", "text": "Operators of critical power systems (e.g. TSOs or DSOs) worldwide are usually required by regulations to build resilience into the power grids by applying multi-level redundant secondary protection schemes. It is therefore recommended that the operators check whether appropriate resilient protection measures are in place. The risk of cyber incidents impacting the grid\u0027s reliability can thus be minimized by virtue of the grid design.\nSiemens strongly recommends applying the provided security updates using the corresponding tooling and documented procedures made available with the product. If supported by the product, an automated means to apply the security updates across multiple product instances may be used. Siemens strongly recommends prior validation of any security update before being applied, and supervision by trained staff of the update process in the target environment. \nAs a general security measure Siemens strongly recommends to protect network access with appropriate mechanisms (e.g. firewalls, segmentation, VPN). It is advised to configure the environment according to our operational guidelines in order to run the devices in a protected IT environment.\n\nRecommended security guidelines can be found at:\n\nhttps://www.siemens.com/gridsecurity", "title": "General Recommendations" }, { "category": "general", "text": "For further inquiries on security vulnerabilities in Siemens products and solutions, please contact the Siemens ProductCERT: https://www.siemens.com/cert/advisories", "title": "Additional Resources" }, { "category": "legal_disclaimer", "text": "Siemens Security Advisories are subject to the terms and conditions contained in Siemens\u0027 underlying license terms or other applicable agreements previously agreed to with Siemens (hereinafter \"License Terms\"). To the extent applicable to information, software or documentation made available in or through a Siemens Security Advisory, the Terms of Use of Siemens\u0027 Global Website (https://www.siemens.com/terms_of_use, hereinafter \"Terms of Use\"), in particular Sections 8-10 of the Terms of Use, shall apply additionally. In case of conflicts, the License Terms shall prevail over the Terms of Use.", "title": "Terms of Use" } ], "publisher": { "category": "vendor", "contact_details": "productcert@siemens.com", "name": "Siemens ProductCERT", "namespace": "https://www.siemens.com" }, "references": [ { "category": "self", "summary": "SSA-035466: Incorrect Permission Assignment in SICAM PAS/PQS - HTML Version", "url": "https://cert-portal.siemens.com/productcert/html/ssa-035466.html" }, { "category": "self", "summary": "SSA-035466: Incorrect Permission Assignment in SICAM PAS/PQS - CSAF Version", "url": "https://cert-portal.siemens.com/productcert/csaf/ssa-035466.json" }, { "category": "self", "summary": "SSA-035466: Incorrect Permission Assignment in SICAM PAS/PQS - PDF Version", "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-035466.pdf" }, { "category": "self", "summary": "SSA-035466: Incorrect Permission Assignment in SICAM PAS/PQS - TXT Version", "url": "https://cert-portal.siemens.com/productcert/txt/ssa-035466.txt" } ], "title": "SSA-035466: Incorrect Permission Assignment in SICAM PAS/PQS", "tracking": { "current_release_date": "2024-06-11T00:00:00Z", "generator": { "engine": { "name": "Siemens ProductCERT CSAF Generator", "version": "1" } }, "id": "SSA-035466", "initial_release_date": "2023-10-10T00:00:00Z", "revision_history": [ { "date": "2023-10-10T00:00:00Z", "legacy_version": "1.0", "number": "1", "summary": "Publication Date" }, { "date": "2024-06-11T00:00:00Z", "legacy_version": "1.1", "number": "2", "summary": "Added fix release for SICAM PAS/PQS for CVE-2023-38640" } ], "status": "final", "version": "2" } }, "product_tree": { "branches": [ { "branches": [ { "branches": [ { "category": "product_version_range", "name": "\u003e=V8.00\u003cV8.22", "product": { "name": "SICAM PAS/PQS", "product_id": "1" } }, { "category": "product_version_range", "name": "\u003e=V8.00\u003cV8.20", "product": { "name": "SICAM PAS/PQS", "product_id": "2" } } ], "category": "product_name", "name": "SICAM PAS/PQS" } ], "category": "vendor", "name": "Siemens" } ] }, "vulnerabilities": [ { "cve": "CVE-2023-38640", "cwe": { "id": "CWE-732", "name": "Incorrect Permission Assignment for Critical Resource" }, "notes": [ { "category": "summary", "text": "The affected application is installed with specific files and folders with insecure permissions. This could allow an authenticated local attacker to read and modify configuration data in the context of the application process.", "title": "Summary" } ], "product_status": { "known_affected": [ "1" ] }, "remediations": [ { "category": "mitigation", "details": "Ensure that only trusted persons have access to the system and avoid the configuration of additional local accounts on the server", "product_ids": [ "1" ] }, { "category": "vendor_fix", "details": "Install the Security Patch (available at \nhttps://support.industry.siemens.com/cs/ww/\nen/view/109824392/), which can be applied to versions V8.00 to V8.21", "product_ids": [ "1" ] }, { "category": "vendor_fix", "details": "Update to V8.22 or later version", "product_ids": [ "1" ] } ], "scores": [ { "cvss_v3": { "baseScore": 6.6, "baseSeverity": "MEDIUM", "vectorString": "CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:L/I:L/A:H/E:P/RL:O/RC:C", "version": "3.1" }, "products": [ "1" ] } ], "title": "CVE-2023-38640" }, { "cve": "CVE-2023-45205", "cwe": { "id": "CWE-732", "name": "Incorrect Permission Assignment for Critical Resource" }, "notes": [ { "category": "summary", "text": "The affected application is installed with specific files and folders with insecure permissions. This could allow an authenticated local attacker to inject arbitrary code and escalate privileges to `NT AUTHORITY/SYSTEM`.", "title": "Summary" } ], "product_status": { "known_affected": [ "2" ] }, "remediations": [ { "category": "mitigation", "details": "Ensure that only trusted persons have access to the system and avoid the configuration of additional local accounts on the server", "product_ids": [ "2" ] }, { "category": "vendor_fix", "details": "Install the Security Patch (available at \nhttps://support.industry.siemens.com/cs/ww/\nen/view/109824392/), which can be applied to versions V8.00 to V8.21", "product_ids": [ "2" ] }, { "category": "vendor_fix", "details": "Update to V8.20 or later version", "product_ids": [ "2" ] } ], "scores": [ { "cvss_v3": { "baseScore": 7.8, "baseSeverity": "HIGH", "vectorString": "CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H/E:P/RL:O/RC:C", "version": "3.1" }, "products": [ "2" ] } ], "title": "CVE-2023-45205" } ] }
var-202310-0215
Vulnerability from variot
A vulnerability has been identified in SICAM PAS/PQS (All versions >= V8.00 < V8.22). The affected application is installed with specific files and folders with insecure permissions. This could allow an authenticated local attacker to read and modify configuration data in the context of the application process. Siemens' sicam pas/pqs Contains a vulnerability in improper permission assignment for critical resources.Information may be obtained and information may be tampered with. Siemens SICAM PAS/PQS is a software from Germany's Siemens with operating systems for energy automation and power quality
Show details on source website{ "@context": { "@vocab": "https://www.variotdbs.pl/ref/VARIoTentry#", "affected_products": { "@id": "https://www.variotdbs.pl/ref/affected_products" }, "configurations": { "@id": "https://www.variotdbs.pl/ref/configurations" }, "credits": { "@id": "https://www.variotdbs.pl/ref/credits" }, "cvss": { "@id": "https://www.variotdbs.pl/ref/cvss/" }, "description": { "@id": "https://www.variotdbs.pl/ref/description/" }, "exploit_availability": { "@id": "https://www.variotdbs.pl/ref/exploit_availability/" }, "external_ids": { "@id": "https://www.variotdbs.pl/ref/external_ids/" }, "iot": { "@id": "https://www.variotdbs.pl/ref/iot/" }, "iot_taxonomy": { "@id": "https://www.variotdbs.pl/ref/iot_taxonomy/" }, "patch": { "@id": "https://www.variotdbs.pl/ref/patch/" }, "problemtype_data": { "@id": "https://www.variotdbs.pl/ref/problemtype_data/" }, "references": { "@id": "https://www.variotdbs.pl/ref/references/" }, "sources": { "@id": "https://www.variotdbs.pl/ref/sources/" }, "sources_release_date": { "@id": "https://www.variotdbs.pl/ref/sources_release_date/" }, "sources_update_date": { "@id": "https://www.variotdbs.pl/ref/sources_update_date/" }, "threat_type": { "@id": "https://www.variotdbs.pl/ref/threat_type/" }, "title": { "@id": "https://www.variotdbs.pl/ref/title/" }, "type": { "@id": "https://www.variotdbs.pl/ref/type/" } }, "@id": "https://www.variotdbs.pl/vuln/VAR-202310-0215", "affected_products": { "@context": { "@vocab": "https://www.variotdbs.pl/ref/affected_products#", "data": { "@container": "@list" }, "sources": { "@container": "@list", "@context": { "@vocab": "https://www.variotdbs.pl/ref/sources#" }, "@id": "https://www.variotdbs.pl/ref/sources" } }, "data": [ { "model": "sicam pas\\/pqs", "scope": "gte", "trust": 1.0, "vendor": "siemens", "version": "8.00" }, { "model": "sicam pas\\/pqs", "scope": "lt", "trust": 1.0, "vendor": "siemens", "version": "8.22" }, { "model": "sicam pas/pqs", "scope": null, "trust": 0.8, "vendor": "\u30b7\u30fc\u30e1\u30f3\u30b9", "version": null }, { "model": "sicam pas/pqs", "scope": "eq", "trust": 0.8, "vendor": "\u30b7\u30fc\u30e1\u30f3\u30b9", "version": "8.00 that\u0027s all 8.22" }, { "model": "sicam pas/pqs", "scope": "eq", "trust": 0.8, "vendor": "\u30b7\u30fc\u30e1\u30f3\u30b9", "version": null }, { "model": "sicam pas/pqs", "scope": "gte", "trust": 0.6, "vendor": "siemens", "version": "v8.00,\u003cv8.22" } ], "sources": [ { "db": "CNVD", "id": "CNVD-2023-75594" }, { "db": "JVNDB", "id": "JVNDB-2023-014550" }, { "db": "NVD", "id": "CVE-2023-38640" } ] }, "configurations": { "@context": { "@vocab": "https://www.variotdbs.pl/ref/configurations#", "children": { "@container": "@list" }, "cpe_match": { "@container": "@list" }, "data": { "@container": "@list" }, "nodes": { "@container": "@list" } }, "data": [ { "CVE_data_version": "4.0", "nodes": [ { "children": [], "cpe_match": [ { "cpe23Uri": "cpe:2.3:a:siemens:sicam_pas\\/pqs:*:*:*:*:*:*:*:*", "cpe_name": [], "versionEndExcluding": "8.22", "versionStartIncluding": "8.00", "vulnerable": true } ], "operator": "OR" } ] } ], "sources": [ { "db": "NVD", "id": "CVE-2023-38640" } ] }, "cve": "CVE-2023-38640", "cvss": { "@context": { "cvssV2": { "@container": "@list", "@context": { "@vocab": "https://www.variotdbs.pl/ref/cvss/cvssV2#" }, "@id": "https://www.variotdbs.pl/ref/cvss/cvssV2" }, "cvssV3": { "@container": "@list", "@context": { "@vocab": "https://www.variotdbs.pl/ref/cvss/cvssV3#" }, "@id": "https://www.variotdbs.pl/ref/cvss/cvssV3/" }, "severity": { "@container": "@list", "@context": { "@vocab": "https://www.variotdbs.pl/cvss/severity#" }, "@id": "https://www.variotdbs.pl/ref/cvss/severity" }, "sources": { "@container": "@list", "@context": { "@vocab": "https://www.variotdbs.pl/ref/sources#" }, "@id": "https://www.variotdbs.pl/ref/sources" } }, "data": [ { "cvssV2": [ { "accessComplexity": "LOW", "accessVector": "LOCAL", "authentication": "NONE", "author": "CNVD", "availabilityImpact": "COMPLETE", "baseScore": 6.1, "confidentialityImpact": "PARTIAL", "exploitabilityScore": 3.9, "id": "CNVD-2023-75594", "impactScore": 8.5, "integrityImpact": "PARTIAL", "severity": "MEDIUM", "trust": 0.6, "vectorString": "AV:L/AC:L/Au:N/C:P/I:P/A:C", "version": "2.0" } ], "cvssV3": [ { "attackComplexity": "LOW", "attackVector": "LOCAL", "author": "NVD", "availabilityImpact": "NONE", "baseScore": 4.4, "baseSeverity": "MEDIUM", "confidentialityImpact": "LOW", "exploitabilityScore": 1.8, "impactScore": 2.5, "integrityImpact": "LOW", "privilegesRequired": "LOW", "scope": "UNCHANGED", "trust": 1.0, "userInteraction": "NONE", "vectorString": "CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:L/I:L/A:N", "version": "3.1" }, { "attackComplexity": "LOW", "attackVector": "LOCAL", "author": "productcert@siemens.com", "availabilityImpact": "HIGH", "baseScore": 6.6, "baseSeverity": "MEDIUM", "confidentialityImpact": "LOW", "exploitabilityScore": 1.8, "impactScore": 4.7, "integrityImpact": "LOW", "privilegesRequired": "LOW", "scope": "UNCHANGED", "trust": 1.0, "userInteraction": "NONE", "vectorString": "CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:L/I:L/A:H", "version": "3.1" }, { "attackComplexity": "Low", "attackVector": "Local", "author": "NVD", "availabilityImpact": "None", "baseScore": 4.4, "baseSeverity": "Medium", "confidentialityImpact": "Low", "exploitabilityScore": null, "id": "CVE-2023-38640", "impactScore": null, "integrityImpact": "Low", "privilegesRequired": "Low", "scope": "Unchanged", "trust": 0.8, "userInteraction": "None", "vectorString": "CVSS:3.0/AV:L/AC:L/PR:L/UI:N/S:U/C:L/I:L/A:N", "version": "3.0" } ], "severity": [ { "author": "NVD", "id": "CVE-2023-38640", "trust": 1.8, "value": "MEDIUM" }, { "author": "productcert@siemens.com", "id": "CVE-2023-38640", "trust": 1.0, "value": "MEDIUM" }, { "author": "CNVD", "id": "CNVD-2023-75594", "trust": 0.6, "value": "MEDIUM" } ] } ], "sources": [ { "db": "CNVD", "id": "CNVD-2023-75594" }, { "db": "JVNDB", "id": "JVNDB-2023-014550" }, { "db": "NVD", "id": "CVE-2023-38640" }, { "db": "NVD", "id": "CVE-2023-38640" } ] }, "description": { "@context": { "@vocab": "https://www.variotdbs.pl/ref/description#", "sources": { "@container": "@list", "@context": { "@vocab": "https://www.variotdbs.pl/ref/sources#" } } }, "data": "A vulnerability has been identified in SICAM PAS/PQS (All versions \u003e= V8.00 \u003c V8.22). The affected application is installed with specific files and folders with insecure permissions. This could allow an authenticated local attacker to read and modify configuration data in the context of the application process. Siemens\u0027 sicam pas/pqs Contains a vulnerability in improper permission assignment for critical resources.Information may be obtained and information may be tampered with. Siemens SICAM PAS/PQS is a software from Germany\u0027s Siemens with operating systems for energy automation and power quality", "sources": [ { "db": "NVD", "id": "CVE-2023-38640" }, { "db": "JVNDB", "id": "JVNDB-2023-014550" }, { "db": "CNVD", "id": "CNVD-2023-75594" } ], "trust": 2.16 }, "external_ids": { "@context": { "@vocab": "https://www.variotdbs.pl/ref/external_ids#", "data": { "@container": "@list" }, "sources": { "@container": "@list", "@context": { "@vocab": "https://www.variotdbs.pl/ref/sources#" } } }, "data": [ { "db": "NVD", "id": "CVE-2023-38640", "trust": 3.2 }, { "db": "SIEMENS", "id": "SSA-035466", "trust": 2.4 }, { "db": "ICS CERT", "id": "ICSA-23-285-06", "trust": 0.8 }, { "db": "JVN", "id": "JVNVU98753493", "trust": 0.8 }, { "db": "JVNDB", "id": "JVNDB-2023-014550", "trust": 0.8 }, { "db": "CNVD", "id": "CNVD-2023-75594", "trust": 0.6 } ], "sources": [ { "db": "CNVD", "id": "CNVD-2023-75594" }, { "db": "JVNDB", "id": "JVNDB-2023-014550" }, { "db": "NVD", "id": "CVE-2023-38640" } ] }, "id": "VAR-202310-0215", "iot": { "@context": { "@vocab": "https://www.variotdbs.pl/ref/iot#", "sources": { "@container": "@list", "@context": { "@vocab": "https://www.variotdbs.pl/ref/sources#" } } }, "data": true, "sources": [ { "db": "CNVD", "id": "CNVD-2023-75594" } ], "trust": 1.1969862999999998 }, "iot_taxonomy": { "@context": { "@vocab": "https://www.variotdbs.pl/ref/iot_taxonomy#", "data": { "@container": "@list" }, "sources": { "@container": "@list", "@context": { "@vocab": "https://www.variotdbs.pl/ref/sources#" } } }, "data": [ { "category": [ "ICS" ], "sub_category": null, "trust": 0.6 } ], "sources": [ { "db": "CNVD", "id": "CNVD-2023-75594" } ] }, "last_update_date": "2024-06-11T22:58:16.395000Z", "patch": { "@context": { "@vocab": "https://www.variotdbs.pl/ref/patch#", "data": { "@container": "@list" }, "sources": { "@container": "@list", "@context": { "@vocab": "https://www.variotdbs.pl/ref/sources#" } } }, "data": [ { "title": "Patch for Siemens SICAM PAS/PQS incorrect permission assignment vulnerability", "trust": 0.6, "url": "https://www.cnvd.org.cn/patchinfo/show/466621" } ], "sources": [ { "db": "CNVD", "id": "CNVD-2023-75594" } ] }, "problemtype_data": { "@context": { "@vocab": "https://www.variotdbs.pl/ref/problemtype_data#", "sources": { "@container": "@list", "@context": { "@vocab": "https://www.variotdbs.pl/ref/sources#" } } }, "data": [ { "problemtype": "CWE-732", "trust": 1.0 }, { "problemtype": "Improper permission assignment for critical resources (CWE-732) [ others ]", "trust": 0.8 } ], "sources": [ { "db": "JVNDB", "id": "JVNDB-2023-014550" }, { "db": "NVD", "id": "CVE-2023-38640" } ] }, "references": { "@context": { "@vocab": "https://www.variotdbs.pl/ref/references#", "data": { "@container": "@list" }, "sources": { "@container": "@list", "@context": { "@vocab": "https://www.variotdbs.pl/ref/sources#" } } }, "data": [ { "trust": 1.8, "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-035466.pdf" }, { "trust": 1.6, "url": "https://cert-portal.siemens.com/productcert/html/ssa-035466.html" }, { "trust": 0.8, "url": "https://jvn.jp/vu/jvnvu98753493/" }, { "trust": 0.8, "url": "https://nvd.nist.gov/vuln/detail/cve-2023-38640" }, { "trust": 0.8, "url": "https://www.cisa.gov/news-events/ics-advisories/icsa-23-285-06" } ], "sources": [ { "db": "CNVD", "id": "CNVD-2023-75594" }, { "db": "JVNDB", "id": "JVNDB-2023-014550" }, { "db": "NVD", "id": "CVE-2023-38640" } ] }, "sources": { "@context": { "@vocab": "https://www.variotdbs.pl/ref/sources#", "data": { "@container": "@list" } }, "data": [ { "db": "CNVD", "id": "CNVD-2023-75594" }, { "db": "JVNDB", "id": "JVNDB-2023-014550" }, { "db": "NVD", "id": "CVE-2023-38640" } ] }, "sources_release_date": { "@context": { "@vocab": "https://www.variotdbs.pl/ref/sources_release_date#", "data": { "@container": "@list" } }, "data": [ { "date": "2023-10-12T00:00:00", "db": "CNVD", "id": "CNVD-2023-75594" }, { "date": "2023-12-25T00:00:00", "db": "JVNDB", "id": "JVNDB-2023-014550" }, { "date": "2023-10-10T11:15:12.063000", "db": "NVD", "id": "CVE-2023-38640" } ] }, "sources_update_date": { "@context": { "@vocab": "https://www.variotdbs.pl/ref/sources_update_date#", "data": { "@container": "@list" } }, "data": [ { "date": "2023-10-11T00:00:00", "db": "CNVD", "id": "CNVD-2023-75594" }, { "date": "2023-12-25T02:38:00", "db": "JVNDB", "id": "JVNDB-2023-014550" }, { "date": "2024-06-11T09:15:13.423000", "db": "NVD", "id": "CVE-2023-38640" } ] }, "title": { "@context": { "@vocab": "https://www.variotdbs.pl/ref/title#", "sources": { "@container": "@list", "@context": { "@vocab": "https://www.variotdbs.pl/ref/sources#" } } }, "data": "Siemens\u0027 \u00a0sicam\u00a0pas/pqs\u00a0 Vulnerability in improper permission assignment for critical resources in", "sources": [ { "db": "JVNDB", "id": "JVNDB-2023-014550" } ], "trust": 0.8 } }
ghsa-vvhw-v3wp-4m8r
Vulnerability from github
A vulnerability has been identified in SICAM PAS/PQS (All versions >= V8.00 < V8.22). The affected application is installed with specific files and folders with insecure permissions. This could allow an authenticated local attacker to read and modify configuration data in the context of the application process.
{ "affected": [], "aliases": [ "CVE-2023-38640" ], "database_specific": { "cwe_ids": [ "CWE-732" ], "github_reviewed": false, "github_reviewed_at": null, "nvd_published_at": "2023-10-10T11:15:12Z", "severity": "MODERATE" }, "details": "A vulnerability has been identified in SICAM PAS/PQS (All versions \u003e= V8.00 \u003c V8.22). The affected application is installed with specific files and folders with insecure permissions. This could allow an authenticated local attacker to read and modify configuration data in the context of the application process.", "id": "GHSA-vvhw-v3wp-4m8r", "modified": "2024-06-11T09:30:53Z", "published": "2023-10-10T12:32:11Z", "references": [ { "type": "ADVISORY", "url": "https://nvd.nist.gov/vuln/detail/CVE-2023-38640" }, { "type": "WEB", "url": "https://cert-portal.siemens.com/productcert/html/ssa-035466.html" }, { "type": "WEB", "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-035466.pdf" } ], "schema_version": "1.4.0", "severity": [ { "score": "CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:L/I:L/A:H", "type": "CVSS_V3" } ] }
icsa-23-285-06
Vulnerability from csaf_cisa
Notes
{ "document": { "acknowledgments": [ { "organization": "Siemens ProductCERT", "summary": "reporting these vulnerabilities to CISA." } ], "category": "csaf_security_advisory", "csaf_version": "2.0", "distribution": { "text": "Disclosure is not limited", "tlp": { "label": "WHITE", "url": "https://us-cert.cisa.gov/tlp/" } }, "lang": "en", "notes": [ { "category": "summary", "text": "SICAM PAS/PQS is affected by insecure permission assignments in application folders that could allow an authenticated local attacker to read and modify configuration data or to escalate privileges. \n\nSiemens has prepared a security patch and recommends to run it on affected systems to fix the permissions of the impacted folders. This security patch will be integral part of the upcoming SICAM PAS/PQS V8.22 and later versions.", "title": "Summary" }, { "category": "general", "text": "Operators of critical power systems (e.g. TSOs or DSOs) worldwide are usually required by regulations to build resilience into the power grids by applying multi-level redundant secondary protection schemes. It is therefore recommended that the operators check whether appropriate resilient protection measures are in place. The risk of cyber incidents impacting the grid\u0027s reliability can thus be minimized by virtue of the grid design.\nSiemens strongly recommends applying the provided security updates using the corresponding tooling and documented procedures made available with the product. If supported by the product, an automated means to apply the security updates across multiple product instances may be used. Siemens strongly recommends prior validation of any security update before being applied, and supervision by trained staff of the update process in the target environment. \nAs a general security measure Siemens strongly recommends to protect network access with appropriate mechanisms (e.g. firewalls, segmentation, VPN). It is advised to configure the environment according to our operational guidelines in order to run the devices in a protected IT environment.\n\nRecommended security guidelines can be found at:\n\nhttps://www.siemens.com/gridsecurity", "title": "General Recommendations" }, { "category": "general", "text": "For further inquiries on security vulnerabilities in Siemens products and solutions, please contact the Siemens ProductCERT: https://www.siemens.com/cert/advisories", "title": "Additional Resources" }, { "category": "legal_disclaimer", "text": "Siemens Security Advisories are subject to the terms and conditions contained in Siemens\u0027 underlying license terms or other applicable agreements previously agreed to with Siemens (hereinafter \"License Terms\"). To the extent applicable to information, software or documentation made available in or through a Siemens Security Advisory, the Terms of Use of Siemens\u0027 Global Website (https://www.siemens.com/terms_of_use, hereinafter \"Terms of Use\"), in particular Sections 8-10 of the Terms of Use, shall apply additionally. In case of conflicts, the License Terms shall prevail over the Terms of Use.", "title": "Terms of Use" }, { "category": "legal_disclaimer", "text": "All information products included in https://us-cert.cisa.gov/ics are provided \"as is\" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see https://us-cert.cisa.gov/tlp/.", "title": "Legal Notice" }, { "category": "other", "text": "This CISA CSAF advisory was converted from Siemens ProductCERT\u0027s CSAF advisory.", "title": "Advisory Conversion Disclaimer" }, { "category": "other", "text": "Multiple", "title": "Critical infrastructure sectors" }, { "category": "other", "text": "Worldwide", "title": "Countries/areas deployed" }, { "category": "other", "text": "Germany", "title": "Company headquarters location" }, { "category": "general", "text": "CISA recommends users take defensive measures to minimize the exploitation risk of this vulnerability.", "title": "Recommended Practices" }, { "category": "general", "text": "Minimize network exposure for all control system devices and/or systems, and ensure they are not accessible from the internet.", "title": "Recommended Practices" }, { "category": "general", "text": "Locate control system networks and remote devices behind firewalls and isolate them from business networks.", "title": "Recommended Practices" }, { "category": "general", "text": "When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most recent version available. Also recognize VPN is only as secure as its connected devices.", "title": "Recommended Practices" }, { "category": "general", "text": "CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.", "title": "Recommended Practices" }, { "category": "general", "text": "CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.", "title": "Recommended Practices" }, { "category": "general", "text": "CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets. Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.", "title": "Recommended Practices" }, { "category": "general", "text": "Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.", "title": "Recommended Practices" } ], "publisher": { "category": "other", "contact_details": "central@cisa.dhs.gov", "name": "CISA", "namespace": "https://www.cisa.gov/" }, "references": [ { "category": "self", "summary": "SSA-035466: Incorrect Permission Assignment in SICAM PAS/PQS - CSAF Version", "url": "https://cert-portal.siemens.com/productcert/csaf/ssa-035466.json" }, { "category": "self", "summary": "SSA-035466: Incorrect Permission Assignment in SICAM PAS/PQS - HTML Version", "url": "https://cert-portal.siemens.com/productcert/html/ssa-035466.html" }, { "category": "self", "summary": "SSA-035466: Incorrect Permission Assignment in SICAM PAS/PQS - PDF Version", "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-035466.pdf" }, { "category": "self", "summary": "SSA-035466: Incorrect Permission Assignment in SICAM PAS/PQS - TXT Version", "url": "https://cert-portal.siemens.com/productcert/txt/ssa-035466.txt" }, { "category": "self", "summary": "ICS Advisory ICSA-23-285-06 JSON", "url": "https://raw.githubusercontent.com/cisagov/CSAF/develop/csaf_files/OT/white/2023/icsa-23-285-06.json" }, { "category": "self", "summary": "ICS Advisory ICSA-23-285-06 - Web Version", "url": "https://www.cisa.gov/news-events/ics-advisories/icsa-23-285-06" }, { "category": "external", "summary": "Recommended Practices", "url": "https://www.cisa.gov/uscert/ics/alerts/ICS-ALERT-10-301-01" }, { "category": "external", "summary": "Recommended Practices", "url": "https://www.cisa.gov/resources-tools/resources/ics-recommended-practices" }, { "category": "external", "summary": "Recommended Practices", "url": "https://www.cisa.gov/topics/industrial-control-systems" }, { "category": "external", "summary": "Recommended Practices", "url": "https://us-cert.cisa.gov/sites/default/files/recommended_practices/NCCIC_ICS-CERT_Defense_in_Depth_2016_S508C.pdf" }, { "category": "external", "summary": "Recommended Practices", "url": "https://www.cisa.gov/sites/default/files/publications/Cybersecurity_Best_Practices_for_Industrial_Control_Systems.pdf" }, { "category": "external", "summary": "Recommended Practices", "url": "https://www.cisa.gov/uscert/ics/tips/ICS-TIP-12-146-01B" } ], "title": "Siemens SICAM PAS/PQS", "tracking": { "current_release_date": "2023-10-10T00:00:00Z", "generator": { "engine": { "name": "CISA CSAF Generator", "version": "1" } }, "id": "ICSA-23-285-06", "initial_release_date": "2023-10-10T00:00:00Z", "revision_history": [ { "date": "2023-10-10T00:00:00Z", "legacy_version": "1.0", "number": "1", "summary": "Publication Date" } ], "status": "final", "version": "1" } }, "product_tree": { "branches": [ { "branches": [ { "branches": [ { "category": "product_version_range", "name": "\u003e=V8.00\u003cV8.22", "product": { "name": "SICAM PAS/PQS", "product_id": "1" } }, { "category": "product_version_range", "name": "\u003e=V8.00\u003cV8.20", "product": { "name": "SICAM PAS/PQS", "product_id": "2" } } ], "category": "product_name", "name": "SICAM PAS/PQS" } ], "category": "vendor", "name": "Siemens" } ] }, "vulnerabilities": [ { "cve": "CVE-2023-38640", "cwe": { "id": "CWE-732", "name": "Incorrect Permission Assignment for Critical Resource" }, "notes": [ { "category": "summary", "text": "The affected application is installed with specific files and folders with insecure permissions. This could allow an authenticated local attacker to read and modify configuration data in the context of the application process.", "title": "Summary" } ], "product_status": { "known_affected": [ "1" ] }, "remediations": [ { "category": "mitigation", "details": "Ensure that only trusted persons have access to the system and avoid the configuration of additional local accounts on the server", "product_ids": [ "1" ] }, { "category": "vendor_fix", "details": "Install the Security Patch (available at \nhttps://support.industry.siemens.com/cs/ww/\nen/view/109824392/), which can be applied to versions V8.00 to V8.21", "product_ids": [ "1" ] }, { "category": "vendor_fix", "details": "Update to V8.22 or later version", "product_ids": [ "1" ] } ], "scores": [ { "cvss_v3": { "baseScore": 6.6, "baseSeverity": "MEDIUM", "vectorString": "CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:L/I:L/A:H/E:P/RL:O/RC:C", "version": "3.1" }, "products": [ "1" ] } ], "title": "CVE-2023-38640" }, { "cve": "CVE-2023-45205", "cwe": { "id": "CWE-732", "name": "Incorrect Permission Assignment for Critical Resource" }, "notes": [ { "category": "summary", "text": "The affected application is installed with specific files and folders with insecure permissions. This could allow an authenticated local attacker to inject arbitrary code and escalate privileges to `NT AUTHORITY/SYSTEM`.", "title": "Summary" } ], "product_status": { "known_affected": [ "2" ] }, "remediations": [ { "category": "mitigation", "details": "Ensure that only trusted persons have access to the system and avoid the configuration of additional local accounts on the server", "product_ids": [ "2" ] }, { "category": "vendor_fix", "details": "Install the Security Patch (available at \nhttps://support.industry.siemens.com/cs/ww/\nen/view/109824392/), which can be applied to versions V8.00 to V8.21", "product_ids": [ "2" ] }, { "category": "vendor_fix", "details": "Update to V8.20 or later version", "product_ids": [ "2" ] } ], "scores": [ { "cvss_v3": { "baseScore": 7.8, "baseSeverity": "HIGH", "vectorString": "CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H/E:P/RL:O/RC:C", "version": "3.1" }, "products": [ "2" ] } ], "title": "CVE-2023-45205" } ] }
gsd-2023-38640
Vulnerability from gsd
{ "GSD": { "alias": "CVE-2023-38640", "id": "GSD-2023-38640" }, "gsd": { "metadata": { "exploitCode": "unknown", "remediation": "unknown", "reportConfidence": "confirmed", "type": "vulnerability" }, "osvSchema": { "aliases": [ "CVE-2023-38640" ], "details": "A vulnerability has been identified in SICAM PAS/PQS (All versions \u003e= V8.00 \u003c V8.22). The affected application is installed with specific files and folders with insecure permissions. This could allow an authenticated local attacker to read and modify configuration data in the context of the application process.", "id": "GSD-2023-38640", "modified": "2023-12-13T01:20:35.639141Z", "schema_version": "1.4.0" } }, "namespaces": { "cve.org": { "CVE_data_meta": { "ASSIGNER": "productcert@siemens.com", "ID": "CVE-2023-38640", "STATE": "PUBLIC" }, "affects": { "vendor": { "vendor_data": [ { "product": { "product_data": [ { "product_name": "SICAM PAS/PQS", "version": { "version_data": [ { "version_affected": "=", "version_value": "All versions \u003e= V8.00 \u003c V8.22" } ] } } ] }, "vendor_name": "Siemens" } ] } }, "data_format": "MITRE", "data_type": "CVE", "data_version": "4.0", "description": { "description_data": [ { "lang": "eng", "value": "A vulnerability has been identified in SICAM PAS/PQS (All versions \u003e= V8.00 \u003c V8.22). The affected application is installed with specific files and folders with insecure permissions. This could allow an authenticated local attacker to read and modify configuration data in the context of the application process." } ] }, "impact": { "cvss": [ { "baseScore": 6.6, "baseSeverity": "MEDIUM", "vectorString": "CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:L/I:L/A:H/E:P/RL:O/RC:C", "version": "3.1" } ] }, "problemtype": { "problemtype_data": [ { "description": [ { "cweId": "CWE-732", "lang": "eng", "value": "CWE-732: Incorrect Permission Assignment for Critical Resource" } ] } ] }, "references": { "reference_data": [ { "name": "https://cert-portal.siemens.com/productcert/pdf/ssa-035466.pdf", "refsource": "MISC", "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-035466.pdf" } ] } }, "nvd.nist.gov": { "configurations": { "CVE_data_version": "4.0", "nodes": [ { "children": [], "cpe_match": [ { "cpe23Uri": "cpe:2.3:a:siemens:sicam_pas\\/pqs:*:*:*:*:*:*:*:*", "cpe_name": [], "versionEndExcluding": "8.22", "versionStartIncluding": "8.00", "vulnerable": true } ], "operator": "OR" } ] }, "cve": { "CVE_data_meta": { "ASSIGNER": "productcert@siemens.com", "ID": "CVE-2023-38640" }, "data_format": "MITRE", "data_type": "CVE", "data_version": "4.0", "description": { "description_data": [ { "lang": "en", "value": "A vulnerability has been identified in SICAM PAS/PQS (All versions \u003e= V8.00 \u003c V8.22). The affected application is installed with specific files and folders with insecure permissions. This could allow an authenticated local attacker to read and modify configuration data in the context of the application process." } ] }, "problemtype": { "problemtype_data": [ { "description": [ { "lang": "en", "value": "CWE-732" } ] } ] }, "references": { "reference_data": [ { "name": "https://cert-portal.siemens.com/productcert/pdf/ssa-035466.pdf", "refsource": "MISC", "tags": [ "Patch", "Vendor Advisory" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-035466.pdf" } ] } }, "impact": { "baseMetricV3": { "cvssV3": { "attackComplexity": "LOW", "attackVector": "LOCAL", "availabilityImpact": "NONE", "baseScore": 4.4, "baseSeverity": "MEDIUM", "confidentialityImpact": "LOW", "integrityImpact": "LOW", "privilegesRequired": "LOW", "scope": "UNCHANGED", "userInteraction": "NONE", "vectorString": "CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:L/I:L/A:N", "version": "3.1" }, "exploitabilityScore": 1.8, "impactScore": 2.5 } }, "lastModifiedDate": "2023-10-14T02:43Z", "publishedDate": "2023-10-10T11:15Z" } } }
wid-sec-w-2023-2603
Vulnerability from csaf_certbund
Notes
{ "document": { "aggregate_severity": { "text": "hoch" }, "category": "csaf_base", "csaf_version": "2.0", "distribution": { "tlp": { "label": "WHITE", "url": "https://www.first.org/tlp/" } }, "lang": "de-DE", "notes": [ { "category": "legal_disclaimer", "text": "Das BSI ist als Anbieter f\u00fcr die eigenen, zur Nutzung bereitgestellten Inhalte nach den allgemeinen Gesetzen verantwortlich. Nutzerinnen und Nutzer sind jedoch daf\u00fcr verantwortlich, die Verwendung und/oder die Umsetzung der mit den Inhalten bereitgestellten Informationen sorgf\u00e4ltig im Einzelfall zu pr\u00fcfen." }, { "category": "description", "text": "Siemens SICAM ist eine Produktfamilie von SCADA-Systemen f\u00fcr den Betrieb von industriellen Prozessen.", "title": "Produktbeschreibung" }, { "category": "summary", "text": "Ein entfernter, anonymer oder lokaler Angreifer kann mehrere Schwachstellen in Siemens SICAM ausnutzen, um beliebigen Code auszuf\u00fchren, Sicherheitsma\u00dfnahmen zu umgehen, vertrauliche Informationen offenzulegen, einen Denial-of-Service-Zustand auszul\u00f6sen, seine Privilegien zu erweitern und Daten zu manipulieren.", "title": "Angriff" }, { "category": "general", "text": "- BIOS/Firmware\n- Hardware Appliance", "title": "Betroffene Betriebssysteme" } ], "publisher": { "category": "other", "contact_details": "csaf-provider@cert-bund.de", "name": "Bundesamt f\u00fcr Sicherheit in der Informationstechnik", "namespace": "https://www.bsi.bund.de" }, "references": [ { "category": "self", "summary": "WID-SEC-W-2023-2603 - CSAF Version", "url": "https://wid.cert-bund.de/.well-known/csaf/white/2023/wid-sec-w-2023-2603.json" }, { "category": "self", "summary": "WID-SEC-2023-2603 - Portal Version", "url": "https://wid.cert-bund.de/portal/wid/securityadvisory?name=WID-SEC-2023-2603" }, { "category": "external", "summary": "Siemens Security Advisory vom 2023-10-09", "url": "https://cert-portal.siemens.com/productcert/html/ssa-285795.html" }, { "category": "external", "summary": "Siemens Security Advisory vom 2023-10-09", "url": "https://cert-portal.siemens.com/productcert/html/ssa-784849.html" }, { "category": "external", "summary": "Siemens Security Advisory vom 2023-10-09", "url": "https://cert-portal.siemens.com/productcert/html/ssa-770890.html" }, { "category": "external", "summary": "Siemens Security Advisory vom 2023-10-09", "url": "https://cert-portal.siemens.com/productcert/html/ssa-134651.html" }, { "category": "external", "summary": "Siemens Security Advisory vom 2023-10-09", "url": "https://cert-portal.siemens.com/productcert/html/ssa-035466.html" } ], "source_lang": "en-US", "title": "Siemens SICAM: Mehrere Schwachstellen", "tracking": { "current_release_date": "2023-10-09T22:00:00.000+00:00", "generator": { "date": "2024-02-15T17:47:17.112+00:00", "engine": { "name": "BSI-WID", "version": "1.3.0" } }, "id": "WID-SEC-W-2023-2603", "initial_release_date": "2023-10-09T22:00:00.000+00:00", "revision_history": [ { "date": "2023-10-09T22:00:00.000+00:00", "number": "1", "summary": "Initiale Fassung" } ], "status": "final", "version": "1" } }, "product_tree": { "branches": [ { "branches": [ { "branches": [ { "category": "product_name", "name": "Siemens SICAM A8000", "product": { "name": "Siemens SICAM A8000", "product_id": "T024199", "product_identification_helper": { "cpe": "cpe:/h:siemens:sicam:a8000" } } }, { "category": "product_name", "name": "Siemens SICAM PAS", "product": { "name": "Siemens SICAM PAS", "product_id": "T030347", "product_identification_helper": { "cpe": "cpe:/h:siemens:sicam:pas" } } }, { "category": "product_name", "name": "Siemens SICAM PQS", "product": { "name": "Siemens SICAM PQS", "product_id": "T030348", "product_identification_helper": { "cpe": "cpe:/h:siemens:sicam:pqs" } } }, { "category": "product_name", "name": "Siemens SICAM CP", "product": { "name": "Siemens SICAM CP", "product_id": "T030349", "product_identification_helper": { "cpe": "cpe:/h:siemens:sicam:cp" } } }, { "category": "product_name", "name": "Siemens SICAM HMI Comfort Outdoor Panels", "product": { "name": "Siemens SICAM HMI Comfort Outdoor Panels", "product_id": "T030350", "product_identification_helper": { "cpe": "cpe:/h:siemens:sicam:hmi_comfort_outdoor_panels" } } }, { "category": "product_name", "name": "Siemens SICAM HMI KTP Mobile Panels", "product": { "name": "Siemens SICAM HMI KTP Mobile Panels", "product_id": "T030351", "product_identification_helper": { "cpe": "cpe:/h:siemens:sicam:hmi_ktp_mobile_panels" } } }, { "category": "product_name", "name": "Siemens SICAM NET PC Software", "product": { "name": "Siemens SICAM NET PC Software", "product_id": "T030352", "product_identification_helper": { "cpe": "cpe:/h:siemens:sicam:net_pc_software" } } } ], "category": "product_name", "name": "SICAM" } ], "category": "vendor", "name": "Siemens" } ] }, "vulnerabilities": [ { "cve": "CVE-2023-45205", "notes": [ { "category": "description", "text": "Es existieren mehrere Schwachstellen in verschiedenen Siemens SICAM Ger\u00e4ten. Die Fehler bestehen unter anderem aufgrund von unsicheren Berechtigungen, einer hartkodierten ID, einem Directory Traversal und einem unzureichenden Control Mapping. Ein Angreifer kann diese Schwachstellen ausnutzen, um beliebigen Code auszuf\u00fchren, Sicherheitsma\u00dfnahmen zu umgehen, vertrauliche Informationen offenzulegen, einen Denial-of-Service-Zustand auszul\u00f6sen, seine Privilegien zu erweitern und Daten zu manipulieren. Die erfolgreiche Ausnutzung einiger dieser Schwachstellen erfordert eine Benutzerinteraktion oder erh\u00f6hte Privilegien." } ], "product_status": { "known_affected": [ "T030347", "T030349", "T030348", "T030350", "T024199", "T030352", "T030351" ] }, "release_date": "2023-10-09T22:00:00Z", "title": "CVE-2023-45205" }, { "cve": "CVE-2023-42796", "notes": [ { "category": "description", "text": "Es existieren mehrere Schwachstellen in verschiedenen Siemens SICAM Ger\u00e4ten. Die Fehler bestehen unter anderem aufgrund von unsicheren Berechtigungen, einer hartkodierten ID, einem Directory Traversal und einem unzureichenden Control Mapping. Ein Angreifer kann diese Schwachstellen ausnutzen, um beliebigen Code auszuf\u00fchren, Sicherheitsma\u00dfnahmen zu umgehen, vertrauliche Informationen offenzulegen, einen Denial-of-Service-Zustand auszul\u00f6sen, seine Privilegien zu erweitern und Daten zu manipulieren. Die erfolgreiche Ausnutzung einiger dieser Schwachstellen erfordert eine Benutzerinteraktion oder erh\u00f6hte Privilegien." } ], "product_status": { "known_affected": [ "T030347", "T030349", "T030348", "T030350", "T024199", "T030352", "T030351" ] }, "release_date": "2023-10-09T22:00:00Z", "title": "CVE-2023-42796" }, { "cve": "CVE-2023-38640", "notes": [ { "category": "description", "text": "Es existieren mehrere Schwachstellen in verschiedenen Siemens SICAM Ger\u00e4ten. Die Fehler bestehen unter anderem aufgrund von unsicheren Berechtigungen, einer hartkodierten ID, einem Directory Traversal und einem unzureichenden Control Mapping. Ein Angreifer kann diese Schwachstellen ausnutzen, um beliebigen Code auszuf\u00fchren, Sicherheitsma\u00dfnahmen zu umgehen, vertrauliche Informationen offenzulegen, einen Denial-of-Service-Zustand auszul\u00f6sen, seine Privilegien zu erweitern und Daten zu manipulieren. Die erfolgreiche Ausnutzung einiger dieser Schwachstellen erfordert eine Benutzerinteraktion oder erh\u00f6hte Privilegien." } ], "product_status": { "known_affected": [ "T030347", "T030349", "T030348", "T030350", "T024199", "T030352", "T030351" ] }, "release_date": "2023-10-09T22:00:00Z", "title": "CVE-2023-38640" }, { "cve": "CVE-2023-37195", "notes": [ { "category": "description", "text": "Es existieren mehrere Schwachstellen in verschiedenen Siemens SICAM Ger\u00e4ten. Die Fehler bestehen unter anderem aufgrund von unsicheren Berechtigungen, einer hartkodierten ID, einem Directory Traversal und einem unzureichenden Control Mapping. Ein Angreifer kann diese Schwachstellen ausnutzen, um beliebigen Code auszuf\u00fchren, Sicherheitsma\u00dfnahmen zu umgehen, vertrauliche Informationen offenzulegen, einen Denial-of-Service-Zustand auszul\u00f6sen, seine Privilegien zu erweitern und Daten zu manipulieren. Die erfolgreiche Ausnutzung einiger dieser Schwachstellen erfordert eine Benutzerinteraktion oder erh\u00f6hte Privilegien." } ], "product_status": { "known_affected": [ "T030347", "T030349", "T030348", "T030350", "T024199", "T030352", "T030351" ] }, "release_date": "2023-10-09T22:00:00Z", "title": "CVE-2023-37195" }, { "cve": "CVE-2023-37194", "notes": [ { "category": "description", "text": "Es existieren mehrere Schwachstellen in verschiedenen Siemens SICAM Ger\u00e4ten. Die Fehler bestehen unter anderem aufgrund von unsicheren Berechtigungen, einer hartkodierten ID, einem Directory Traversal und einem unzureichenden Control Mapping. Ein Angreifer kann diese Schwachstellen ausnutzen, um beliebigen Code auszuf\u00fchren, Sicherheitsma\u00dfnahmen zu umgehen, vertrauliche Informationen offenzulegen, einen Denial-of-Service-Zustand auszul\u00f6sen, seine Privilegien zu erweitern und Daten zu manipulieren. Die erfolgreiche Ausnutzung einiger dieser Schwachstellen erfordert eine Benutzerinteraktion oder erh\u00f6hte Privilegien." } ], "product_status": { "known_affected": [ "T030347", "T030349", "T030348", "T030350", "T024199", "T030352", "T030351" ] }, "release_date": "2023-10-09T22:00:00Z", "title": "CVE-2023-37194" }, { "cve": "CVE-2023-36380", "notes": [ { "category": "description", "text": "Es existieren mehrere Schwachstellen in verschiedenen Siemens SICAM Ger\u00e4ten. Die Fehler bestehen unter anderem aufgrund von unsicheren Berechtigungen, einer hartkodierten ID, einem Directory Traversal und einem unzureichenden Control Mapping. Ein Angreifer kann diese Schwachstellen ausnutzen, um beliebigen Code auszuf\u00fchren, Sicherheitsma\u00dfnahmen zu umgehen, vertrauliche Informationen offenzulegen, einen Denial-of-Service-Zustand auszul\u00f6sen, seine Privilegien zu erweitern und Daten zu manipulieren. Die erfolgreiche Ausnutzung einiger dieser Schwachstellen erfordert eine Benutzerinteraktion oder erh\u00f6hte Privilegien." } ], "product_status": { "known_affected": [ "T030347", "T030349", "T030348", "T030350", "T024199", "T030352", "T030351" ] }, "release_date": "2023-10-09T22:00:00Z", "title": "CVE-2023-36380" }, { "cve": "CVE-2021-45117", "notes": [ { "category": "description", "text": "Es existieren mehrere Schwachstellen in verschiedenen Siemens SICAM Ger\u00e4ten. Die Fehler bestehen unter anderem aufgrund von unsicheren Berechtigungen, einer hartkodierten ID, einem Directory Traversal und einem unzureichenden Control Mapping. Ein Angreifer kann diese Schwachstellen ausnutzen, um beliebigen Code auszuf\u00fchren, Sicherheitsma\u00dfnahmen zu umgehen, vertrauliche Informationen offenzulegen, einen Denial-of-Service-Zustand auszul\u00f6sen, seine Privilegien zu erweitern und Daten zu manipulieren. Die erfolgreiche Ausnutzung einiger dieser Schwachstellen erfordert eine Benutzerinteraktion oder erh\u00f6hte Privilegien." } ], "product_status": { "known_affected": [ "T030347", "T030349", "T030348", "T030350", "T024199", "T030352", "T030351" ] }, "release_date": "2023-10-09T22:00:00Z", "title": "CVE-2021-45117" } ] }
- Seen: The vulnerability was mentioned, discussed, or seen somewhere by the user.
- Confirmed: The vulnerability is confirmed from an analyst perspective.
- Exploited: This vulnerability was exploited and seen by the user reporting the sighting.
- Patched: This vulnerability was successfully patched by the user reporting the sighting.
- Not exploited: This vulnerability was not exploited or seen by the user reporting the sighting.
- Not confirmed: The user expresses doubt about the veracity of the vulnerability.
- Not patched: This vulnerability was not successfully patched by the user reporting the sighting.