icsa-20-133-01
Vulnerability from csaf_cisa
Published
2020-05-12 00:00
Modified
2020-05-12 00:00
Summary
Eaton Intelligent Power Manager
Notes
CISA Disclaimer
This CSAF advisory was extracted from unstructured data and may contain inaccuracies. If you notice any errors, please reach out to the designated contact at CISA CSAF: central@cisa.dhs.gov
Legal Notice
All information products included in https://us-cert.cisa.gov/ics are provided "as is" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see https://us-cert.cisa.gov/tlp/.
Risk evaluation
Successful exploitation of these vulnerabilities could allow an attacker to perform command injection or code execution and allow non-administrator users to manipulate the system configurations.
Critical infrastructure sectors
Energy
Countries/areas deployed
Worldwide
Company headquarters location
Ireland
Recommended Practices
CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability. Specifically, users should:
Recommended Practices
CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.
CISA also provides a section for control systems security recommended practices on the ICS webpage onus-cert.gov. Several recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.
Recommended Practices
Additional mitigation guidance and recommended practices are publicly available on the ICS webpage on us-cert.gov in the Technical Information Paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.
Organizations observing any suspected malicious activity should follow their established internal procedures and report their findings to CISA for tracking and correlation against other incidents.
Exploitability
No known public exploits specifically target these vulnerabilities.
{ "document": { "acknowledgments": [ { "names": [ "Sivathmican Sivakumaran" ], "organization": "Trend Micro \u0027s Zero Day Initiative", "summary": "reporting these vulnerabilities to CISA" } ], "category": "csaf_security_advisory", "csaf_version": "2.0", "distribution": { "text": "Disclosure is not limited", "tlp": { "label": "WHITE", "url": "https://us-cert.cisa.gov/tlp/" } }, "lang": "en-US", "notes": [ { "category": "general", "text": "This CSAF advisory was extracted from unstructured data and may contain inaccuracies. If you notice any errors, please reach out to the designated contact at CISA CSAF: central@cisa.dhs.gov", "title": "CISA Disclaimer" }, { "category": "legal_disclaimer", "text": "All information products included in https://us-cert.cisa.gov/ics are provided \"as is\" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see https://us-cert.cisa.gov/tlp/.", "title": "Legal Notice" }, { "category": "summary", "text": "Successful exploitation of these vulnerabilities could allow an attacker to perform command injection or code execution and allow non-administrator users to manipulate the system configurations.", "title": "Risk evaluation" }, { "category": "other", "text": "Energy", "title": "Critical infrastructure sectors" }, { "category": "other", "text": "Worldwide", "title": "Countries/areas deployed" }, { "category": "other", "text": "Ireland", "title": "Company headquarters location" }, { "category": "general", "text": "CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability. Specifically, users should:", "title": "Recommended Practices" }, { "category": "general", "text": "CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.\nCISA also provides a section for control systems security recommended practices on the ICS webpage onus-cert.gov. Several recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.", "title": "Recommended Practices" }, { "category": "general", "text": "Additional mitigation guidance and recommended practices are publicly available on the ICS webpage on us-cert.gov in the Technical Information Paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.\nOrganizations observing any suspected malicious activity should follow their established internal procedures and report their findings to CISA for tracking and correlation against other incidents.", "title": "Recommended Practices" }, { "category": "other", "text": "No known public exploits specifically target these vulnerabilities.", "title": "Exploitability" } ], "publisher": { "category": "coordinator", "contact_details": "Email: CISAservicedesk@cisa.dhs.gov;\n Toll Free: 1-888-282-0870", "name": "CISA", "namespace": "https://www.cisa.gov/" }, "references": [ { "category": "self", "summary": "ICS Advisory ICSA-20-133-01 JSON", "url": "https://raw.githubusercontent.com/cisagov/CSAF/develop/csaf_files/OT/white/2020/icsa-20-133-01.json" }, { "category": "self", "summary": "ICS Advisory ICSA-20-133-01 Web Version", "url": "https://www.cisa.gov/news-events/ics-advisories/icsa-20-133-01" }, { "category": "external", "summary": "Recommended Practices", "url": "https://www.us-cert.gov/ics/alerts/ICS-ALERT-10-301-01" }, { "category": "external", "summary": "Recommended Practices", "url": "https://www.us-cert.gov/sites/default/files/recommended_practices/NCCIC_ICS-CERT_Defense_in_Depth_2016_S508C.pdf" }, { "category": "external", "summary": "Recommended Practices", "url": "https://www.us-cert.gov/ics/tips/ICS-TIP-12-146-01B" } ], "title": "Eaton Intelligent Power Manager", "tracking": { "current_release_date": "2020-05-12T00:00:00.000000Z", "generator": { "engine": { "name": "CISA CSAF Generator", "version": "1.0.0" } }, "id": "ICSA-20-133-01", "initial_release_date": "2020-05-12T00:00:00.000000Z", "revision_history": [ { "date": "2020-05-12T00:00:00.000000Z", "legacy_version": "Initial", "number": "1", "summary": "ICSA-20-133-01 Eaton Intelligent Power Manager" } ], "status": "final", "version": "1" } }, "product_tree": { "branches": [ { "branches": [ { "branches": [ { "category": "product_version_range", "name": "\u003c= 1.67", "product": { "name": "Intelligent Power Manager: v1.67 and prior", "product_id": "CSAFPID-0001" } } ], "category": "product_name", "name": "Intelligent Power Manager" } ], "category": "vendor", "name": "Eaton" } ] }, "vulnerabilities": [ { "cve": "CVE-2020-6651", "cwe": { "id": "CWE-20", "name": "Improper Input Validation" }, "notes": [ { "category": "summary", "text": "The affected product may not validate import configuration file names properly, which could allow an attacker to perform command injection or code execution.CVE-2020-6651 has been assigned to this vulnerability. A CVSS v3 base score of 8.8 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H).", "title": "Vulnerability Summary" } ], "product_status": { "known_affected": [ "CSAFPID-0001" ] }, "references": [ { "category": "external", "summary": "web.nvd.nist.gov", "url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2020-6651" }, { "category": "external", "summary": "www.first.org", "url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H" } ], "remediations": [ { "category": "vendor_fix", "details": "Eaton has released Intelligent Power Manager v1.68 to address the reported vulnerabilities.", "product_ids": [ "CSAFPID-0001" ], "url": "https://www.eaton.com/us/en-us/catalog/backup-power-ups-surge-it-power-distribution/eaton-intelligent-power-manager/download-eaton-intelligent-power-manager-ipm.html" }, { "category": "vendor_fix", "details": "To prevent the exploitation of the issues and safeguard the software from malicious entities, Eaton recommends blocking Ports 4679 and 4680 at the enterprise network or home network where Intelligent Power Manager software is installed and used.", "product_ids": [ "CSAFPID-0001" ] }, { "category": "mitigation", "details": "For additional information please see the Eaton Vulnerability Advisory.", "product_ids": [ "CSAFPID-0001" ], "url": "https://www.eaton.com/content/dam/eaton/company/news-insights/cybersecurity/security-bulletins/eaton-vulnerability-advisory-intelligent-power-manager-v1-1.pdf" } ], "scores": [ { "cvss_v3": { "baseScore": 8.8, "baseSeverity": "HIGH", "vectorString": "CVSS:3.0/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H", "version": "3.0" }, "products": [ "CSAFPID-0001" ] } ] }, { "cve": "CVE-2020-6652", "cwe": { "id": "CWE-266", "name": "Incorrect Privilege Assignment" }, "notes": [ { "category": "summary", "text": "The affected product may allow non-administrator users to upload the system configuration files by sending specially crafted requests, which could allow non-administrator users to manipulate the system configurations.CVE-2020-6652 has been assigned to this vulnerability. A CVSS v3 base score of 7.8 has been calculated; the CVSS vector string is (AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H).", "title": "Vulnerability Summary" } ], "product_status": { "known_affected": [ "CSAFPID-0001" ] }, "references": [ { "category": "external", "summary": "web.nvd.nist.gov", "url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2020-6652" }, { "category": "external", "summary": "www.first.org", "url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H" } ], "remediations": [ { "category": "vendor_fix", "details": "Eaton has released Intelligent Power Manager v1.68 to address the reported vulnerabilities.", "product_ids": [ "CSAFPID-0001" ], "url": "https://www.eaton.com/us/en-us/catalog/backup-power-ups-surge-it-power-distribution/eaton-intelligent-power-manager/download-eaton-intelligent-power-manager-ipm.html" }, { "category": "vendor_fix", "details": "To prevent the exploitation of the issues and safeguard the software from malicious entities, Eaton recommends blocking Ports 4679 and 4680 at the enterprise network or home network where Intelligent Power Manager software is installed and used.", "product_ids": [ "CSAFPID-0001" ] }, { "category": "mitigation", "details": "For additional information please see the Eaton Vulnerability Advisory.", "product_ids": [ "CSAFPID-0001" ], "url": "https://www.eaton.com/content/dam/eaton/company/news-insights/cybersecurity/security-bulletins/eaton-vulnerability-advisory-intelligent-power-manager-v1-1.pdf" } ], "scores": [ { "cvss_v3": { "baseScore": 7.8, "baseSeverity": "HIGH", "vectorString": "CVSS:3.0/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H", "version": "3.0" }, "products": [ "CSAFPID-0001" ] } ] } ] }
Loading...
Loading...
Sightings
Author | Source | Type | Date |
---|
Nomenclature
- Seen: The vulnerability was mentioned, discussed, or seen somewhere by the user.
- Confirmed: The vulnerability is confirmed from an analyst perspective.
- Exploited: This vulnerability was exploited and seen by the user reporting the sighting.
- Patched: This vulnerability was successfully patched by the user reporting the sighting.
- Not exploited: This vulnerability was not exploited or seen by the user reporting the sighting.
- Not confirmed: The user expresses doubt about the veracity of the vulnerability.
- Not patched: This vulnerability was not successfully patched by the user reporting the sighting.