gsd-2022-29492
Vulnerability from gsd
Modified
2023-12-13 01:19
Details
Improper Input Validation vulnerability in the handling of a malformed IEC 104 TCP packet in the Hitachi Energy MicroSCADA X SYS600, MicroSCADA Pro SYS600. Upon receiving a malformed IEC 104 TCP packet, the malformed packet is dropped, however the TCP connection is left open. This may cause a denial-of-service if the affected connection is left open. This issue affects: Hitachi Energy MicroSCADA Pro SYS600 version 9.4 FP2 Hotfix 4 and earlier versions Hitachi Energy MicroSCADA X SYS600 version 10 to version 10.3.1. cpe:2.3:a:hitachienergy:microscada_pro_sys600:9.0:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_pro_sys600:9.1:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_pro_sys600:9.2:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_pro_sys600:9.3:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_pro_sys600:9.4:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.1:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.1.1:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.2:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.2.1:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.3:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.3.1:*:*:*:*:*:*:*
Aliases
Aliases



{
  "GSD": {
    "alias": "CVE-2022-29492",
    "description": "Improper Input Validation vulnerability in the handling of a malformed IEC 104 TCP packet in the Hitachi Energy MicroSCADA X SYS600, MicroSCADA Pro SYS600. Upon receiving a malformed IEC 104 TCP packet, the malformed packet is dropped, however the TCP connection is left open. This may cause a denial-of-service if the affected connection is left open. This issue affects: Hitachi Energy MicroSCADA Pro SYS600 version 9.4 FP2 Hotfix 4 and earlier versions Hitachi Energy MicroSCADA X SYS600 version 10 to version 10.3.1. cpe:2.3:a:hitachienergy:microscada_pro_sys600:9.0:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_pro_sys600:9.1:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_pro_sys600:9.2:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_pro_sys600:9.3:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_pro_sys600:9.4:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.1:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.1.1:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.2:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.2.1:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.3:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.3.1:*:*:*:*:*:*:*",
    "id": "GSD-2022-29492"
  },
  "gsd": {
    "metadata": {
      "exploitCode": "unknown",
      "remediation": "unknown",
      "reportConfidence": "confirmed",
      "type": "vulnerability"
    },
    "osvSchema": {
      "aliases": [
        "CVE-2022-29492"
      ],
      "details": "Improper Input Validation vulnerability in the handling of a malformed IEC 104 TCP packet in the Hitachi Energy MicroSCADA X SYS600, MicroSCADA Pro SYS600. Upon receiving a malformed IEC 104 TCP packet, the malformed packet is dropped, however the TCP connection is left open. This may cause a denial-of-service if the affected connection is left open. This issue affects: Hitachi Energy MicroSCADA Pro SYS600 version 9.4 FP2 Hotfix 4 and earlier versions Hitachi Energy MicroSCADA X SYS600 version 10 to version 10.3.1. cpe:2.3:a:hitachienergy:microscada_pro_sys600:9.0:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_pro_sys600:9.1:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_pro_sys600:9.2:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_pro_sys600:9.3:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_pro_sys600:9.4:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.1:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.1.1:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.2:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.2.1:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.3:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.3.1:*:*:*:*:*:*:*",
      "id": "GSD-2022-29492",
      "modified": "2023-12-13T01:19:42.129333Z",
      "schema_version": "1.4.0"
    }
  },
  "namespaces": {
    "cve.org": {
      "CVE_data_meta": {
        "ASSIGNER": "cybersecurity@hitachienergy.com",
        "DATE_PUBLIC": "2022-09-06T14:30:00.000Z",
        "ID": "CVE-2022-29492",
        "STATE": "PUBLIC",
        "TITLE": "A vulnerability exists in the handling of a malformed IEC 104 TCP packet. Upon receiving a malformed IEC 104 TCP packet, the malformed packet is dropped, however the TCP connection is left open. This may cause a denial-of-service if the affected connection is left open."
      },
      "affects": {
        "vendor": {
          "vendor_data": [
            {
              "product": {
                "product_data": [
                  {
                    "product_name": "MicroSCADA X SYS600",
                    "version": {
                      "version_data": [
                        {
                          "version_affected": "=",
                          "version_value": "10"
                        },
                        {
                          "version_affected": "=",
                          "version_value": "10.1"
                        },
                        {
                          "version_affected": "=",
                          "version_value": "10.1.1"
                        },
                        {
                          "version_affected": "=",
                          "version_value": "10.2"
                        },
                        {
                          "version_affected": "=",
                          "version_value": "10.2.1"
                        },
                        {
                          "version_affected": "=",
                          "version_value": "10.3"
                        },
                        {
                          "version_affected": "=",
                          "version_value": "10.3.1"
                        }
                      ]
                    }
                  },
                  {
                    "product_name": "MicroSCADA Pro SYS600",
                    "version": {
                      "version_data": [
                        {
                          "version_affected": "\u003c=",
                          "version_value": "9.2 FP2 Hotfix 4"
                        }
                      ]
                    }
                  }
                ]
              },
              "vendor_name": "Hitachi Energy"
            }
          ]
        }
      },
      "data_format": "MITRE",
      "data_type": "CVE",
      "data_version": "4.0",
      "description": {
        "description_data": [
          {
            "lang": "eng",
            "value": "Improper Input Validation vulnerability in the handling of a malformed IEC 104 TCP packet in the Hitachi Energy MicroSCADA X SYS600, MicroSCADA Pro SYS600. Upon receiving a malformed IEC 104 TCP packet, the malformed packet is dropped, however the TCP connection is left open. This may cause a denial-of-service if the affected connection is left open. This issue affects: Hitachi Energy MicroSCADA Pro SYS600 version 9.4 FP2 Hotfix 4 and earlier versions Hitachi Energy MicroSCADA X SYS600 version 10 to version 10.3.1. cpe:2.3:a:hitachienergy:microscada_pro_sys600:9.0:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_pro_sys600:9.1:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_pro_sys600:9.2:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_pro_sys600:9.3:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_pro_sys600:9.4:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.1:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.1.1:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.2:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.2.1:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.3:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.3.1:*:*:*:*:*:*:*"
          }
        ]
      },
      "generator": {
        "engine": "Vulnogram 0.0.9"
      },
      "impact": {
        "cvss": {
          "attackComplexity": "LOW",
          "attackVector": "NETWORK",
          "availabilityImpact": "LOW",
          "baseScore": 5.3,
          "baseSeverity": "MEDIUM",
          "confidentialityImpact": "NONE",
          "integrityImpact": "NONE",
          "privilegesRequired": "NONE",
          "scope": "UNCHANGED",
          "userInteraction": "NONE",
          "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:L",
          "version": "3.1"
        }
      },
      "problemtype": {
        "problemtype_data": [
          {
            "description": [
              {
                "lang": "eng",
                "value": "CWE-20 Improper Input Validation"
              }
            ]
          }
        ]
      },
      "references": {
        "reference_data": [
          {
            "name": "https://search.abb.com/library/Download.aspx?DocumentID=8DBD000106\u0026LanguageCode=en\u0026DocumentPartId=\u0026Action=Launch",
            "refsource": "CONFIRM",
            "url": "https://search.abb.com/library/Download.aspx?DocumentID=8DBD000106\u0026LanguageCode=en\u0026DocumentPartId=\u0026Action=Launch"
          }
        ]
      },
      "solution": [
        {
          "lang": "eng",
          "value": "Remediated in SYS600 10.4 \nFor MicroSCADA Pro SYS600  - Upgrade to at least SYS600 version 10.4.\nFor MicroSCADA X SYS600  - Update to at least SYS600 version 10.4."
        }
      ],
      "source": {
        "discovery": "INTERNAL"
      },
      "work_around": [
        {
          "lang": "eng",
          "value": "Apply general mitigation factors as specify in the advisory."
        }
      ]
    },
    "nvd.nist.gov": {
      "configurations": {
        "CVE_data_version": "4.0",
        "nodes": [
          {
            "children": [
              {
                "children": [],
                "cpe_match": [
                  {
                    "cpe23Uri": "cpe:2.3:a:hitachienergy:microscada_x_sys600:*:*:*:*:*:*:*:*",
                    "cpe_name": [],
                    "versionEndExcluding": "10.4",
                    "versionStartIncluding": "9.0",
                    "vulnerable": true
                  }
                ],
                "operator": "OR"
              },
              {
                "children": [],
                "cpe_match": [
                  {
                    "cpe23Uri": "cpe:2.3:h:hitachienergy:sys600:-:*:*:*:*:*:*:*",
                    "cpe_name": [],
                    "vulnerable": false
                  }
                ],
                "operator": "OR"
              }
            ],
            "cpe_match": [],
            "operator": "AND"
          }
        ]
      },
      "cve": {
        "CVE_data_meta": {
          "ASSIGNER": "cybersecurity@hitachienergy.com",
          "ID": "CVE-2022-29492"
        },
        "data_format": "MITRE",
        "data_type": "CVE",
        "data_version": "4.0",
        "description": {
          "description_data": [
            {
              "lang": "en",
              "value": "Improper Input Validation vulnerability in the handling of a malformed IEC 104 TCP packet in the Hitachi Energy MicroSCADA X SYS600, MicroSCADA Pro SYS600. Upon receiving a malformed IEC 104 TCP packet, the malformed packet is dropped, however the TCP connection is left open. This may cause a denial-of-service if the affected connection is left open. This issue affects: Hitachi Energy MicroSCADA Pro SYS600 version 9.4 FP2 Hotfix 4 and earlier versions Hitachi Energy MicroSCADA X SYS600 version 10 to version 10.3.1. cpe:2.3:a:hitachienergy:microscada_pro_sys600:9.0:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_pro_sys600:9.1:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_pro_sys600:9.2:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_pro_sys600:9.3:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_pro_sys600:9.4:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.1:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.1.1:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.2:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.2.1:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.3:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.3.1:*:*:*:*:*:*:*"
            }
          ]
        },
        "problemtype": {
          "problemtype_data": [
            {
              "description": [
                {
                  "lang": "en",
                  "value": "CWE-20"
                }
              ]
            }
          ]
        },
        "references": {
          "reference_data": [
            {
              "name": "https://search.abb.com/library/Download.aspx?DocumentID=8DBD000106\u0026LanguageCode=en\u0026DocumentPartId=\u0026Action=Launch",
              "refsource": "CONFIRM",
              "tags": [
                "Vendor Advisory"
              ],
              "url": "https://search.abb.com/library/Download.aspx?DocumentID=8DBD000106\u0026LanguageCode=en\u0026DocumentPartId=\u0026Action=Launch"
            }
          ]
        }
      },
      "impact": {
        "baseMetricV3": {
          "cvssV3": {
            "attackComplexity": "LOW",
            "attackVector": "NETWORK",
            "availabilityImpact": "HIGH",
            "baseScore": 7.5,
            "baseSeverity": "HIGH",
            "confidentialityImpact": "NONE",
            "integrityImpact": "NONE",
            "privilegesRequired": "NONE",
            "scope": "UNCHANGED",
            "userInteraction": "NONE",
            "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H",
            "version": "3.1"
          },
          "exploitabilityScore": 3.9,
          "impactScore": 3.6
        }
      },
      "lastModifiedDate": "2022-10-05T13:45Z",
      "publishedDate": "2022-09-14T18:15Z"
    }
  }
}


Log in or create an account to share your comment.




Tags
Taxonomy of the tags.


Loading...

Loading...

Loading...

Sightings

Author Source Type Date

Nomenclature

  • Seen: The vulnerability was mentioned, discussed, or seen somewhere by the user.
  • Confirmed: The vulnerability is confirmed from an analyst perspective.
  • Exploited: This vulnerability was exploited and seen by the user reporting the sighting.
  • Patched: This vulnerability was successfully patched by the user reporting the sighting.
  • Not exploited: This vulnerability was not exploited or seen by the user reporting the sighting.
  • Not confirmed: The user expresses doubt about the veracity of the vulnerability.
  • Not patched: This vulnerability was not successfully patched by the user reporting the sighting.