icsa-21-147-05
Vulnerability from csaf_cisa
Published
2021-05-27 00:00
Modified
2021-05-27 00:00
Summary
Mitsubishi Electric MELSEC iQ-R Series

Notes

CISA Disclaimer
This CSAF advisory was extracted from unstructured data and may contain inaccuracies. If you notice any errors, please reach out to the designated contact at CISA CSAF: central@cisa.dhs.gov
Legal Notice
All information products included in https://us-cert.cisa.gov/ics are provided "as is" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see https://us-cert.cisa.gov/tlp/.
Risk evaluation
Successful exploitation of this vulnerability may prevent legitimate clients from connecting to an affected product.
Critical infrastructure sectors
Critical Manufacturing
Countries/areas deployed
Worldwide
Company headquarters location
Japan
Recommended Practices
CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures. CISA also provides a section for control systems security recommended practices on the ICS webpage onus-cert.cisa.gov. Several recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.
Recommended Practices
Additional mitigation guidance and recommended practices are publicly available on the ICS webpage on us-cert.cisa.gov in the Technical Information Paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies. Organizations observing any suspected malicious activity should follow their established internal procedures and report their findings to CISA for tracking and correlation against other incidents.
Exploitability
No known public exploits specifically target this vulnerability.



{
  "document": {
    "acknowledgments": [
      {
        "names": [
          "Younes Dragoni"
        ],
        "organization": "Nozomi Networks",
        "summary": "reporting this vulnerability to CISA"
      }
    ],
    "category": "csaf_security_advisory",
    "csaf_version": "2.0",
    "distribution": {
      "text": "Disclosure is not limited",
      "tlp": {
        "label": "WHITE",
        "url": "https://us-cert.cisa.gov/tlp/"
      }
    },
    "lang": "en-US",
    "notes": [
      {
        "category": "general",
        "text": "This CSAF advisory was extracted from unstructured data and may contain inaccuracies. If you notice any errors, please reach out to the designated contact at CISA CSAF: central@cisa.dhs.gov",
        "title": "CISA Disclaimer"
      },
      {
        "category": "legal_disclaimer",
        "text": "All information products included in https://us-cert.cisa.gov/ics are provided \"as is\" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see https://us-cert.cisa.gov/tlp/.",
        "title": "Legal Notice"
      },
      {
        "category": "summary",
        "text": "Successful exploitation of this vulnerability may prevent legitimate clients from connecting to an affected product.",
        "title": "Risk evaluation"
      },
      {
        "category": "other",
        "text": "Critical Manufacturing",
        "title": "Critical infrastructure sectors"
      },
      {
        "category": "other",
        "text": "Worldwide",
        "title": "Countries/areas deployed"
      },
      {
        "category": "other",
        "text": "Japan",
        "title": "Company headquarters location"
      },
      {
        "category": "general",
        "text": "CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.\nCISA also provides a section for control systems security recommended practices on the ICS webpage onus-cert.cisa.gov. Several recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.",
        "title": "Recommended Practices"
      },
      {
        "category": "general",
        "text": "Additional mitigation guidance and recommended practices are publicly available on the ICS webpage on us-cert.cisa.gov in the Technical Information Paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.\nOrganizations observing any suspected malicious activity should follow their established internal procedures and report their findings to CISA for tracking and correlation against other incidents.",
        "title": "Recommended Practices"
      },
      {
        "category": "other",
        "text": "No known public exploits specifically target this vulnerability.",
        "title": "Exploitability"
      }
    ],
    "publisher": {
      "category": "coordinator",
      "contact_details": "Email: CISAservicedesk@cisa.dhs.gov;\n Toll Free: 1-888-282-0870",
      "name": "CISA",
      "namespace": "https://www.cisa.gov/"
    },
    "references": [
      {
        "category": "self",
        "summary": "ICS Advisory ICSA-21-147-05 JSON",
        "url": "https://raw.githubusercontent.com/cisagov/CSAF/develop/csaf_files/OT/white/2021/icsa-21-147-05.json"
      },
      {
        "category": "self",
        "summary": "ICS Advisory ICSA-21-147-05 Web Version",
        "url": "https://www.cisa.gov/news-events/ics-advisories/icsa-21-147-05"
      },
      {
        "category": "external",
        "summary": "Recommended Practices",
        "url": "https://us-cert.cisa.gov/sites/default/files/recommended_practices/NCCIC_ICS-CERT_Defense_in_Depth_2016_S508C.pdf"
      },
      {
        "category": "external",
        "summary": "Recommended Practices",
        "url": "https://us-cert.cisa.gov/ics/tips/ICS-TIP-12-146-01B"
      }
    ],
    "title": "Mitsubishi Electric MELSEC iQ-R Series",
    "tracking": {
      "current_release_date": "2021-05-27T00:00:00.000000Z",
      "generator": {
        "engine": {
          "name": "CISA CSAF Generator",
          "version": "1.0.0"
        }
      },
      "id": "ICSA-21-147-05",
      "initial_release_date": "2021-05-27T00:00:00.000000Z",
      "revision_history": [
        {
          "date": "2021-05-27T00:00:00.000000Z",
          "legacy_version": "Initial",
          "number": "1",
          "summary": "ICSA-21-147-05 Mitsubishi Electric MELSEC iQ-R Series"
        }
      ],
      "status": "final",
      "version": "1"
    }
  },
  "product_tree": {
    "branches": [
      {
        "branches": [
          {
            "branches": [
              {
                "category": "product_version",
                "name": "vers:all/*",
                "product": {
                  "name": "R08/16/32/120SFCPU: All versions",
                  "product_id": "CSAFPID-0001"
                }
              }
            ],
            "category": "product_name",
            "name": "R08/16/32/120SFCPU"
          },
          {
            "branches": [
              {
                "category": "product_version",
                "name": "vers:all/*",
                "product": {
                  "name": "R00/01/02CPU: All versions",
                  "product_id": "CSAFPID-0002"
                }
              }
            ],
            "category": "product_name",
            "name": "R00/01/02CPU"
          },
          {
            "branches": [
              {
                "category": "product_version",
                "name": "vers:all/*",
                "product": {
                  "name": "R08/16/32/120PCPU: All versions",
                  "product_id": "CSAFPID-0003"
                }
              }
            ],
            "category": "product_name",
            "name": "R08/16/32/120PCPU"
          },
          {
            "branches": [
              {
                "category": "product_version",
                "name": "vers:all/*",
                "product": {
                  "name": "R04/08/16/32/120(EN)CPU: All versions",
                  "product_id": "CSAFPID-0004"
                }
              }
            ],
            "category": "product_name",
            "name": "R04/08/16/32/120(EN)CPU"
          },
          {
            "branches": [
              {
                "category": "product_version",
                "name": "vers:all/*",
                "product": {
                  "name": "R08/16/32/120PSFCPU: All versions",
                  "product_id": "CSAFPID-0005"
                }
              }
            ],
            "category": "product_name",
            "name": "R08/16/32/120PSFCPU"
          }
        ],
        "category": "vendor",
        "name": "Mitsubishi Electric"
      }
    ]
  },
  "vulnerabilities": [
    {
      "cve": "CVE-2021-20591",
      "cwe": {
        "id": "CWE-400",
        "name": "Uncontrolled Resource Consumption"
      },
      "notes": [
        {
          "category": "summary",
          "text": "Due to improper session management, an attacker may prevent legitimate clients from connecting to an affected product by not properly closing a connection. If multiple MELSOFT transmission ports (TCP/IP) are open, the other ports are not affected. Sequence control is not affected by this vulnerability.CVE-2021-20591 has been assigned to this vulnerability. A CVSS v3 base score of 5.3 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:L).",
          "title": "Vulnerability Summary"
        }
      ],
      "product_status": {
        "known_affected": [
          "CSAFPID-0001",
          "CSAFPID-0002",
          "CSAFPID-0003",
          "CSAFPID-0004",
          "CSAFPID-0005"
        ]
      },
      "references": [
        {
          "category": "external",
          "summary": "web.nvd.nist.gov",
          "url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2021-20591"
        },
        {
          "category": "external",
          "summary": "www.first.org",
          "url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:L"
        }
      ],
      "remediations": [
        {
          "category": "mitigation",
          "details": "Use a firewall, a virtual private network (VPN), etc., to prevent unauthorized access when Internet access is required.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005"
          ]
        },
        {
          "category": "mitigation",
          "details": "Use within a LAN and block access from untrusted networks and hosts through firewalls.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005"
          ]
        },
        {
          "category": "mitigation",
          "details": "Use the IP filter function to restrict the connectable IP addresses. See MELSEC iQ-R Ethernet User\u0027s Manual (Application) 1.13 Security \u201cIP filter\u201d for more information.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005"
          ]
        },
        {
          "category": "mitigation",
          "details": "Use the MELSOFT transmission port (UDP/IP).",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005"
          ]
        },
        {
          "category": "mitigation",
          "details": "If Port 5007 of the MELSOFT transmission port (TCP/IP) is not used, set b2 to \"1\" in advance. See MELSEC iQ-R Ethernet User\u0027s Manual (Application) Appendix 3, Buffer Memory for more information.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005"
          ]
        },
        {
          "category": "mitigation",
          "details": "If this vulnerability is exploited, legitimate users can recover by first disabling the port with the forced connection invalidation function and then re-enabling the port. For an example see MELSEC iQ-R Ethernet User\u0027s Manual (Application) Appendix 3, Buffer Memory.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005"
          ]
        },
        {
          "category": "mitigation",
          "details": "Please refer to the Mitsubishi Electric advisory for further details.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005"
          ],
          "url": "https://www.mitsubishielectric.com/en/psirt/vulnerability/pdf/2021-003_en.pdf"
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "baseScore": 5.3,
            "baseSeverity": "MEDIUM",
            "vectorString": "CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:L",
            "version": "3.0"
          },
          "products": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005"
          ]
        }
      ]
    }
  ]
}


Log in or create an account to share your comment.




Tags
Taxonomy of the tags.


Loading…

Loading…

Loading…

Sightings

Author Source Type Date

Nomenclature

  • Seen: The vulnerability was mentioned, discussed, or seen somewhere by the user.
  • Confirmed: The vulnerability is confirmed from an analyst perspective.
  • Exploited: This vulnerability was exploited and seen by the user reporting the sighting.
  • Patched: This vulnerability was successfully patched by the user reporting the sighting.
  • Not exploited: This vulnerability was not exploited or seen by the user reporting the sighting.
  • Not confirmed: The user expresses doubt about the veracity of the vulnerability.
  • Not patched: This vulnerability was not successfully patched by the user reporting the sighting.