FKIE_CVE-2021-35533
Vulnerability from fkie_nvd - Published: 2021-11-26 17:15 - Updated: 2024-11-21 06:12
Severity ?
7.5 (High) - CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H
7.5 (High) - CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H
7.5 (High) - CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H
Summary
Improper Input Validation vulnerability in the APDU parser in the Bidirectional Communication Interface (BCI) IEC 60870-5-104 function of Hitachi Energy RTU500 series allows an attacker to cause the receiving RTU500 CMU of which the BCI is enabled to reboot when receiving a specially crafted message. By default, BCI IEC 60870-5-104 function is disabled (not configured). This issue affects: Hitachi Energy RTU500 series CMU Firmware version 12.0.* (all versions); CMU Firmware version 12.2.* (all versions); CMU Firmware version 12.4.* (all versions).
References
Impacted products
| Vendor | Product | Version | |
|---|---|---|---|
| hitachienergy | rtu500_firmware | 12.0 | |
| hitachienergy | rtu500_firmware | 12.2 | |
| hitachienergy | rtu500_firmware | 12.4 | |
| hitachienergy | rtu500 | - |
{
"configurations": [
{
"nodes": [
{
"cpeMatch": [
{
"criteria": "cpe:2.3:o:hitachienergy:rtu500_firmware:12.0:*:*:*:*:*:*:*",
"matchCriteriaId": "9BA3F33A-8787-4128-A790-685BCB272A82",
"vulnerable": true
},
{
"criteria": "cpe:2.3:o:hitachienergy:rtu500_firmware:12.2:*:*:*:*:*:*:*",
"matchCriteriaId": "FCD4343D-4B6E-4D6A-A2F3-EFA5CFE4290D",
"vulnerable": true
},
{
"criteria": "cpe:2.3:o:hitachienergy:rtu500_firmware:12.4:*:*:*:*:*:*:*",
"matchCriteriaId": "9CCC7155-16F2-4E60-ABCB-0E6FF71CEC67",
"vulnerable": true
}
],
"negate": false,
"operator": "OR"
},
{
"cpeMatch": [
{
"criteria": "cpe:2.3:h:hitachienergy:rtu500:-:*:*:*:*:*:*:*",
"matchCriteriaId": "DE94252D-03EE-451B-8322-B4DBC790C6E9",
"vulnerable": false
}
],
"negate": false,
"operator": "OR"
}
],
"operator": "AND"
}
],
"cveTags": [],
"descriptions": [
{
"lang": "en",
"value": "Improper Input Validation vulnerability in the APDU parser in the Bidirectional Communication Interface (BCI) IEC 60870-5-104 function of Hitachi Energy RTU500 series allows an attacker to cause the receiving RTU500 CMU of which the BCI is enabled to reboot when receiving a specially crafted message. By default, BCI IEC 60870-5-104 function is disabled (not configured). This issue affects: Hitachi Energy RTU500 series CMU Firmware version 12.0.* (all versions); CMU Firmware version 12.2.* (all versions); CMU Firmware version 12.4.* (all versions)."
},
{
"lang": "es",
"value": "Una vulnerabilidad de comprobaci\u00f3n de entrada inapropiada en el analizador de APDU en la funci\u00f3n IEC 60870-5-104 de la interfaz de comunicaci\u00f3n bidireccional (BCI) de la serie RTU500 de Hitachi Energy permite a un atacante causar el reinicio de la CMU RTU500 receptora en la que est\u00e1 habilitado el BCI cuando recibe un mensaje especialmente dise\u00f1ado. Por defecto, la funci\u00f3n BCI IEC 60870-5-104 est\u00e1 deshabilitada (no configurada). Este problema afecta a: Firmware de la CMU de la serie Hitachi Energy RTU500, versi\u00f3n 12.0.* (todas las versiones); Firmware de la CMU, versi\u00f3n 12.2.* (todas las versiones); Firmware de la CMU, versi\u00f3n 12.4.* (todas las versiones)"
}
],
"id": "CVE-2021-35533",
"lastModified": "2024-11-21T06:12:27.677",
"metrics": {
"cvssMetricV2": [
{
"acInsufInfo": false,
"baseSeverity": "HIGH",
"cvssData": {
"accessComplexity": "MEDIUM",
"accessVector": "NETWORK",
"authentication": "NONE",
"availabilityImpact": "COMPLETE",
"baseScore": 7.1,
"confidentialityImpact": "NONE",
"integrityImpact": "NONE",
"vectorString": "AV:N/AC:M/Au:N/C:N/I:N/A:C",
"version": "2.0"
},
"exploitabilityScore": 8.6,
"impactScore": 6.9,
"obtainAllPrivilege": false,
"obtainOtherPrivilege": false,
"obtainUserPrivilege": false,
"source": "nvd@nist.gov",
"type": "Primary",
"userInteractionRequired": false
}
],
"cvssMetricV31": [
{
"cvssData": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 7.5,
"baseSeverity": "HIGH",
"confidentialityImpact": "NONE",
"integrityImpact": "NONE",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H",
"version": "3.1"
},
"exploitabilityScore": 3.9,
"impactScore": 3.6,
"source": "cybersecurity@hitachienergy.com",
"type": "Secondary"
},
{
"cvssData": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 7.5,
"baseSeverity": "HIGH",
"confidentialityImpact": "NONE",
"integrityImpact": "NONE",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H",
"version": "3.1"
},
"exploitabilityScore": 3.9,
"impactScore": 3.6,
"source": "nvd@nist.gov",
"type": "Primary"
}
]
},
"published": "2021-11-26T17:15:07.743",
"references": [
{
"source": "cybersecurity@hitachienergy.com",
"tags": [
"Vendor Advisory"
],
"url": "https://search.abb.com/library/Download.aspx?DocumentID=8DBD000063\u0026LanguageCode=en\u0026DocumentPartId=\u0026Action=Launch"
},
{
"source": "af854a3a-2127-422b-91ae-364da2661108",
"tags": [
"Vendor Advisory"
],
"url": "https://search.abb.com/library/Download.aspx?DocumentID=8DBD000063\u0026LanguageCode=en\u0026DocumentPartId=\u0026Action=Launch"
}
],
"sourceIdentifier": "cybersecurity@hitachienergy.com",
"vulnStatus": "Modified",
"weaknesses": [
{
"description": [
{
"lang": "en",
"value": "CWE-20"
}
],
"source": "cybersecurity@hitachienergy.com",
"type": "Secondary"
},
{
"description": [
{
"lang": "en",
"value": "CWE-20"
}
],
"source": "nvd@nist.gov",
"type": "Primary"
}
]
}
Loading…
Loading…
Sightings
| Author | Source | Type | Date |
|---|
Nomenclature
- Seen: The vulnerability was mentioned, discussed, or observed by the user.
- Confirmed: The vulnerability has been validated from an analyst's perspective.
- Published Proof of Concept: A public proof of concept is available for this vulnerability.
- Exploited: The vulnerability was observed as exploited by the user who reported the sighting.
- Patched: The vulnerability was observed as successfully patched by the user who reported the sighting.
- Not exploited: The vulnerability was not observed as exploited by the user who reported the sighting.
- Not confirmed: The user expressed doubt about the validity of the vulnerability.
- Not patched: The vulnerability was not observed as successfully patched by the user who reported the sighting.
Loading…
Loading…