GHSA-34QF-4246-PHGF
Vulnerability from github – Published: 2024-07-04 09:32 – Updated: 2024-07-04 09:32
VLAI?
Details
Improper Authentication vulnerability in the mobile monitoring feature of ICONICS GENESIS64 versions 10.97 to 10.97.2, Mitsubishi Electric GENESIS64 versions 10.97 to 10.97.2 and Mitsubishi Electric MC Works64 all versions allows a remote unauthenticated attacker to bypass proper authentication and log in to the system when all of the following conditions are met: * Active Directory is used in the security setting. * “Automatic log in” option is enabled in the security setting. * The IcoAnyGlass IIS Application Pool is running under an Active Directory Domain Account. * The IcoAnyGlass IIS Application Pool account is included in GENESIS64TM and MC Works64 Security and has permission to log in.
Severity ?
5.9 (Medium)
{
"affected": [],
"aliases": [
"CVE-2024-1573"
],
"database_specific": {
"cwe_ids": [
"CWE-287"
],
"github_reviewed": false,
"github_reviewed_at": null,
"nvd_published_at": "2024-07-04T09:15:03Z",
"severity": "MODERATE"
},
"details": "Improper Authentication vulnerability in the mobile monitoring feature of ICONICS GENESIS64 versions 10.97 to 10.97.2, Mitsubishi Electric GENESIS64 versions 10.97 to 10.97.2 and Mitsubishi Electric MC Works64 all versions allows a remote unauthenticated attacker to bypass proper authentication and log in to the system when all of the following conditions are met: * Active Directory is used in the security setting.\n * \u201cAutomatic log in\u201d option is enabled in the security setting.\n * The IcoAnyGlass IIS Application Pool is running under an Active Directory Domain Account.\n * The IcoAnyGlass IIS Application Pool account is included in GENESIS64TM and MC Works64 Security and has permission to log in.",
"id": "GHSA-34qf-4246-phgf",
"modified": "2024-07-04T09:32:49Z",
"published": "2024-07-04T09:32:49Z",
"references": [
{
"type": "ADVISORY",
"url": "https://nvd.nist.gov/vuln/detail/CVE-2024-1573"
},
{
"type": "WEB",
"url": "https://jvn.jp/vu/JVNVU98894016"
},
{
"type": "WEB",
"url": "https://www.cisa.gov/news-events/ics-advisories/icsa-24-184-03"
},
{
"type": "WEB",
"url": "https://www.mitsubishielectric.com/en/psirt/vulnerability/pdf/2024-004_en.pdf"
}
],
"schema_version": "1.4.0",
"severity": [
{
"score": "CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:N/I:H/A:N",
"type": "CVSS_V3"
}
]
}
Loading…
Loading…
Sightings
| Author | Source | Type | Date |
|---|
Nomenclature
- Seen: The vulnerability was mentioned, discussed, or observed by the user.
- Confirmed: The vulnerability has been validated from an analyst's perspective.
- Published Proof of Concept: A public proof of concept is available for this vulnerability.
- Exploited: The vulnerability was observed as exploited by the user who reported the sighting.
- Patched: The vulnerability was observed as successfully patched by the user who reported the sighting.
- Not exploited: The vulnerability was not observed as exploited by the user who reported the sighting.
- Not confirmed: The user expressed doubt about the validity of the vulnerability.
- Not patched: The vulnerability was not observed as successfully patched by the user who reported the sighting.
Loading…