FKIE_CVE-2022-4608
Vulnerability from fkie_nvd - Published: 2023-07-26 06:15 - Updated: 2024-11-21 07:35
Severity ?
7.5 (High) - CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H
7.5 (High) - CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H
7.5 (High) - CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H
Summary
A vulnerability exists in HCI IEC 60870-5-104 function included in certain versions of the RTU500 series product. The vulnerability can only be exploited, if the HCI 60870-5-104 is configured with support for IEC 62351-3. After session resumption interval is expired an RTU500 initiated update of session parameters causes an unexpected restart due to a stack overflow.
References
Impacted products
| Vendor | Product | Version | |
|---|---|---|---|
| hitachienergy | rtu500_firmware | 13.3.1 | |
| hitachienergy | rtu500_firmware | 13.3.2 | |
| hitachienergy | rtu500_firmware | 13.3.3 | |
| hitachienergy | rtu500_firmware | 13.4.1 | |
| hitachienergy | rtu500 | - |
{
"configurations": [
{
"nodes": [
{
"cpeMatch": [
{
"criteria": "cpe:2.3:o:hitachienergy:rtu500_firmware:13.3.1:*:*:*:*:*:*:*",
"matchCriteriaId": "C444DE8E-5AC5-409B-8DA0-5C49A69076DD",
"vulnerable": true
},
{
"criteria": "cpe:2.3:o:hitachienergy:rtu500_firmware:13.3.2:*:*:*:*:*:*:*",
"matchCriteriaId": "4C55747C-E5DA-4444-B017-1994011A5EF7",
"vulnerable": true
},
{
"criteria": "cpe:2.3:o:hitachienergy:rtu500_firmware:13.3.3:*:*:*:*:*:*:*",
"matchCriteriaId": "0997C03B-21AC-4767-856C-79833FB378A8",
"vulnerable": true
},
{
"criteria": "cpe:2.3:o:hitachienergy:rtu500_firmware:13.4.1:*:*:*:*:*:*:*",
"matchCriteriaId": "C0763F03-C6C8-4104-9028-3CF265F289D5",
"vulnerable": true
}
],
"negate": false,
"operator": "OR"
},
{
"cpeMatch": [
{
"criteria": "cpe:2.3:h:hitachienergy:rtu500:-:*:*:*:*:*:*:*",
"matchCriteriaId": "DE94252D-03EE-451B-8322-B4DBC790C6E9",
"vulnerable": false
}
],
"negate": false,
"operator": "OR"
}
],
"operator": "AND"
}
],
"cveTags": [],
"descriptions": [
{
"lang": "en",
"value": "A vulnerability exists in HCI IEC 60870-5-104 function included in certain versions of the RTU500 series product. The vulnerability can only be exploited, if the HCI 60870-5-104 is configured with support for IEC 62351-3. After session resumption interval is expired an RTU500 initiated update of session parameters causes an unexpected restart due to a stack overflow."
}
],
"id": "CVE-2022-4608",
"lastModified": "2024-11-21T07:35:35.383",
"metrics": {
"cvssMetricV31": [
{
"cvssData": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 7.5,
"baseSeverity": "HIGH",
"confidentialityImpact": "NONE",
"integrityImpact": "NONE",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H",
"version": "3.1"
},
"exploitabilityScore": 3.9,
"impactScore": 3.6,
"source": "cybersecurity@hitachienergy.com",
"type": "Secondary"
},
{
"cvssData": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 7.5,
"baseSeverity": "HIGH",
"confidentialityImpact": "NONE",
"integrityImpact": "NONE",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H",
"version": "3.1"
},
"exploitabilityScore": 3.9,
"impactScore": 3.6,
"source": "nvd@nist.gov",
"type": "Primary"
}
]
},
"published": "2023-07-26T06:15:10.220",
"references": [
{
"source": "cybersecurity@hitachienergy.com",
"url": "https://publisher.hitachienergy.com/preview?DocumentID=8DBD000121\u0026LanguageCode=en\u0026DocumentPartId=\u0026Action=Launch"
},
{
"source": "af854a3a-2127-422b-91ae-364da2661108",
"url": "https://search.abb.com/library/Download.aspx?DocumentID=8DBD000121\u0026LanguageCode=en\u0026DocumentPartId=\u0026Action=Launch"
}
],
"sourceIdentifier": "cybersecurity@hitachienergy.com",
"vulnStatus": "Modified",
"weaknesses": [
{
"description": [
{
"lang": "en",
"value": "CWE-787"
}
],
"source": "cybersecurity@hitachienergy.com",
"type": "Secondary"
},
{
"description": [
{
"lang": "en",
"value": "CWE-787"
}
],
"source": "nvd@nist.gov",
"type": "Primary"
}
]
}
Loading…
Loading…
Sightings
| Author | Source | Type | Date |
|---|
Nomenclature
- Seen: The vulnerability was mentioned, discussed, or observed by the user.
- Confirmed: The vulnerability has been validated from an analyst's perspective.
- Published Proof of Concept: A public proof of concept is available for this vulnerability.
- Exploited: The vulnerability was observed as exploited by the user who reported the sighting.
- Patched: The vulnerability was observed as successfully patched by the user who reported the sighting.
- Not exploited: The vulnerability was not observed as exploited by the user who reported the sighting.
- Not confirmed: The user expressed doubt about the validity of the vulnerability.
- Not patched: The vulnerability was not observed as successfully patched by the user who reported the sighting.
Loading…
Loading…