icsa-21-110-06
Vulnerability from csaf_cisa
Published
2021-04-20 00:00
Modified
2021-04-20 00:00
Summary
Eaton Intelligent Power Manager

Notes

CISA Disclaimer
This CSAF advisory was extracted from unstructured data and may contain inaccuracies. If you notice any errors, please reach out to the designated contact at CISA CSAF: central@cisa.dhs.gov
Legal Notice
All information products included in https://us-cert.cisa.gov/ics are provided "as is" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see https://us-cert.cisa.gov/tlp/.
Risk evaluation
Successful exploitation of these vulnerabilities could allow attackers to change certain settings, upload code, delete files, or execute commands.
Critical infrastructure sectors
Energy
Countries/areas deployed
Worldwide
Company headquarters location
Ireland
Recommended Practices
CISA recommends users take defensive measures to minimize the risk of exploitation of these vulnerabilities. CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures. CISA also provides a section for control systems security recommended practices on the ICS webpage onus-cert.cisa.gov. Several recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.
Recommended Practices
Additional mitigation guidance and recommended practices are publicly available on the ICS webpage on us-cert.cisa.gov in the Technical Information Paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies. Organizations observing any suspected malicious activity should follow their established internal procedures and report their findings to CISA for tracking and correlation against other incidents.
Exploitability
No known public exploits specifically target these vulnerabilities.



{
  "document": {
    "acknowledgments": [
      {
        "names": [
          "Amir Preminger"
        ],
        "organization": "Claroty",
        "summary": "reporting these vulnerabilities to Eaton"
      }
    ],
    "category": "csaf_security_advisory",
    "csaf_version": "2.0",
    "distribution": {
      "text": "Disclosure is not limited",
      "tlp": {
        "label": "WHITE",
        "url": "https://us-cert.cisa.gov/tlp/"
      }
    },
    "lang": "en-US",
    "notes": [
      {
        "category": "general",
        "text": "This CSAF advisory was extracted from unstructured data and may contain inaccuracies. If you notice any errors, please reach out to the designated contact at CISA CSAF: central@cisa.dhs.gov",
        "title": "CISA Disclaimer"
      },
      {
        "category": "legal_disclaimer",
        "text": "All information products included in https://us-cert.cisa.gov/ics are provided \"as is\" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see https://us-cert.cisa.gov/tlp/.",
        "title": "Legal Notice"
      },
      {
        "category": "summary",
        "text": "Successful exploitation of these vulnerabilities could allow attackers to change certain settings, upload code, delete files, or execute commands.",
        "title": "Risk evaluation"
      },
      {
        "category": "other",
        "text": "Energy",
        "title": "Critical infrastructure sectors"
      },
      {
        "category": "other",
        "text": "Worldwide",
        "title": "Countries/areas deployed"
      },
      {
        "category": "other",
        "text": "Ireland",
        "title": "Company headquarters location"
      },
      {
        "category": "general",
        "text": "CISA recommends users take defensive measures to minimize the risk of exploitation of these vulnerabilities. CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.\nCISA also provides a section for control systems security recommended practices on the ICS webpage onus-cert.cisa.gov. Several recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.",
        "title": "Recommended Practices"
      },
      {
        "category": "general",
        "text": "Additional mitigation guidance and recommended practices are publicly available on the ICS webpage on us-cert.cisa.gov in the Technical Information Paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.\nOrganizations observing any suspected malicious activity should follow their established internal procedures and report their findings to CISA for tracking and correlation against other incidents.",
        "title": "Recommended Practices"
      },
      {
        "category": "other",
        "text": "No known public exploits specifically target these vulnerabilities.",
        "title": "Exploitability"
      }
    ],
    "publisher": {
      "category": "coordinator",
      "contact_details": "Email: CISAservicedesk@cisa.dhs.gov;\n Toll Free: 1-888-282-0870",
      "name": "CISA",
      "namespace": "https://www.cisa.gov/"
    },
    "references": [
      {
        "category": "self",
        "summary": "ICS Advisory ICSA-21-110-06 JSON",
        "url": "https://raw.githubusercontent.com/cisagov/CSAF/develop/csaf_files/OT/white/2021/icsa-21-110-06.json"
      },
      {
        "category": "self",
        "summary": "ICS Advisory ICSA-21-110-06 Web Version",
        "url": "https://www.cisa.gov/news-events/ics-advisories/icsa-21-110-06"
      },
      {
        "category": "external",
        "summary": "Recommended Practices",
        "url": "https://us-cert.cisa.gov/sites/default/files/recommended_practices/NCCIC_ICS-CERT_Defense_in_Depth_2016_S508C.pdf"
      },
      {
        "category": "external",
        "summary": "Recommended Practices",
        "url": "https://us-cert.cisa.gov/ics/tips/ICS-TIP-12-146-01B"
      }
    ],
    "title": "Eaton Intelligent Power Manager",
    "tracking": {
      "current_release_date": "2021-04-20T00:00:00.000000Z",
      "generator": {
        "engine": {
          "name": "CISA CSAF Generator",
          "version": "1.0.0"
        }
      },
      "id": "ICSA-21-110-06",
      "initial_release_date": "2021-04-20T00:00:00.000000Z",
      "revision_history": [
        {
          "date": "2021-04-20T00:00:00.000000Z",
          "legacy_version": "Initial",
          "number": "1",
          "summary": "ICSA-21-110-06 Eaton Intelligent Power Manager"
        }
      ],
      "status": "final",
      "version": "1"
    }
  },
  "product_tree": {
    "branches": [
      {
        "branches": [
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "\u003c 1.68",
                "product": {
                  "name": "Eaton Intelligent Power Protector (IPP) : All versions prior to 1.68",
                  "product_id": "CSAFPID-0001"
                }
              }
            ],
            "category": "product_name",
            "name": "Eaton Intelligent Power Protector (IPP)"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "\u003c 1.69",
                "product": {
                  "name": "Eaton Intelligent Power Manager (IPM): All versions prior to 1.69",
                  "product_id": "CSAFPID-0002"
                }
              }
            ],
            "category": "product_name",
            "name": "Eaton Intelligent Power Manager (IPM)"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "\u003c 1.69",
                "product": {
                  "name": "Eaton Intelligent Power Manager Virtual Appliance (IPM VA): All versions prior to 1.69",
                  "product_id": "CSAFPID-0003"
                }
              }
            ],
            "category": "product_name",
            "name": "Eaton Intelligent Power Manager Virtual Appliance (IPM VA)"
          }
        ],
        "category": "vendor",
        "name": "Eaton"
      }
    ]
  },
  "vulnerabilities": [
    {
      "cve": "CVE-2021-23276",
      "cwe": {
        "id": "CWE-89",
        "name": "Improper Neutralization of Special Elements used in an SQL Command (\u0027SQL Injection\u0027)"
      },
      "notes": [
        {
          "category": "summary",
          "text": "Eaton Intelligent Power Manager (IPM) prior to 1.69 is vulnerable to authenticated SQL injection. A malicious user can send a specially crafted packet to exploit this vulnerability. Successful exploitation of this vulnerability can allow attackers to add users in the data base.CVE-2021-23276 has been assigned to this vulnerability. A CVSS v3 base score of 7.1 has been calculated; the CVSS vector string is (AV:A/AC:H/PR:L/UI:N/S:U/C:H/I:H/A:H).",
          "title": "Vulnerability Summary"
        }
      ],
      "product_status": {
        "known_affected": [
          "CSAFPID-0001",
          "CSAFPID-0002",
          "CSAFPID-0003"
        ]
      },
      "references": [
        {
          "category": "external",
          "summary": "web.nvd.nist.gov",
          "url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2021-23276"
        },
        {
          "category": "external",
          "summary": "www.first.org",
          "url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:A/AC:H/PR:L/UI:N/S:U/C:H/I:H/A:H"
        }
      ],
      "remediations": [
        {
          "category": "mitigation",
          "details": "Eaton IPM v1.69: Download | IPM | Eaton",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ],
          "url": "https://www.eaton.com/us/en-us/catalog/backup-power-ups-surge-it-power-distribution/eaton-intelligent-power-manager/download-eaton-intelligent-power-manager-ipm.html"
        },
        {
          "category": "mitigation",
          "details": "Eaton IPP v1.68: Download software | Power management | Eaton",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ],
          "url": "https://www.eaton.com/us/en-us/products/backup-power-ups-surge-it-power-distribution/software-downloads.html"
        },
        {
          "category": "mitigation",
          "details": "To prevent the exploitation of the issues and safeguard the software from malicious entities, Eaton recommends blocking Ports 4679 and 4680 at the enterprise network or home network where Intelligent Power Manager (IPM) software is installed and used.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        },
        {
          "category": "mitigation",
          "details": "Please see Eaton vulnerability advisory number ETN-VA-2021-1000 for more information.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ],
          "url": "https://www.eaton.com/content/dam/eaton/company/news-insights/cybersecurity/security-bulletins/eaton-intelligent-power-manager-ipm-vulnerability-advisory.pdf"
        },
        {
          "category": "mitigation",
          "details": "Restrict exposure to external networks for all control system devices and/or systems and ensure they are not directly accessible from the open Internet.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        },
        {
          "category": "mitigation",
          "details": "Deploy control system networks and remote devices behind barrier devices (e.g., firewalls, data diodes) and isolate them from business networks.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        },
        {
          "category": "mitigation",
          "details": "Remote access to control system networks should be made available on a strict need-to-use basis. Remote access should use secure methods, such as virtual private networks (VPNs) updated to the most current version available.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        },
        {
          "category": "mitigation",
          "details": "Regularly update/patch software/applications to latest versions available, as applicable.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        },
        {
          "category": "mitigation",
          "details": "Enable audit logs on all devices and applications.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        },
        {
          "category": "mitigation",
          "details": "Disable/deactivate unused communication channels, TCP/UDP ports and services (e.g., SNMP, FTP, BootP, DHCP, etc.) on networked devices.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        },
        {
          "category": "mitigation",
          "details": "Create security zones for devices with common security requirements using barrier devices (e.g., firewalls, data diodes).",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        },
        {
          "category": "mitigation",
          "details": "Change default passwords following initial startup. Use complex secure passwords or passphrases.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        },
        {
          "category": "mitigation",
          "details": "Perform regular security assessments and risk analysis of networked control systems.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "baseScore": 7.1,
            "baseSeverity": "HIGH",
            "vectorString": "CVSS:3.0/AV:A/AC:H/PR:L/UI:N/S:U/C:H/I:H/A:H",
            "version": "3.0"
          },
          "products": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        }
      ]
    },
    {
      "cve": "CVE-2021-23277",
      "cwe": {
        "id": "CWE-95",
        "name": "Improper Neutralization of Directives in Dynamically Evaluated Code (\u0027Eval Injection\u0027)"
      },
      "notes": [
        {
          "category": "summary",
          "text": "Eaton Intelligent Power Manager (IPM) prior to 1.69 is vulnerable to an unauthenticated eval injection vulnerability. The software does not neutralize code syntax from users before using in the dynamic evaluation call in the loadUserFile function under scripts/libs/utils.js. Successful exploitation can allow attackers to control the input to the function and execute attacker-controlled commands.CVE-2021-23277 has been assigned to this vulnerability. A CVSS v3 base score of 8.3 has been calculated; the CVSS vector string is (AV:A/AC:H/PR:N/UI:N/S:C/C:H/I:H/A:H).",
          "title": "Vulnerability Summary"
        }
      ],
      "product_status": {
        "known_affected": [
          "CSAFPID-0001",
          "CSAFPID-0002",
          "CSAFPID-0003"
        ]
      },
      "references": [
        {
          "category": "external",
          "summary": "web.nvd.nist.gov",
          "url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2021-23277"
        },
        {
          "category": "external",
          "summary": "www.first.org",
          "url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:A/AC:H/PR:N/UI:N/S:C/C:H/I:H/A:H"
        }
      ],
      "remediations": [
        {
          "category": "mitigation",
          "details": "Eaton IPM v1.69: Download | IPM | Eaton",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ],
          "url": "https://www.eaton.com/us/en-us/catalog/backup-power-ups-surge-it-power-distribution/eaton-intelligent-power-manager/download-eaton-intelligent-power-manager-ipm.html"
        },
        {
          "category": "mitigation",
          "details": "Eaton IPP v1.68: Download software | Power management | Eaton",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ],
          "url": "https://www.eaton.com/us/en-us/products/backup-power-ups-surge-it-power-distribution/software-downloads.html"
        },
        {
          "category": "mitigation",
          "details": "To prevent the exploitation of the issues and safeguard the software from malicious entities, Eaton recommends blocking Ports 4679 and 4680 at the enterprise network or home network where Intelligent Power Manager (IPM) software is installed and used.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        },
        {
          "category": "mitigation",
          "details": "Please see Eaton vulnerability advisory number ETN-VA-2021-1000 for more information.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ],
          "url": "https://www.eaton.com/content/dam/eaton/company/news-insights/cybersecurity/security-bulletins/eaton-intelligent-power-manager-ipm-vulnerability-advisory.pdf"
        },
        {
          "category": "mitigation",
          "details": "Restrict exposure to external networks for all control system devices and/or systems and ensure they are not directly accessible from the open Internet.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        },
        {
          "category": "mitigation",
          "details": "Deploy control system networks and remote devices behind barrier devices (e.g., firewalls, data diodes) and isolate them from business networks.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        },
        {
          "category": "mitigation",
          "details": "Remote access to control system networks should be made available on a strict need-to-use basis. Remote access should use secure methods, such as virtual private networks (VPNs) updated to the most current version available.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        },
        {
          "category": "mitigation",
          "details": "Regularly update/patch software/applications to latest versions available, as applicable.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        },
        {
          "category": "mitigation",
          "details": "Enable audit logs on all devices and applications.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        },
        {
          "category": "mitigation",
          "details": "Disable/deactivate unused communication channels, TCP/UDP ports and services (e.g., SNMP, FTP, BootP, DHCP, etc.) on networked devices.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        },
        {
          "category": "mitigation",
          "details": "Create security zones for devices with common security requirements using barrier devices (e.g., firewalls, data diodes).",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        },
        {
          "category": "mitigation",
          "details": "Change default passwords following initial startup. Use complex secure passwords or passphrases.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        },
        {
          "category": "mitigation",
          "details": "Perform regular security assessments and risk analysis of networked control systems.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "baseScore": 8.3,
            "baseSeverity": "HIGH",
            "vectorString": "CVSS:3.0/AV:A/AC:H/PR:N/UI:N/S:C/C:H/I:H/A:H",
            "version": "3.0"
          },
          "products": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        }
      ]
    },
    {
      "cve": "CVE-2021-23278",
      "cwe": {
        "id": "CWE-20",
        "name": "Improper Input Validation"
      },
      "notes": [
        {
          "category": "summary",
          "text": "Eaton Intelligent Power Manager (IPM) prior to 1.69 is vulnerable to an authenticated arbitrary file delete vulnerability induced due to improper input validation at server/maps_srv.js with the removeBackground function and server/node_upgrade_srv.js with the removeFirmware function. An attacker can send specially crafted packets to delete the files on the system where IPM software is installed.CVE-2021-23278 has been assigned to this vulnerability. A CVSS v3 base score of 8.7 has been calculated; the CVSS vector string is (AV:A/AC:L/PR:L/UI:N/S:C/C:N/I:H/A:H).",
          "title": "Vulnerability Summary"
        }
      ],
      "product_status": {
        "known_affected": [
          "CSAFPID-0001",
          "CSAFPID-0002",
          "CSAFPID-0003"
        ]
      },
      "references": [
        {
          "category": "external",
          "summary": "web.nvd.nist.gov",
          "url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2021-23278"
        },
        {
          "category": "external",
          "summary": "www.first.org",
          "url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:A/AC:L/PR:L/UI:N/S:C/C:N/I:H/A:H"
        }
      ],
      "remediations": [
        {
          "category": "mitigation",
          "details": "Eaton IPM v1.69: Download | IPM | Eaton",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ],
          "url": "https://www.eaton.com/us/en-us/catalog/backup-power-ups-surge-it-power-distribution/eaton-intelligent-power-manager/download-eaton-intelligent-power-manager-ipm.html"
        },
        {
          "category": "mitigation",
          "details": "Eaton IPP v1.68: Download software | Power management | Eaton",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ],
          "url": "https://www.eaton.com/us/en-us/products/backup-power-ups-surge-it-power-distribution/software-downloads.html"
        },
        {
          "category": "mitigation",
          "details": "To prevent the exploitation of the issues and safeguard the software from malicious entities, Eaton recommends blocking Ports 4679 and 4680 at the enterprise network or home network where Intelligent Power Manager (IPM) software is installed and used.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        },
        {
          "category": "mitigation",
          "details": "Please see Eaton vulnerability advisory number ETN-VA-2021-1000 for more information.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ],
          "url": "https://www.eaton.com/content/dam/eaton/company/news-insights/cybersecurity/security-bulletins/eaton-intelligent-power-manager-ipm-vulnerability-advisory.pdf"
        },
        {
          "category": "mitigation",
          "details": "Restrict exposure to external networks for all control system devices and/or systems and ensure they are not directly accessible from the open Internet.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        },
        {
          "category": "mitigation",
          "details": "Deploy control system networks and remote devices behind barrier devices (e.g., firewalls, data diodes) and isolate them from business networks.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        },
        {
          "category": "mitigation",
          "details": "Remote access to control system networks should be made available on a strict need-to-use basis. Remote access should use secure methods, such as virtual private networks (VPNs) updated to the most current version available.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        },
        {
          "category": "mitigation",
          "details": "Regularly update/patch software/applications to latest versions available, as applicable.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        },
        {
          "category": "mitigation",
          "details": "Enable audit logs on all devices and applications.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        },
        {
          "category": "mitigation",
          "details": "Disable/deactivate unused communication channels, TCP/UDP ports and services (e.g., SNMP, FTP, BootP, DHCP, etc.) on networked devices.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        },
        {
          "category": "mitigation",
          "details": "Create security zones for devices with common security requirements using barrier devices (e.g., firewalls, data diodes).",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        },
        {
          "category": "mitigation",
          "details": "Change default passwords following initial startup. Use complex secure passwords or passphrases.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        },
        {
          "category": "mitigation",
          "details": "Perform regular security assessments and risk analysis of networked control systems.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "baseScore": 8.7,
            "baseSeverity": "HIGH",
            "vectorString": "CVSS:3.0/AV:A/AC:L/PR:L/UI:N/S:C/C:N/I:H/A:H",
            "version": "3.0"
          },
          "products": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        }
      ]
    },
    {
      "cve": "CVE-2021-23279",
      "cwe": {
        "id": "CWE-20",
        "name": "Improper Input Validation"
      },
      "notes": [
        {
          "category": "summary",
          "text": "Eaton Intelligent Power Manager (IPM) prior to 1.69 is vulnerable to an unauthenticated arbitrary file delete vulnerability induced due to improper input validation in meta_driver_srv.js class with the saveDriverData function using invalidated driverID. An attacker can send specially crafted packets to delete the files on the system where IPM software is installed.CVE-2021-23279 has been assigned to this vulnerability. A CVSS v3 base score of 8.0 has been calculated; the CVSS vector string is (AV:A/AC:H/PR:N/UI:N/S:C/C:N/I:H/A:H).",
          "title": "Vulnerability Summary"
        }
      ],
      "product_status": {
        "known_affected": [
          "CSAFPID-0001",
          "CSAFPID-0002",
          "CSAFPID-0003"
        ]
      },
      "references": [
        {
          "category": "external",
          "summary": "web.nvd.nist.gov",
          "url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2021-23279"
        },
        {
          "category": "external",
          "summary": "www.first.org",
          "url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:A/AC:H/PR:N/UI:N/S:C/C:N/I:H/A:H"
        }
      ],
      "remediations": [
        {
          "category": "mitigation",
          "details": "Eaton IPM v1.69: Download | IPM | Eaton",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ],
          "url": "https://www.eaton.com/us/en-us/catalog/backup-power-ups-surge-it-power-distribution/eaton-intelligent-power-manager/download-eaton-intelligent-power-manager-ipm.html"
        },
        {
          "category": "mitigation",
          "details": "Eaton IPP v1.68: Download software | Power management | Eaton",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ],
          "url": "https://www.eaton.com/us/en-us/products/backup-power-ups-surge-it-power-distribution/software-downloads.html"
        },
        {
          "category": "mitigation",
          "details": "To prevent the exploitation of the issues and safeguard the software from malicious entities, Eaton recommends blocking Ports 4679 and 4680 at the enterprise network or home network where Intelligent Power Manager (IPM) software is installed and used.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        },
        {
          "category": "mitigation",
          "details": "Please see Eaton vulnerability advisory number ETN-VA-2021-1000 for more information.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ],
          "url": "https://www.eaton.com/content/dam/eaton/company/news-insights/cybersecurity/security-bulletins/eaton-intelligent-power-manager-ipm-vulnerability-advisory.pdf"
        },
        {
          "category": "mitigation",
          "details": "Restrict exposure to external networks for all control system devices and/or systems and ensure they are not directly accessible from the open Internet.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        },
        {
          "category": "mitigation",
          "details": "Deploy control system networks and remote devices behind barrier devices (e.g., firewalls, data diodes) and isolate them from business networks.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        },
        {
          "category": "mitigation",
          "details": "Remote access to control system networks should be made available on a strict need-to-use basis. Remote access should use secure methods, such as virtual private networks (VPNs) updated to the most current version available.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        },
        {
          "category": "mitigation",
          "details": "Regularly update/patch software/applications to latest versions available, as applicable.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        },
        {
          "category": "mitigation",
          "details": "Enable audit logs on all devices and applications.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        },
        {
          "category": "mitigation",
          "details": "Disable/deactivate unused communication channels, TCP/UDP ports and services (e.g., SNMP, FTP, BootP, DHCP, etc.) on networked devices.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        },
        {
          "category": "mitigation",
          "details": "Create security zones for devices with common security requirements using barrier devices (e.g., firewalls, data diodes).",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        },
        {
          "category": "mitigation",
          "details": "Change default passwords following initial startup. Use complex secure passwords or passphrases.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        },
        {
          "category": "mitigation",
          "details": "Perform regular security assessments and risk analysis of networked control systems.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "baseScore": 8.0,
            "baseSeverity": "HIGH",
            "vectorString": "CVSS:3.0/AV:A/AC:H/PR:N/UI:N/S:C/C:N/I:H/A:H",
            "version": "3.0"
          },
          "products": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        }
      ]
    },
    {
      "cve": "CVE-2021-23280",
      "cwe": {
        "id": "CWE-434",
        "name": "Unrestricted Upload of File with Dangerous Type"
      },
      "notes": [
        {
          "category": "summary",
          "text": "Eaton Intelligent Power Manager (IPM) prior to 1.69 is vulnerable to an authenticated arbitrary file upload vulnerability. IPM \u0027s maps_srv.js allows an attacker to upload a malicious NodeJS file using the uploadBackground function. An attacker can upload a malicious code or execute any command using a specially crafted packet to exploit the vulnerability.CVE-2021-23280 has been assigned to this vulnerability. A CVSS v3 base score of 8.0 has been calculated; the CVSS vector string is (AV:A/AC:H/PR:L/UI:N/S:C/C:H/I:H/A:H).",
          "title": "Vulnerability Summary"
        }
      ],
      "product_status": {
        "known_affected": [
          "CSAFPID-0001",
          "CSAFPID-0002",
          "CSAFPID-0003"
        ]
      },
      "references": [
        {
          "category": "external",
          "summary": "web.nvd.nist.gov",
          "url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2021-23280"
        },
        {
          "category": "external",
          "summary": "www.first.org",
          "url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:A/AC:H/PR:L/UI:N/S:C/C:H/I:H/A:H"
        }
      ],
      "remediations": [
        {
          "category": "mitigation",
          "details": "Eaton IPM v1.69: Download | IPM | Eaton",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ],
          "url": "https://www.eaton.com/us/en-us/catalog/backup-power-ups-surge-it-power-distribution/eaton-intelligent-power-manager/download-eaton-intelligent-power-manager-ipm.html"
        },
        {
          "category": "mitigation",
          "details": "Eaton IPP v1.68: Download software | Power management | Eaton",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ],
          "url": "https://www.eaton.com/us/en-us/products/backup-power-ups-surge-it-power-distribution/software-downloads.html"
        },
        {
          "category": "mitigation",
          "details": "To prevent the exploitation of the issues and safeguard the software from malicious entities, Eaton recommends blocking Ports 4679 and 4680 at the enterprise network or home network where Intelligent Power Manager (IPM) software is installed and used.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        },
        {
          "category": "mitigation",
          "details": "Please see Eaton vulnerability advisory number ETN-VA-2021-1000 for more information.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ],
          "url": "https://www.eaton.com/content/dam/eaton/company/news-insights/cybersecurity/security-bulletins/eaton-intelligent-power-manager-ipm-vulnerability-advisory.pdf"
        },
        {
          "category": "mitigation",
          "details": "Restrict exposure to external networks for all control system devices and/or systems and ensure they are not directly accessible from the open Internet.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        },
        {
          "category": "mitigation",
          "details": "Deploy control system networks and remote devices behind barrier devices (e.g., firewalls, data diodes) and isolate them from business networks.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        },
        {
          "category": "mitigation",
          "details": "Remote access to control system networks should be made available on a strict need-to-use basis. Remote access should use secure methods, such as virtual private networks (VPNs) updated to the most current version available.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        },
        {
          "category": "mitigation",
          "details": "Regularly update/patch software/applications to latest versions available, as applicable.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        },
        {
          "category": "mitigation",
          "details": "Enable audit logs on all devices and applications.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        },
        {
          "category": "mitigation",
          "details": "Disable/deactivate unused communication channels, TCP/UDP ports and services (e.g., SNMP, FTP, BootP, DHCP, etc.) on networked devices.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        },
        {
          "category": "mitigation",
          "details": "Create security zones for devices with common security requirements using barrier devices (e.g., firewalls, data diodes).",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        },
        {
          "category": "mitigation",
          "details": "Change default passwords following initial startup. Use complex secure passwords or passphrases.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        },
        {
          "category": "mitigation",
          "details": "Perform regular security assessments and risk analysis of networked control systems.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "baseScore": 8.0,
            "baseSeverity": "HIGH",
            "vectorString": "CVSS:3.0/AV:A/AC:H/PR:L/UI:N/S:C/C:H/I:H/A:H",
            "version": "3.0"
          },
          "products": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        }
      ]
    },
    {
      "cve": "CVE-2021-23281",
      "cwe": {
        "id": "CWE-94",
        "name": "Improper Control of Generation of Code (\u0027Code Injection\u0027)"
      },
      "notes": [
        {
          "category": "summary",
          "text": "Eaton Intelligent Power Manager (IPM) prior to 1.69 is vulnerable to an unauthenticated remote code execution vulnerability. IPM software does not sanitize the date provided via the coverterCheckList function in meta_driver_srv.js class. Attackers can send a specially crafted packet to make IPM connect to rouge SNMP server and execute attacker-controlled code.CVE-2021-23281 has been assigned to this vulnerability. A CVSS v3 base score of 8.3 has been calculated; the CVSS vector string is (AV:A/AC:H/PR:N/UI:N/S:C/C:H/I:H/A:H).",
          "title": "Vulnerability Summary"
        }
      ],
      "product_status": {
        "known_affected": [
          "CSAFPID-0001",
          "CSAFPID-0002",
          "CSAFPID-0003"
        ]
      },
      "references": [
        {
          "category": "external",
          "summary": "web.nvd.nist.gov",
          "url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2021-23281"
        },
        {
          "category": "external",
          "summary": "www.first.org",
          "url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:A/AC:H/PR:N/UI:N/S:C/C:H/I:H/A:H"
        }
      ],
      "remediations": [
        {
          "category": "mitigation",
          "details": "Eaton IPM v1.69: Download | IPM | Eaton",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ],
          "url": "https://www.eaton.com/us/en-us/catalog/backup-power-ups-surge-it-power-distribution/eaton-intelligent-power-manager/download-eaton-intelligent-power-manager-ipm.html"
        },
        {
          "category": "mitigation",
          "details": "Eaton IPP v1.68: Download software | Power management | Eaton",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ],
          "url": "https://www.eaton.com/us/en-us/products/backup-power-ups-surge-it-power-distribution/software-downloads.html"
        },
        {
          "category": "mitigation",
          "details": "To prevent the exploitation of the issues and safeguard the software from malicious entities, Eaton recommends blocking Ports 4679 and 4680 at the enterprise network or home network where Intelligent Power Manager (IPM) software is installed and used.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        },
        {
          "category": "mitigation",
          "details": "Please see Eaton vulnerability advisory number ETN-VA-2021-1000 for more information.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ],
          "url": "https://www.eaton.com/content/dam/eaton/company/news-insights/cybersecurity/security-bulletins/eaton-intelligent-power-manager-ipm-vulnerability-advisory.pdf"
        },
        {
          "category": "mitigation",
          "details": "Restrict exposure to external networks for all control system devices and/or systems and ensure they are not directly accessible from the open Internet.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        },
        {
          "category": "mitigation",
          "details": "Deploy control system networks and remote devices behind barrier devices (e.g., firewalls, data diodes) and isolate them from business networks.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        },
        {
          "category": "mitigation",
          "details": "Remote access to control system networks should be made available on a strict need-to-use basis. Remote access should use secure methods, such as virtual private networks (VPNs) updated to the most current version available.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        },
        {
          "category": "mitigation",
          "details": "Regularly update/patch software/applications to latest versions available, as applicable.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        },
        {
          "category": "mitigation",
          "details": "Enable audit logs on all devices and applications.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        },
        {
          "category": "mitigation",
          "details": "Disable/deactivate unused communication channels, TCP/UDP ports and services (e.g., SNMP, FTP, BootP, DHCP, etc.) on networked devices.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        },
        {
          "category": "mitigation",
          "details": "Create security zones for devices with common security requirements using barrier devices (e.g., firewalls, data diodes).",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        },
        {
          "category": "mitigation",
          "details": "Change default passwords following initial startup. Use complex secure passwords or passphrases.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        },
        {
          "category": "mitigation",
          "details": "Perform regular security assessments and risk analysis of networked control systems.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "baseScore": 8.3,
            "baseSeverity": "HIGH",
            "vectorString": "CVSS:3.0/AV:A/AC:H/PR:N/UI:N/S:C/C:H/I:H/A:H",
            "version": "3.0"
          },
          "products": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        }
      ]
    }
  ]
}


Log in or create an account to share your comment.




Tags
Taxonomy of the tags.


Loading...

Loading...

Loading...

Sightings

Author Source Type Date

Nomenclature

  • Seen: The vulnerability was mentioned, discussed, or seen somewhere by the user.
  • Confirmed: The vulnerability is confirmed from an analyst perspective.
  • Exploited: This vulnerability was exploited and seen by the user reporting the sighting.
  • Patched: This vulnerability was successfully patched by the user reporting the sighting.
  • Not exploited: This vulnerability was not exploited or seen by the user reporting the sighting.
  • Not confirmed: The user expresses doubt about the veracity of the vulnerability.
  • Not patched: This vulnerability was not successfully patched by the user reporting the sighting.