ICSA-18-347-04
Vulnerability from csaf_cisa - Published: 2018-12-13 00:00 - Updated: 2018-12-13 00:00Summary
GE Mark VIe, EX2100e, EX2100e
Notes
CISA Disclaimer
This CSAF advisory was extracted from unstructured data and may contain inaccuracies. If you notice any errors, please reach out to the designated contact at CISA CSAF: central@cisa.dhs.gov
Legal Notice
All information products included in https://us-cert.cisa.gov/ics are provided "as is" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see https://us-cert.cisa.gov/tlp/.
Risk evaluation
Successful exploitation of this vulnerability could allow an attacker to access system data, which could result in escalation of privilege and unauthorized access to the controller.
Critical infrastructure sectors
Energy
Countries/areas deployed
Worldwide
Company headquarters location
United States
Recommended Practices
NCCIC reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.NCCIC also provides a section for control systems security recommended practices on the ICS-CERT web page. Several recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.
Recommended Practices
Additional mitigation guidance and recommended practices are publicly available on the ICS-CERT website in the Technical Information Paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.Organizations observing any suspected malicious activity should follow their established internal procedures and report their findings to NCCIC for tracking and correlation against other incidents.
Exploitability
No known public exploits specifically target this vulnerability. This vulnerability is not exploitable remotely.
{
"document": {
"acknowledgments": [
{
"names": [
"Can Demirel"
],
"organization": "Biznet Bilisim",
"summary": "reporting this vulnerability to NCCIC"
}
],
"category": "csaf_security_advisory",
"csaf_version": "2.0",
"distribution": {
"text": "Disclosure is not limited",
"tlp": {
"label": "WHITE",
"url": "https://us-cert.cisa.gov/tlp/"
}
},
"lang": "en-US",
"notes": [
{
"category": "general",
"text": "This CSAF advisory was extracted from unstructured data and may contain inaccuracies. If you notice any errors, please reach out to the designated contact at CISA CSAF: central@cisa.dhs.gov",
"title": "CISA Disclaimer"
},
{
"category": "legal_disclaimer",
"text": "All information products included in https://us-cert.cisa.gov/ics are provided \"as is\" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see https://us-cert.cisa.gov/tlp/.",
"title": "Legal Notice"
},
{
"category": "summary",
"text": "Successful exploitation of this vulnerability could allow an attacker to access system data, which could result in escalation of privilege and unauthorized access to the controller.",
"title": "Risk evaluation"
},
{
"category": "other",
"text": "Energy",
"title": "Critical infrastructure sectors"
},
{
"category": "other",
"text": "Worldwide",
"title": "Countries/areas deployed"
},
{
"category": "other",
"text": "United States",
"title": "Company headquarters location"
},
{
"category": "general",
"text": "NCCIC reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.NCCIC also provides a section for control systems security recommended practices on the ICS-CERT web page. Several recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.",
"title": "Recommended Practices"
},
{
"category": "general",
"text": "Additional mitigation guidance and recommended practices are publicly available on the ICS-CERT website in the Technical Information Paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.Organizations observing any suspected malicious activity should follow their established internal procedures and report their findings to NCCIC for tracking and correlation against other incidents.",
"title": "Recommended Practices"
},
{
"category": "other",
"text": "No known public exploits specifically target this vulnerability. This vulnerability is not exploitable remotely.",
"title": "Exploitability"
}
],
"publisher": {
"category": "coordinator",
"contact_details": "Email: CISAservicedesk@cisa.dhs.gov;\n Toll Free: 1-888-282-0870",
"name": "CISA",
"namespace": "https://www.cisa.gov/"
},
"references": [
{
"category": "self",
"summary": "ICS Advisory ICSA-18-347-04 JSON",
"url": "https://raw.githubusercontent.com/cisagov/CSAF/develop/csaf_files/OT/white/2018/icsa-18-347-04.json"
},
{
"category": "self",
"summary": "ICS Advisory ICSA-18-347-04 Web Version",
"url": "https://www.cisa.gov/news-events/ics-advisories/icsa-18-347-04"
},
{
"category": "external",
"summary": "Recommended Practices",
"url": "https://www.cisa.gov/uscert/sites/default/files/recommended_practices/NCCIC_ICS-CERT_Defense_in_Depth_2016_S508C.pdf"
},
{
"category": "external",
"summary": "Recommended Practices",
"url": "https://www.cisa.gov/uscert/ics/tips/ICS-TIP-12-146-01B"
}
],
"title": "GE Mark VIe, EX2100e, EX2100e",
"tracking": {
"current_release_date": "2018-12-13T00:00:00.000000Z",
"generator": {
"engine": {
"name": "CISA CSAF Generator",
"version": "1.0.0"
}
},
"id": "ICSA-18-347-04",
"initial_release_date": "2018-12-13T00:00:00.000000Z",
"revision_history": [
{
"date": "2018-12-13T00:00:00.000000Z",
"legacy_version": "Initial",
"number": "1",
"summary": "ICSA-18-347-04 GE Mark VIe, EX2100e, EX2100e_Reg, and LS2100e"
}
],
"status": "final",
"version": "1"
}
},
"product_tree": {
"branches": [
{
"branches": [
{
"branches": [
{
"category": "product_version_range",
"name": "\u003c 04.09.00C",
"product": {
"name": "EX2100e: All versions prior to v04.09.00C",
"product_id": "CSAFPID-0001"
}
}
],
"category": "product_name",
"name": "EX2100e"
},
{
"branches": [
{
"category": "product_version_range",
"name": "\u003e= 03.03.28C | \u003c= 05.02.04C",
"product": {
"name": "Mark VIe: Versions 03.03.28C to 05.02.04C",
"product_id": "CSAFPID-0002"
}
}
],
"category": "product_name",
"name": "Mark VIe"
},
{
"branches": [
{
"category": "product_version_range",
"name": "\u003c 04.09.00C",
"product": {
"name": "EX2100e_Reg: All versions prior to v04.09.00C",
"product_id": "CSAFPID-0003"
}
}
],
"category": "product_name",
"name": "EX2100e_Reg"
},
{
"branches": [
{
"category": "product_version_range",
"name": "\u003c 04.09.00C",
"product": {
"name": "LS2100e: All versions prior to v04.09.00C",
"product_id": "CSAFPID-0004"
}
}
],
"category": "product_name",
"name": "LS2100e"
}
],
"category": "vendor",
"name": "General Electric (GE)"
}
]
},
"vulnerabilities": [
{
"cve": "CVE-2018-19003",
"cwe": {
"id": "CWE-22",
"name": "Improper Limitation of a Pathname to a Restricted Directory (\u0027Path Traversal\u0027)"
},
"notes": [
{
"category": "summary",
"text": "The affected versions of the application have a path traversal vulnerability that fails to restrict the ability of an attacker to gain access to restricted information.CVE-2018-19003 has been assigned to this vulnerability. A CVSS v3 base score of 7.4 has been calculated; the CVSS vector string is (AV:A/AC:L/PR:N/UI:N/S:C/C:H/I:N/A:N).",
"title": "Vulnerability Summary"
}
],
"product_status": {
"known_affected": [
"CSAFPID-0001",
"CSAFPID-0002",
"CSAFPID-0003",
"CSAFPID-0004"
]
},
"references": [
{
"category": "external",
"summary": "web.nvd.nist.gov",
"url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2018-19003"
},
{
"category": "external",
"summary": "www.first.org",
"url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:A/AC:L/PR:N/UI:N/S:C/C:H/I:N/A:N"
}
],
"remediations": [
{
"category": "mitigation",
"details": "The path traversal vulnerability has been corrected by GE. GE recommends users upgrade to the current version of ControlST software as described in CSB25378, which is available to registered users via the GE Power ServiceNow portal (https://gepowerpac.service-now.com).",
"product_ids": [
"CSAFPID-0001",
"CSAFPID-0002",
"CSAFPID-0003",
"CSAFPID-0004"
],
"url": "https://gepowerpac.service-now.com"
},
{
"category": "mitigation",
"details": "In applications where the controller-hosted web server is not required, GE recommends turning off the web server. For all other applications, GE recommends updating the controller to the latest firmware version available in the current ControlST release.",
"product_ids": [
"CSAFPID-0001",
"CSAFPID-0002",
"CSAFPID-0003",
"CSAFPID-0004"
]
},
{
"category": "mitigation",
"details": "With respect to EX2100e, GE recommends that all standalone excitation controls be segmented from other networks using a firewall installed inside the Excitation panels. External communication should be exclusively restricted to only those protocols specifically required for command and control, such as Modbus. Other services including HTTP must be blocked from external access.",
"product_ids": [
"CSAFPID-0001",
"CSAFPID-0002",
"CSAFPID-0003",
"CSAFPID-0004"
]
},
{
"category": "mitigation",
"details": "To minimize the risk of exposure to this and any other vulnerabilities, GE recommends a defense-in-depth approach to protecting critical process control equipment. Guidance on technology and best practices to secure GE controllers from cyber attack are provided in the Mark VIe Control Systems Secure Deployment Guide (GEH-6839), which can be requested through GE Technical Support.",
"product_ids": [
"CSAFPID-0001",
"CSAFPID-0002",
"CSAFPID-0003",
"CSAFPID-0004"
]
},
{
"category": "mitigation",
"details": "Maintain tight physical access control to all critical controllers.",
"product_ids": [
"CSAFPID-0001",
"CSAFPID-0002",
"CSAFPID-0003",
"CSAFPID-0004"
]
},
{
"category": "mitigation",
"details": "Limit network availability to only the most critical needs and implement tight firewall restrictions.",
"product_ids": [
"CSAFPID-0001",
"CSAFPID-0002",
"CSAFPID-0003",
"CSAFPID-0004"
]
},
{
"category": "mitigation",
"details": "Disable any unnecessary network related functions or enable only on an as needed basis.",
"product_ids": [
"CSAFPID-0001",
"CSAFPID-0002",
"CSAFPID-0003",
"CSAFPID-0004"
]
}
],
"scores": [
{
"cvss_v3": {
"baseScore": 7.4,
"baseSeverity": "HIGH",
"vectorString": "CVSS:3.0/AV:A/AC:L/PR:N/UI:N/S:C/C:H/I:N/A:N",
"version": "3.0"
},
"products": [
"CSAFPID-0001",
"CSAFPID-0002",
"CSAFPID-0003",
"CSAFPID-0004"
]
}
]
}
]
}
Loading…
Loading…
Sightings
| Author | Source | Type | Date |
|---|
Nomenclature
- Seen: The vulnerability was mentioned, discussed, or observed by the user.
- Confirmed: The vulnerability has been validated from an analyst's perspective.
- Published Proof of Concept: A public proof of concept is available for this vulnerability.
- Exploited: The vulnerability was observed as exploited by the user who reported the sighting.
- Patched: The vulnerability was observed as successfully patched by the user who reported the sighting.
- Not exploited: The vulnerability was not observed as exploited by the user who reported the sighting.
- Not confirmed: The user expressed doubt about the validity of the vulnerability.
- Not patched: The vulnerability was not observed as successfully patched by the user who reported the sighting.
Loading…