CVE-2025-55038 (GCVE-0-2025-55038)

Vulnerability from cvelistv5 – Published: 2025-09-23 22:24 – Updated: 2025-09-24 14:07
VLAI?
Summary
An authorization bypass vulnerability has been discovered in the Click Plus C2-03CPU2 device firmware version 3.60. Through the KOPR protocol utilized by the Remote PLC application, authenticated users with low-level access permissions can exploit this vulnerability to read and modify PLC variables beyond their intended authorization level.
CWE
Assigner
Credits
Luca Borzacchiello and Diego Zaffaroni of Nozomi Networks reported these vulnerabilities to Automation Direct.
Show details on NVD website

{
  "containers": {
    "adp": [
      {
        "metrics": [
          {
            "other": {
              "content": {
                "id": "CVE-2025-55038",
                "options": [
                  {
                    "Exploitation": "none"
                  },
                  {
                    "Automatable": "no"
                  },
                  {
                    "Technical Impact": "total"
                  }
                ],
                "role": "CISA Coordinator",
                "timestamp": "2025-09-24T14:06:10.499891Z",
                "version": "2.0.3"
              },
              "type": "ssvc"
            }
          }
        ],
        "providerMetadata": {
          "dateUpdated": "2025-09-24T14:07:38.232Z",
          "orgId": "134c704f-9b21-4f2e-91b3-4a467353bcc0",
          "shortName": "CISA-ADP"
        },
        "title": "CISA ADP Vulnrichment"
      }
    ],
    "cna": {
      "affected": [
        {
          "defaultStatus": "unaffected",
          "product": "CLICK PLUS C0-0x CPU firmware",
          "vendor": "AutomationDirect",
          "versions": [
            {
              "lessThan": "v3.71",
              "status": "affected",
              "version": "0",
              "versionType": "custom"
            }
          ]
        },
        {
          "defaultStatus": "unaffected",
          "product": "CLICK PLUS C0-1x CPU firmware",
          "vendor": "AutomationDirect",
          "versions": [
            {
              "lessThan": "v3.71",
              "status": "affected",
              "version": "0",
              "versionType": "custom"
            }
          ]
        },
        {
          "defaultStatus": "unaffected",
          "product": "CLICK PLUS C2-x CPU firmware",
          "vendor": "AutomationDirect",
          "versions": [
            {
              "lessThan": "v3.71",
              "status": "affected",
              "version": "0",
              "versionType": "custom"
            }
          ]
        }
      ],
      "credits": [
        {
          "lang": "en",
          "type": "finder",
          "value": "Luca Borzacchiello and Diego Zaffaroni of Nozomi Networks reported these vulnerabilities to Automation Direct."
        }
      ],
      "datePublic": "2025-09-23T16:00:00.000Z",
      "descriptions": [
        {
          "lang": "en",
          "supportingMedia": [
            {
              "base64": false,
              "type": "text/html",
              "value": "\u003cspan style=\"background-color: rgb(255, 255, 255);\"\u003eAn authorization bypass vulnerability has been discovered in the Click Plus C2-03CPU2 device firmware version 3.60. Through the KOPR protocol utilized by the Remote PLC application, authenticated users with low-level access permissions can exploit this vulnerability to read and modify PLC variables beyond their intended authorization level.\u003c/span\u003e"
            }
          ],
          "value": "An authorization bypass vulnerability has been discovered in the Click Plus C2-03CPU2 device firmware version 3.60. Through the KOPR protocol utilized by the Remote PLC application, authenticated users with low-level access permissions can exploit this vulnerability to read and modify PLC variables beyond their intended authorization level."
        }
      ],
      "metrics": [
        {
          "cvssV4_0": {
            "Automatable": "NOT_DEFINED",
            "Recovery": "NOT_DEFINED",
            "Safety": "NOT_DEFINED",
            "attackComplexity": "HIGH",
            "attackRequirements": "NONE",
            "attackVector": "NETWORK",
            "baseScore": 7.6,
            "baseSeverity": "HIGH",
            "privilegesRequired": "LOW",
            "providerUrgency": "NOT_DEFINED",
            "subAvailabilityImpact": "NONE",
            "subConfidentialityImpact": "NONE",
            "subIntegrityImpact": "NONE",
            "userInteraction": "NONE",
            "valueDensity": "NOT_DEFINED",
            "vectorString": "CVSS:4.0/AV:N/AC:H/AT:N/PR:L/UI:N/VC:H/VI:H/VA:N/SC:N/SI:N/SA:N",
            "version": "4.0",
            "vulnAvailabilityImpact": "NONE",
            "vulnConfidentialityImpact": "HIGH",
            "vulnIntegrityImpact": "HIGH",
            "vulnerabilityResponseEffort": "NOT_DEFINED"
          },
          "format": "CVSS",
          "scenarios": [
            {
              "lang": "en",
              "value": "GENERAL"
            }
          ]
        },
        {
          "cvssV3_1": {
            "attackComplexity": "HIGH",
            "attackVector": "NETWORK",
            "availabilityImpact": "NONE",
            "baseScore": 6.8,
            "baseSeverity": "MEDIUM",
            "confidentialityImpact": "HIGH",
            "integrityImpact": "HIGH",
            "privilegesRequired": "LOW",
            "scope": "UNCHANGED",
            "userInteraction": "NONE",
            "vectorString": "CVSS:3.1/AV:N/AC:H/PR:L/UI:N/S:U/C:H/I:H/A:N",
            "version": "3.1"
          },
          "format": "CVSS",
          "scenarios": [
            {
              "lang": "en",
              "value": "GENERAL"
            }
          ]
        }
      ],
      "problemTypes": [
        {
          "descriptions": [
            {
              "cweId": "CWE-862",
              "description": "CWE-862 Missing Authorization",
              "lang": "en",
              "type": "CWE"
            }
          ]
        }
      ],
      "providerMetadata": {
        "dateUpdated": "2025-09-23T22:24:28.676Z",
        "orgId": "7d14cffa-0d7d-4270-9dc0-52cabd5a23a6",
        "shortName": "icscert"
      },
      "references": [
        {
          "url": "https://www.cisa.gov/news-events/ics-advisories/icsa-25-266-01"
        },
        {
          "url": "https://www.automationdirect.com/support/software-downloads"
        }
      ],
      "solutions": [
        {
          "lang": "en",
          "supportingMedia": [
            {
              "base64": false,
              "type": "text/html",
              "value": "\u003cp\u003eAutomationDirect recommends that users update CLICK PLUS and firmware to \u003ca target=\"_blank\" rel=\"nofollow\" href=\"https://www.automationdirect.com/support/software-downloads\"\u003eV3.80.\u003c/a\u003e\u003c/p\u003e\u003cp\u003eIf the update cannot be applied right away, the following compensating controls are recommended until the upgrade can be performed:\u003c/p\u003e\u003cul\u003e\u003cli\u003eNetwork Isolation \u2013 Disconnect the CLICK PLUS PLC from external networks (e.g., the internet or corporate LAN) to reduce exposure.\u003c/li\u003e\u003cli\u003eSecure Communications \u2013 Use only trusted, dedicated internal networks or air-gapped systems for device communication.\u003c/li\u003e\u003cli\u003eAccess Control \u2013 Restrict both physical and logical access to authorized personnel only.\u003c/li\u003e\u003cli\u003eApplication Whitelisting \u2013 Configure whitelisting so that only trusted, pre-approved applications are allowed to run. Block any unauthorized software.\u003c/li\u003e\u003cli\u003eEndpoint Protection \u2013 Use antivirus or EDR tools and configure host-based firewalls to block unauthorized access attempts.\u003c/li\u003e\u003cli\u003eLogging \u0026amp; Monitoring \u2013 Enable and regularly review system logs to detect suspicious or unauthorized activity.\u003c/li\u003e\u003cli\u003eBackup \u0026amp; Recovery \u2013 Maintain secure, tested backups of the PLC and its configurations to minimize downtime in case of an incident.\u003c/li\u003e\u003cli\u003eOngoing Risk Assessment \u2013 Continuously evaluate risks associated with running outdated firmware and adjust compensating measures accordingly.\u003c/li\u003e\u003c/ul\u003e\n\n\u003cbr\u003e"
            }
          ],
          "value": "AutomationDirect recommends that users update CLICK PLUS and firmware to  V3.80. https://www.automationdirect.com/support/software-downloads \n\nIf the update cannot be applied right away, the following compensating controls are recommended until the upgrade can be performed:\n\n  *  Network Isolation \u2013 Disconnect the CLICK PLUS PLC from external networks (e.g., the internet or corporate LAN) to reduce exposure.\n  *  Secure Communications \u2013 Use only trusted, dedicated internal networks or air-gapped systems for device communication.\n  *  Access Control \u2013 Restrict both physical and logical access to authorized personnel only.\n  *  Application Whitelisting \u2013 Configure whitelisting so that only trusted, pre-approved applications are allowed to run. Block any unauthorized software.\n  *  Endpoint Protection \u2013 Use antivirus or EDR tools and configure host-based firewalls to block unauthorized access attempts.\n  *  Logging \u0026 Monitoring \u2013 Enable and regularly review system logs to detect suspicious or unauthorized activity.\n  *  Backup \u0026 Recovery \u2013 Maintain secure, tested backups of the PLC and its configurations to minimize downtime in case of an incident.\n  *  Ongoing Risk Assessment \u2013 Continuously evaluate risks associated with running outdated firmware and adjust compensating measures accordingly."
        }
      ],
      "source": {
        "advisory": "ICSA-25-266-01",
        "discovery": "EXTERNAL"
      },
      "title": "AutomationDirect CLICK PLUS Missing Authorization",
      "x_generator": {
        "engine": "Vulnogram 0.2.0"
      }
    }
  },
  "cveMetadata": {
    "assignerOrgId": "7d14cffa-0d7d-4270-9dc0-52cabd5a23a6",
    "assignerShortName": "icscert",
    "cveId": "CVE-2025-55038",
    "datePublished": "2025-09-23T22:24:28.676Z",
    "dateReserved": "2025-09-16T20:09:26.660Z",
    "dateUpdated": "2025-09-24T14:07:38.232Z",
    "state": "PUBLISHED"
  },
  "dataType": "CVE_RECORD",
  "dataVersion": "5.1",
  "vulnerability-lookup:meta": {
    "nvd": "{\"cve\":{\"id\":\"CVE-2025-55038\",\"sourceIdentifier\":\"ics-cert@hq.dhs.gov\",\"published\":\"2025-09-23T23:15:30.497\",\"lastModified\":\"2025-09-24T18:11:24.520\",\"vulnStatus\":\"Awaiting Analysis\",\"cveTags\":[],\"descriptions\":[{\"lang\":\"en\",\"value\":\"An authorization bypass vulnerability has been discovered in the Click Plus C2-03CPU2 device firmware version 3.60. Through the KOPR protocol utilized by the Remote PLC application, authenticated users with low-level access permissions can exploit this vulnerability to read and modify PLC variables beyond their intended authorization level.\"}],\"metrics\":{\"cvssMetricV40\":[{\"source\":\"ics-cert@hq.dhs.gov\",\"type\":\"Secondary\",\"cvssData\":{\"version\":\"4.0\",\"vectorString\":\"CVSS:4.0/AV:N/AC:H/AT:N/PR:L/UI:N/VC:H/VI:H/VA:N/SC:N/SI:N/SA:N/E:X/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:X\",\"baseScore\":7.6,\"baseSeverity\":\"HIGH\",\"attackVector\":\"NETWORK\",\"attackComplexity\":\"HIGH\",\"attackRequirements\":\"NONE\",\"privilegesRequired\":\"LOW\",\"userInteraction\":\"NONE\",\"vulnConfidentialityImpact\":\"HIGH\",\"vulnIntegrityImpact\":\"HIGH\",\"vulnAvailabilityImpact\":\"NONE\",\"subConfidentialityImpact\":\"NONE\",\"subIntegrityImpact\":\"NONE\",\"subAvailabilityImpact\":\"NONE\",\"exploitMaturity\":\"NOT_DEFINED\",\"confidentialityRequirement\":\"NOT_DEFINED\",\"integrityRequirement\":\"NOT_DEFINED\",\"availabilityRequirement\":\"NOT_DEFINED\",\"modifiedAttackVector\":\"NOT_DEFINED\",\"modifiedAttackComplexity\":\"NOT_DEFINED\",\"modifiedAttackRequirements\":\"NOT_DEFINED\",\"modifiedPrivilegesRequired\":\"NOT_DEFINED\",\"modifiedUserInteraction\":\"NOT_DEFINED\",\"modifiedVulnConfidentialityImpact\":\"NOT_DEFINED\",\"modifiedVulnIntegrityImpact\":\"NOT_DEFINED\",\"modifiedVulnAvailabilityImpact\":\"NOT_DEFINED\",\"modifiedSubConfidentialityImpact\":\"NOT_DEFINED\",\"modifiedSubIntegrityImpact\":\"NOT_DEFINED\",\"modifiedSubAvailabilityImpact\":\"NOT_DEFINED\",\"Safety\":\"NOT_DEFINED\",\"Automatable\":\"NOT_DEFINED\",\"Recovery\":\"NOT_DEFINED\",\"valueDensity\":\"NOT_DEFINED\",\"vulnerabilityResponseEffort\":\"NOT_DEFINED\",\"providerUrgency\":\"NOT_DEFINED\"}}],\"cvssMetricV31\":[{\"source\":\"ics-cert@hq.dhs.gov\",\"type\":\"Secondary\",\"cvssData\":{\"version\":\"3.1\",\"vectorString\":\"CVSS:3.1/AV:N/AC:H/PR:L/UI:N/S:U/C:H/I:H/A:N\",\"baseScore\":6.8,\"baseSeverity\":\"MEDIUM\",\"attackVector\":\"NETWORK\",\"attackComplexity\":\"HIGH\",\"privilegesRequired\":\"LOW\",\"userInteraction\":\"NONE\",\"scope\":\"UNCHANGED\",\"confidentialityImpact\":\"HIGH\",\"integrityImpact\":\"HIGH\",\"availabilityImpact\":\"NONE\"},\"exploitabilityScore\":1.6,\"impactScore\":5.2}]},\"weaknesses\":[{\"source\":\"ics-cert@hq.dhs.gov\",\"type\":\"Primary\",\"description\":[{\"lang\":\"en\",\"value\":\"CWE-862\"}]}],\"references\":[{\"url\":\"https://www.automationdirect.com/support/software-downloads\",\"source\":\"ics-cert@hq.dhs.gov\"},{\"url\":\"https://www.cisa.gov/news-events/ics-advisories/icsa-25-266-01\",\"source\":\"ics-cert@hq.dhs.gov\"}]}}",
    "vulnrichment": {
      "containers": "{\"adp\": [{\"title\": \"CISA ADP Vulnrichment\", \"metrics\": [{\"other\": {\"type\": \"ssvc\", \"content\": {\"id\": \"CVE-2025-55038\", \"role\": \"CISA Coordinator\", \"options\": [{\"Exploitation\": \"none\"}, {\"Automatable\": \"no\"}, {\"Technical Impact\": \"total\"}], \"version\": \"2.0.3\", \"timestamp\": \"2025-09-24T14:06:10.499891Z\"}}}], \"providerMetadata\": {\"orgId\": \"134c704f-9b21-4f2e-91b3-4a467353bcc0\", \"shortName\": \"CISA-ADP\", \"dateUpdated\": \"2025-09-24T14:07:33.432Z\"}}], \"cna\": {\"title\": \"AutomationDirect CLICK PLUS Missing Authorization\", \"source\": {\"advisory\": \"ICSA-25-266-01\", \"discovery\": \"EXTERNAL\"}, \"credits\": [{\"lang\": \"en\", \"type\": \"finder\", \"value\": \"Luca Borzacchiello and Diego Zaffaroni of Nozomi Networks reported these vulnerabilities to Automation Direct.\"}], \"metrics\": [{\"format\": \"CVSS\", \"cvssV4_0\": {\"Safety\": \"NOT_DEFINED\", \"version\": \"4.0\", \"Recovery\": \"NOT_DEFINED\", \"baseScore\": 7.6, \"Automatable\": \"NOT_DEFINED\", \"attackVector\": \"NETWORK\", \"baseSeverity\": \"HIGH\", \"valueDensity\": \"NOT_DEFINED\", \"vectorString\": \"CVSS:4.0/AV:N/AC:H/AT:N/PR:L/UI:N/VC:H/VI:H/VA:N/SC:N/SI:N/SA:N\", \"providerUrgency\": \"NOT_DEFINED\", \"userInteraction\": \"NONE\", \"attackComplexity\": \"HIGH\", \"attackRequirements\": \"NONE\", \"privilegesRequired\": \"LOW\", \"subIntegrityImpact\": \"NONE\", \"vulnIntegrityImpact\": \"HIGH\", \"subAvailabilityImpact\": \"NONE\", \"vulnAvailabilityImpact\": \"NONE\", \"subConfidentialityImpact\": \"NONE\", \"vulnConfidentialityImpact\": \"HIGH\", \"vulnerabilityResponseEffort\": \"NOT_DEFINED\"}, \"scenarios\": [{\"lang\": \"en\", \"value\": \"GENERAL\"}]}, {\"format\": \"CVSS\", \"cvssV3_1\": {\"scope\": \"UNCHANGED\", \"version\": \"3.1\", \"baseScore\": 6.8, \"attackVector\": \"NETWORK\", \"baseSeverity\": \"MEDIUM\", \"vectorString\": \"CVSS:3.1/AV:N/AC:H/PR:L/UI:N/S:U/C:H/I:H/A:N\", \"integrityImpact\": \"HIGH\", \"userInteraction\": \"NONE\", \"attackComplexity\": \"HIGH\", \"availabilityImpact\": \"NONE\", \"privilegesRequired\": \"LOW\", \"confidentialityImpact\": \"HIGH\"}, \"scenarios\": [{\"lang\": \"en\", \"value\": \"GENERAL\"}]}], \"affected\": [{\"vendor\": \"AutomationDirect\", \"product\": \"CLICK PLUS C0-0x CPU firmware\", \"versions\": [{\"status\": \"affected\", \"version\": \"0\", \"lessThan\": \"v3.71\", \"versionType\": \"custom\"}], \"defaultStatus\": \"unaffected\"}, {\"vendor\": \"AutomationDirect\", \"product\": \"CLICK PLUS C0-1x CPU firmware\", \"versions\": [{\"status\": \"affected\", \"version\": \"0\", \"lessThan\": \"v3.71\", \"versionType\": \"custom\"}], \"defaultStatus\": \"unaffected\"}, {\"vendor\": \"AutomationDirect\", \"product\": \"CLICK PLUS C2-x CPU firmware\", \"versions\": [{\"status\": \"affected\", \"version\": \"0\", \"lessThan\": \"v3.71\", \"versionType\": \"custom\"}], \"defaultStatus\": \"unaffected\"}], \"solutions\": [{\"lang\": \"en\", \"value\": \"AutomationDirect recommends that users update CLICK PLUS and firmware to  V3.80. https://www.automationdirect.com/support/software-downloads \\n\\nIf the update cannot be applied right away, the following compensating controls are recommended until the upgrade can be performed:\\n\\n  *  Network Isolation \\u2013 Disconnect the CLICK PLUS PLC from external networks (e.g., the internet or corporate LAN) to reduce exposure.\\n  *  Secure Communications \\u2013 Use only trusted, dedicated internal networks or air-gapped systems for device communication.\\n  *  Access Control \\u2013 Restrict both physical and logical access to authorized personnel only.\\n  *  Application Whitelisting \\u2013 Configure whitelisting so that only trusted, pre-approved applications are allowed to run. Block any unauthorized software.\\n  *  Endpoint Protection \\u2013 Use antivirus or EDR tools and configure host-based firewalls to block unauthorized access attempts.\\n  *  Logging \u0026 Monitoring \\u2013 Enable and regularly review system logs to detect suspicious or unauthorized activity.\\n  *  Backup \u0026 Recovery \\u2013 Maintain secure, tested backups of the PLC and its configurations to minimize downtime in case of an incident.\\n  *  Ongoing Risk Assessment \\u2013 Continuously evaluate risks associated with running outdated firmware and adjust compensating measures accordingly.\", \"supportingMedia\": [{\"type\": \"text/html\", \"value\": \"\u003cp\u003eAutomationDirect recommends that users update CLICK PLUS and firmware to \u003ca target=\\\"_blank\\\" rel=\\\"nofollow\\\" href=\\\"https://www.automationdirect.com/support/software-downloads\\\"\u003eV3.80.\u003c/a\u003e\u003c/p\u003e\u003cp\u003eIf the update cannot be applied right away, the following compensating controls are recommended until the upgrade can be performed:\u003c/p\u003e\u003cul\u003e\u003cli\u003eNetwork Isolation \\u2013 Disconnect the CLICK PLUS PLC from external networks (e.g., the internet or corporate LAN) to reduce exposure.\u003c/li\u003e\u003cli\u003eSecure Communications \\u2013 Use only trusted, dedicated internal networks or air-gapped systems for device communication.\u003c/li\u003e\u003cli\u003eAccess Control \\u2013 Restrict both physical and logical access to authorized personnel only.\u003c/li\u003e\u003cli\u003eApplication Whitelisting \\u2013 Configure whitelisting so that only trusted, pre-approved applications are allowed to run. Block any unauthorized software.\u003c/li\u003e\u003cli\u003eEndpoint Protection \\u2013 Use antivirus or EDR tools and configure host-based firewalls to block unauthorized access attempts.\u003c/li\u003e\u003cli\u003eLogging \u0026amp; Monitoring \\u2013 Enable and regularly review system logs to detect suspicious or unauthorized activity.\u003c/li\u003e\u003cli\u003eBackup \u0026amp; Recovery \\u2013 Maintain secure, tested backups of the PLC and its configurations to minimize downtime in case of an incident.\u003c/li\u003e\u003cli\u003eOngoing Risk Assessment \\u2013 Continuously evaluate risks associated with running outdated firmware and adjust compensating measures accordingly.\u003c/li\u003e\u003c/ul\u003e\\n\\n\u003cbr\u003e\", \"base64\": false}]}], \"datePublic\": \"2025-09-23T16:00:00.000Z\", \"references\": [{\"url\": \"https://www.cisa.gov/news-events/ics-advisories/icsa-25-266-01\"}, {\"url\": \"https://www.automationdirect.com/support/software-downloads\"}], \"x_generator\": {\"engine\": \"Vulnogram 0.2.0\"}, \"descriptions\": [{\"lang\": \"en\", \"value\": \"An authorization bypass vulnerability has been discovered in the Click Plus C2-03CPU2 device firmware version 3.60. Through the KOPR protocol utilized by the Remote PLC application, authenticated users with low-level access permissions can exploit this vulnerability to read and modify PLC variables beyond their intended authorization level.\", \"supportingMedia\": [{\"type\": \"text/html\", \"value\": \"\u003cspan style=\\\"background-color: rgb(255, 255, 255);\\\"\u003eAn authorization bypass vulnerability has been discovered in the Click Plus C2-03CPU2 device firmware version 3.60. Through the KOPR protocol utilized by the Remote PLC application, authenticated users with low-level access permissions can exploit this vulnerability to read and modify PLC variables beyond their intended authorization level.\u003c/span\u003e\", \"base64\": false}]}], \"problemTypes\": [{\"descriptions\": [{\"lang\": \"en\", \"type\": \"CWE\", \"cweId\": \"CWE-862\", \"description\": \"CWE-862 Missing Authorization\"}]}], \"providerMetadata\": {\"orgId\": \"7d14cffa-0d7d-4270-9dc0-52cabd5a23a6\", \"shortName\": \"icscert\", \"dateUpdated\": \"2025-09-23T22:24:28.676Z\"}}}",
      "cveMetadata": "{\"cveId\": \"CVE-2025-55038\", \"state\": \"PUBLISHED\", \"dateUpdated\": \"2025-09-24T14:07:38.232Z\", \"dateReserved\": \"2025-09-16T20:09:26.660Z\", \"assignerOrgId\": \"7d14cffa-0d7d-4270-9dc0-52cabd5a23a6\", \"datePublished\": \"2025-09-23T22:24:28.676Z\", \"assignerShortName\": \"icscert\"}",
      "dataType": "CVE_RECORD",
      "dataVersion": "5.1"
    }
  }
}


Log in or create an account to share your comment.




Tags
Taxonomy of the tags.


Loading…

Loading…

Loading…

Sightings

Author Source Type Date

Nomenclature

  • Seen: The vulnerability was mentioned, discussed, or observed by the user.
  • Confirmed: The vulnerability has been validated from an analyst's perspective.
  • Published Proof of Concept: A public proof of concept is available for this vulnerability.
  • Exploited: The vulnerability was observed as exploited by the user who reported the sighting.
  • Patched: The vulnerability was observed as successfully patched by the user who reported the sighting.
  • Not exploited: The vulnerability was not observed as exploited by the user who reported the sighting.
  • Not confirmed: The user expressed doubt about the validity of the vulnerability.