icsa-21-315-03
Vulnerability from csaf_cisa
Published
2021-11-11 00:00
Modified
2022-05-12 00:00
Summary
Siemens SIMATIC WinCC (Update E)

Notes

CISA Disclaimer
This CSAF advisory was extracted from unstructured data and may contain inaccuracies. If you notice any errors, please reach out to the designated contact at CISA CSAF: central@cisa.dhs.gov
Legal Notice
All information products included in https://us-cert.cisa.gov/ics are provided "as is" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see https://us-cert.cisa.gov/tlp/.
Risk evaluation
Successful exploitation of these vulnerabilities could allow local attackers to escalate privileges, and read, write, or delete critical files.
Critical infrastructure sectors
Critical Manufacturing
Countries/areas deployed
Worldwide
Company headquarters location
Germany
Recommended Practices
CISA recommends users take defensive measures to minimize the risk of exploitation of these vulnerabilities. Specifically, users should: Minimize network exposure for all control system devices and/or systems, and ensure they are not accessible from the Internet; Locate control system networks and remote devices behind firewalls and isolate them from the business network; When remote access is required, use secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize VPN is only as secure as its connected devices.
Recommended Practices
CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures. CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics. Several recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.
Recommended Practices
Additional mitigation guidance and recommended practices are publicly available on the ICS webpage on cisa.gov/icsin the Technical Information Paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies. Organizations observing any suspected malicious activity should follow their established internal procedures and report their findings to CISA for tracking and correlation against other incidents.
Additional Resources
For further inquiries on security vulnerabilities in Siemens products and solutions, please contact the Siemens ProductCERT: https://www.siemens.com/cert/advisories
Exploitability
No known public exploits specifically target these vulnerabilities.



{
  "document": {
    "acknowledgments": [
      {
        "names": [
          "Thomas Riedmaier"
        ],
        "organization": "Siemens Energy",
        "summary": "reporting these vulnerabilities to Siemens"
      }
    ],
    "category": "csaf_security_advisory",
    "csaf_version": "2.0",
    "distribution": {
      "text": "Disclosure is not limited",
      "tlp": {
        "label": "WHITE",
        "url": "https://us-cert.cisa.gov/tlp/"
      }
    },
    "lang": "en-US",
    "notes": [
      {
        "category": "general",
        "text": "This CSAF advisory was extracted from unstructured data and may contain inaccuracies. If you notice any errors, please reach out to the designated contact at CISA CSAF: central@cisa.dhs.gov",
        "title": "CISA Disclaimer"
      },
      {
        "category": "legal_disclaimer",
        "text": "All information products included in https://us-cert.cisa.gov/ics are provided \"as is\" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see https://us-cert.cisa.gov/tlp/.",
        "title": "Legal Notice"
      },
      {
        "category": "summary",
        "text": "Successful exploitation of these vulnerabilities could allow local attackers to escalate privileges, and read, write, or delete critical files.",
        "title": "Risk evaluation"
      },
      {
        "category": "other",
        "text": "Critical Manufacturing",
        "title": "Critical infrastructure sectors"
      },
      {
        "category": "other",
        "text": "Worldwide",
        "title": "Countries/areas deployed"
      },
      {
        "category": "other",
        "text": "Germany",
        "title": "Company headquarters location"
      },
      {
        "category": "general",
        "text": "CISA recommends users take defensive measures to minimize the risk of exploitation of these vulnerabilities. Specifically, users should: Minimize network exposure for all control system devices and/or systems, and ensure they are not accessible from the Internet; Locate control system networks and remote devices behind firewalls and isolate them from the business network; When remote access is required, use secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize VPN is only as secure as its connected devices.",
        "title": "Recommended Practices"
      },
      {
        "category": "general",
        "text": "CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.\nCISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics. Several recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.",
        "title": "Recommended Practices"
      },
      {
        "category": "general",
        "text": "Additional mitigation guidance and recommended practices are publicly available on the ICS webpage on cisa.gov/icsin the Technical Information Paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.\nOrganizations observing any suspected malicious activity should follow their established internal procedures and report their findings to CISA for tracking and correlation against other incidents.",
        "title": "Recommended Practices"
      },
      {
        "category": "general",
        "text": "For further inquiries on security vulnerabilities in Siemens products and solutions, please contact the Siemens ProductCERT: https://www.siemens.com/cert/advisories",
        "title": "Additional Resources"
      },
      {
        "category": "other",
        "text": "No known public exploits specifically target these vulnerabilities.",
        "title": "Exploitability"
      }
    ],
    "publisher": {
      "category": "coordinator",
      "contact_details": "Email: CISAservicedesk@cisa.dhs.gov;\n Toll Free: 1-888-282-0870",
      "name": "CISA",
      "namespace": "https://www.cisa.gov/"
    },
    "references": [
      {
        "category": "external",
        "summary": "SSA-840188: Multiple Vulnerabilities in SIMATIC WinCC Affecting Other SIMATIC Software Products - CSAF Version",
        "url": "https://cert-portal.siemens.com/productcert/csaf/ssa-840188.json"
      },
      {
        "category": "self",
        "summary": "ICS Advisory ICSA-21-315-03 JSON",
        "url": "https://raw.githubusercontent.com/cisagov/CSAF/develop/csaf_files/OT/white/2021/icsa-21-315-03.json"
      },
      {
        "category": "self",
        "summary": "ICS Advisory ICSA-21-315-03 Web Version",
        "url": "https://www.cisa.gov/news-events/ics-advisories/icsa-21-315-03"
      },
      {
        "category": "external",
        "summary": "Recommended Practices",
        "url": "https://www.cisa.gov/uscert/ics/alerts/ICS-ALERT-10-301-01"
      },
      {
        "category": "external",
        "summary": "Recommended Practices",
        "url": "https://www.cisa.gov/uscert/sites/default/files/recommended_practices/NCCIC_ICS-CERT_Defense_in_Depth_2016_S508C.pdf"
      },
      {
        "category": "external",
        "summary": "Recommended Practices",
        "url": "https://www.cisa.gov/uscert/ics/tips/ICS-TIP-12-146-01B"
      },
      {
        "category": "external",
        "summary": "SSA-840188: Multiple Vulnerabilities in SIMATIC WinCC Affecting Other SIMATIC Software Products - HTML Version",
        "url": "https://cert-portal.siemens.com/productcert/html/ssa-840188.html"
      },
      {
        "category": "external",
        "summary": "SSA-840188: Multiple Vulnerabilities in SIMATIC WinCC Affecting Other SIMATIC Software Products - PDF Version",
        "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-840188.pdf"
      },
      {
        "category": "external",
        "summary": "SSA-840188: Multiple Vulnerabilities in SIMATIC WinCC Affecting Other SIMATIC Software Products - TXT Version",
        "url": "https://cert-portal.siemens.com/productcert/txt/ssa-840188.txt"
      }
    ],
    "title": "Siemens SIMATIC WinCC (Update E)",
    "tracking": {
      "current_release_date": "2022-05-12T00:00:00.000000Z",
      "generator": {
        "engine": {
          "name": "CISA CSAF Generator",
          "version": "1.0.0"
        }
      },
      "id": "ICSA-21-315-03",
      "initial_release_date": "2021-11-11T00:00:00.000000Z",
      "revision_history": [
        {
          "date": "2021-11-11T00:00:00.000000Z",
          "legacy_version": "Initial",
          "number": "1",
          "summary": "ICSA-21-315-03 Siemens SIMATIC WinCC"
        },
        {
          "date": "2022-02-10T00:00:00.000000Z",
          "legacy_version": "A",
          "number": "2",
          "summary": "ICSA-21-315-03 Siemens SIMATIC WinCC (Update A)"
        },
        {
          "date": "2022-03-10T00:00:00.000000Z",
          "legacy_version": "B",
          "number": "3",
          "summary": "ICSA-21-315-03 Siemens SIMATIC WinCC (Update B)"
        },
        {
          "date": "2022-04-14T00:00:00.000000Z",
          "legacy_version": "C",
          "number": "4",
          "summary": "ICSA-21-315-03 Siemens SIMATIC WinCC (Update C)"
        },
        {
          "date": "2022-05-12T00:00:00.000000Z",
          "legacy_version": "D",
          "number": "5",
          "summary": "ICSA-21-315-03 Siemens SIMATIC WinCC (Update D)"
        }
      ],
      "status": "final",
      "version": "5"
    }
  },
  "product_tree": {
    "branches": [
      {
        "branches": [
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "vers:all/*",
                "product": {
                  "name": "OpenPCS 7 V8.2",
                  "product_id": "CSAFPID-0001"
                }
              }
            ],
            "category": "product_name",
            "name": "OpenPCS 7 V8.2"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "All versions \u003c V9.0 Upd4",
                "product": {
                  "name": "OpenPCS 7 V9.0",
                  "product_id": "CSAFPID-0002"
                }
              }
            ],
            "category": "product_name",
            "name": "OpenPCS 7 V9.0"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "vers:all/*",
                "product": {
                  "name": "OpenPCS 7 V9.1",
                  "product_id": "CSAFPID-0003"
                }
              }
            ],
            "category": "product_name",
            "name": "OpenPCS 7 V9.1"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "vers:all/*",
                "product": {
                  "name": "SIMATIC BATCH V8.2",
                  "product_id": "CSAFPID-0004"
                }
              }
            ],
            "category": "product_name",
            "name": "SIMATIC BATCH V8.2"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "vers:all/*",
                "product": {
                  "name": "SIMATIC BATCH V9.0",
                  "product_id": "CSAFPID-0005"
                }
              }
            ],
            "category": "product_name",
            "name": "SIMATIC BATCH V9.0"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "vers:all/*",
                "product": {
                  "name": "SIMATIC BATCH V9.1",
                  "product_id": "CSAFPID-0006"
                }
              }
            ],
            "category": "product_name",
            "name": "SIMATIC BATCH V9.1"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "vers:all/*",
                "product": {
                  "name": "SIMATIC NET PC Software V14",
                  "product_id": "CSAFPID-0007"
                }
              }
            ],
            "category": "product_name",
            "name": "SIMATIC NET PC Software V14"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "vers:all/*",
                "product": {
                  "name": "SIMATIC NET PC Software V15",
                  "product_id": "CSAFPID-0008"
                }
              }
            ],
            "category": "product_name",
            "name": "SIMATIC NET PC Software V15"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "All versions \u003c V16 Update 6",
                "product": {
                  "name": "SIMATIC NET PC Software V16",
                  "product_id": "CSAFPID-0009"
                }
              }
            ],
            "category": "product_name",
            "name": "SIMATIC NET PC Software V16"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "All versions \u003c V17 SP1",
                "product": {
                  "name": "SIMATIC NET PC Software V17",
                  "product_id": "CSAFPID-00010"
                }
              }
            ],
            "category": "product_name",
            "name": "SIMATIC NET PC Software V17"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "vers:all/*",
                "product": {
                  "name": "SIMATIC PCS 7 V8.2",
                  "product_id": "CSAFPID-00011"
                }
              }
            ],
            "category": "product_name",
            "name": "SIMATIC PCS 7 V8.2"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "All versions \u003c V9.0 SP3 UC04",
                "product": {
                  "name": "SIMATIC PCS 7 V9.0",
                  "product_id": "CSAFPID-00012"
                }
              }
            ],
            "category": "product_name",
            "name": "SIMATIC PCS 7 V9.0"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "All versions \u003c V9.1 SP1",
                "product": {
                  "name": "SIMATIC PCS 7 V9.1",
                  "product_id": "CSAFPID-00013"
                }
              }
            ],
            "category": "product_name",
            "name": "SIMATIC PCS 7 V9.1"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "vers:all/*",
                "product": {
                  "name": "SIMATIC Route Control V8.2",
                  "product_id": "CSAFPID-00014"
                }
              }
            ],
            "category": "product_name",
            "name": "SIMATIC Route Control V8.2"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "vers:all/*",
                "product": {
                  "name": "SIMATIC Route Control V9.0",
                  "product_id": "CSAFPID-00015"
                }
              }
            ],
            "category": "product_name",
            "name": "SIMATIC Route Control V9.0"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "vers:all/*",
                "product": {
                  "name": "SIMATIC Route Control V9.1",
                  "product_id": "CSAFPID-00016"
                }
              }
            ],
            "category": "product_name",
            "name": "SIMATIC Route Control V9.1"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "All versions \u003c V15 SP1 Update 7",
                "product": {
                  "name": "SIMATIC WinCC V15 and earlier",
                  "product_id": "CSAFPID-00017"
                }
              }
            ],
            "category": "product_name",
            "name": "SIMATIC WinCC V15 and earlier"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "All versions \u003c V16 Update 5",
                "product": {
                  "name": "SIMATIC WinCC V16",
                  "product_id": "CSAFPID-00018"
                }
              }
            ],
            "category": "product_name",
            "name": "SIMATIC WinCC V16"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "All versions \u003c V17 Update 2",
                "product": {
                  "name": "SIMATIC WinCC V17",
                  "product_id": "CSAFPID-00019"
                }
              }
            ],
            "category": "product_name",
            "name": "SIMATIC WinCC V17"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "All versions \u003c V7.4 SP1 Update 19",
                "product": {
                  "name": "SIMATIC WinCC V7.4",
                  "product_id": "CSAFPID-00020"
                }
              }
            ],
            "category": "product_name",
            "name": "SIMATIC WinCC V7.4"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "All versions \u003c V7.5 SP2 Update 5",
                "product": {
                  "name": "SIMATIC WinCC V7.5",
                  "product_id": "CSAFPID-00021"
                }
              }
            ],
            "category": "product_name",
            "name": "SIMATIC WinCC V7.5"
          }
        ],
        "category": "vendor",
        "name": "Siemens"
      }
    ]
  },
  "vulnerabilities": [
    {
      "cve": "CVE-2021-40358",
      "cwe": {
        "id": "CWE-22",
        "name": "Improper Limitation of a Pathname to a Restricted Directory (\u0027Path Traversal\u0027)"
      },
      "notes": [
        {
          "category": "summary",
          "text": "Legitimate file operations on the web server of the affected systems do not properly neutralize special elements within the pathname. An attacker could then cause the pathname to resolve to a location outside of the restricted directory on the server and read, write or delete unexpected critical files. CVE-2021-40358 has been assigned to this vulnerability. A CVSS v3 base score of 9.9 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:L/UI:N/S:C/C:H/I:H/A:H).",
          "title": "Summary"
        }
      ],
      "product_status": {
        "known_affected": [
          "CSAFPID-00011",
          "CSAFPID-00012",
          "CSAFPID-00013",
          "CSAFPID-00017",
          "CSAFPID-00018",
          "CSAFPID-00019",
          "CSAFPID-00020",
          "CSAFPID-00021"
        ]
      },
      "references": [
        {
          "category": "external",
          "summary": "web.nvd.nist.gov",
          "url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2021-40358"
        },
        {
          "category": "external",
          "summary": "www.first.org",
          "url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:L/UI:N/S:C/C:H/I:H/A:H"
        }
      ],
      "remediations": [
        {
          "category": "mitigation",
          "details": "CVE-2021-40358: Disable the webserver or only enable it temporarily, when needed",
          "product_ids": [
            "CSAFPID-00011",
            "CSAFPID-00012",
            "CSAFPID-00013",
            "CSAFPID-00017",
            "CSAFPID-00018",
            "CSAFPID-00019",
            "CSAFPID-00020",
            "CSAFPID-00021"
          ]
        },
        {
          "category": "mitigation",
          "details": "To fix CVE-2021-40359 see chapter \"Additional Information\"",
          "product_ids": [
            "CSAFPID-00011",
            "CSAFPID-00012"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "Update to V8.2 SP1; then update SIMATIC WinCC to V7.4 SP1 Update 19 or later version to fix CVE-2021-40358 and CVE-2021-40364",
          "product_ids": [
            "CSAFPID-00011"
          ],
          "url": "https://support.industry.siemens.com/cs/ww/en/view/109806846/"
        },
        {
          "category": "vendor_fix",
          "details": "Update to V15 SP1 Update 7 or later version",
          "product_ids": [
            "CSAFPID-00017"
          ],
          "url": "https://support.industry.siemens.com/cs/us/en/view/109763890/"
        },
        {
          "category": "vendor_fix",
          "details": "Update to V16 Update 5 or later version",
          "product_ids": [
            "CSAFPID-00018"
          ],
          "url": "https://support.industry.siemens.com/cs/ww/en/view/109776017/"
        },
        {
          "category": "vendor_fix",
          "details": "Update to V17 Update 2 or later version",
          "product_ids": [
            "CSAFPID-00019"
          ],
          "url": "https://support.industry.siemens.com/cs/ww/en/view/109784441/"
        },
        {
          "category": "vendor_fix",
          "details": "Update to V7.4 SP1 Update 19 or later version",
          "product_ids": [
            "CSAFPID-00020"
          ],
          "url": "https://support.industry.siemens.com/cs/ww/en/view/109806846/"
        },
        {
          "category": "vendor_fix",
          "details": "Update to V7.5 SP2 Update 5 or later version",
          "product_ids": [
            "CSAFPID-00021"
          ],
          "url": "https://support.industry.siemens.com/cs/ww/en/view/109793460/"
        },
        {
          "category": "vendor_fix",
          "details": "Update to V9.1 SP1 or later version",
          "product_ids": [
            "CSAFPID-00013"
          ],
          "url": "https://support.industry.siemens.com/cs/ww/en/view/109805073/"
        },
        {
          "category": "vendor_fix",
          "details": "Update to V9.0 SP3 UC04 or later version to fix CVE-2021-40358 and CVE-2021-40364",
          "product_ids": [
            "CSAFPID-00012"
          ],
          "url": "https://support.industry.siemens.com/cs/ww/en/view/109780528/"
        },
        {
          "category": "mitigation",
          "details": "As a general security measure, Siemens strongly recommends to protect network access to devices with appropriate mechanisms. In order to operate the devices in a protected IT environment, Siemens recommends to configure the environment according to Siemens\u0027 operational guidelines for Industrial Security (Download: \nhttps://www.siemens.com/cert/operational-guidelines-industrial-security), and to follow the recommendations in the product manuals.\nAdditional information on Industrial Security by Siemens can be found at: https://www.siemens.com/industrialsecurity",
          "product_ids": [
            "CSAFPID-00011",
            "CSAFPID-00012",
            "CSAFPID-00013",
            "CSAFPID-00017",
            "CSAFPID-00018",
            "CSAFPID-00019",
            "CSAFPID-00020",
            "CSAFPID-00021"
          ]
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "baseScore": 9.9,
            "baseSeverity": "CRITICAL",
            "vectorString": "CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:C/C:H/I:H/A:H/E:P/RL:O/RC:C",
            "version": "3.1"
          },
          "products": [
            "CSAFPID-00011",
            "CSAFPID-00012",
            "CSAFPID-00013",
            "CSAFPID-00017",
            "CSAFPID-00018",
            "CSAFPID-00019",
            "CSAFPID-00020",
            "CSAFPID-00021"
          ]
        }
      ],
      "title": "CVE-2021-40358"
    },
    {
      "cve": "CVE-2021-40359",
      "cwe": {
        "id": "CWE-22",
        "name": "Improper Limitation of a Pathname to a Restricted Directory (\u0027Path Traversal\u0027)"
      },
      "notes": [
        {
          "category": "summary",
          "text": "When downloading files, the affected systems do not properly neutralize special elements within the pathname. An attacker could then cause the pathname to resolve to a location outside of the restricted directory on the server and read unexpected critical files. CVE-2021-40359 has been assigned to this vulnerability. A CVSS v3 base score of 7.7 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:L/UI:N/S:C/C:H/I:N/A:N).",
          "title": "Summary"
        }
      ],
      "product_status": {
        "known_affected": [
          "CSAFPID-0001",
          "CSAFPID-0002",
          "CSAFPID-0003",
          "CSAFPID-0004",
          "CSAFPID-0005",
          "CSAFPID-0006",
          "CSAFPID-0007",
          "CSAFPID-0008",
          "CSAFPID-0009",
          "CSAFPID-00010",
          "CSAFPID-00011",
          "CSAFPID-00012",
          "CSAFPID-00013",
          "CSAFPID-00014",
          "CSAFPID-00015",
          "CSAFPID-00016",
          "CSAFPID-00017",
          "CSAFPID-00018",
          "CSAFPID-00019",
          "CSAFPID-00020",
          "CSAFPID-00021"
        ]
      },
      "references": [
        {
          "category": "external",
          "summary": "web.nvd.nist.gov",
          "url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2021-40359"
        },
        {
          "category": "external",
          "summary": "www.first.org",
          "url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:L/UI:N/S:C/C:H/I:N/A:N"
        }
      ],
      "remediations": [
        {
          "category": "mitigation",
          "details": "The vulnerability is fixed if SIMATIC WinCC V7.4 SP1 Update 19 or later version is installed on the same system",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0004",
            "CSAFPID-0005",
            "CSAFPID-00014",
            "CSAFPID-00015"
          ]
        },
        {
          "category": "mitigation",
          "details": "To fix CVE-2021-40359 see chapter \"Additional Information\"",
          "product_ids": [
            "CSAFPID-00011",
            "CSAFPID-00012"
          ]
        },
        {
          "category": "no_fix_planned",
          "details": "Currently no fix is planned",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0004",
            "CSAFPID-0005",
            "CSAFPID-0007",
            "CSAFPID-0008",
            "CSAFPID-00014",
            "CSAFPID-00015"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "Update to V8.2 SP1; then update SIMATIC WinCC to V7.4 SP1 Update 19 or later version to fix CVE-2021-40358 and CVE-2021-40364",
          "product_ids": [
            "CSAFPID-00011"
          ],
          "url": "https://support.industry.siemens.com/cs/ww/en/view/109806846/"
        },
        {
          "category": "vendor_fix",
          "details": "Update to V15 SP1 Update 7 or later version",
          "product_ids": [
            "CSAFPID-00017"
          ],
          "url": "https://support.industry.siemens.com/cs/us/en/view/109763890/"
        },
        {
          "category": "vendor_fix",
          "details": "Update to V16 Update 5 or later version",
          "product_ids": [
            "CSAFPID-00018"
          ],
          "url": "https://support.industry.siemens.com/cs/ww/en/view/109776017/"
        },
        {
          "category": "vendor_fix",
          "details": "Update to V17 Update 2 or later version",
          "product_ids": [
            "CSAFPID-00019"
          ],
          "url": "https://support.industry.siemens.com/cs/ww/en/view/109784441/"
        },
        {
          "category": "vendor_fix",
          "details": "Update to V7.4 SP1 Update 19 or later version",
          "product_ids": [
            "CSAFPID-00020"
          ],
          "url": "https://support.industry.siemens.com/cs/ww/en/view/109806846/"
        },
        {
          "category": "vendor_fix",
          "details": "Update to V7.5 SP2 Update 5 or later version",
          "product_ids": [
            "CSAFPID-00021"
          ],
          "url": "https://support.industry.siemens.com/cs/ww/en/view/109793460/"
        },
        {
          "category": "vendor_fix",
          "details": "Update to V9.1 SP1 or later version",
          "product_ids": [
            "CSAFPID-00013"
          ],
          "url": "https://support.industry.siemens.com/cs/ww/en/view/109805073/"
        },
        {
          "category": "vendor_fix",
          "details": "Update to V9.0 SP3 UC04 or later version to fix CVE-2021-40358 and CVE-2021-40364",
          "product_ids": [
            "CSAFPID-00012"
          ],
          "url": "https://support.industry.siemens.com/cs/ww/en/view/109780528/"
        },
        {
          "category": "vendor_fix",
          "details": "Update to V9.0 Upd4 or later version; V9.0 Upd4 is bundled in PCS 7 V9.0 SP3 UC04",
          "product_ids": [
            "CSAFPID-0002"
          ],
          "url": "https://support.industry.siemens.com/cs/ww/en/view/109780528/"
        },
        {
          "category": "vendor_fix",
          "details": "See remediation for SIMATIC PCS 7 V9.1",
          "product_ids": [
            "CSAFPID-0003",
            "CSAFPID-0006",
            "CSAFPID-00016"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "Update to V16 Update 6 or later version",
          "product_ids": [
            "CSAFPID-0009"
          ],
          "url": "https://support.industry.siemens.com/cs/ww/en/view/109811815/"
        },
        {
          "category": "vendor_fix",
          "details": "Update to V17 SP1 or later version",
          "product_ids": [
            "CSAFPID-00010"
          ],
          "url": "https://support.industry.siemens.com/cs/ww/de/view/109808270/"
        },
        {
          "category": "mitigation",
          "details": "As a general security measure, Siemens strongly recommends to protect network access to devices with appropriate mechanisms. In order to operate the devices in a protected IT environment, Siemens recommends to configure the environment according to Siemens\u0027 operational guidelines for Industrial Security (Download: \nhttps://www.siemens.com/cert/operational-guidelines-industrial-security), and to follow the recommendations in the product manuals.\nAdditional information on Industrial Security by Siemens can be found at: https://www.siemens.com/industrialsecurity",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005",
            "CSAFPID-0006",
            "CSAFPID-0007",
            "CSAFPID-0008",
            "CSAFPID-0009",
            "CSAFPID-00010",
            "CSAFPID-00011",
            "CSAFPID-00012",
            "CSAFPID-00013",
            "CSAFPID-00014",
            "CSAFPID-00015",
            "CSAFPID-00016",
            "CSAFPID-00017",
            "CSAFPID-00018",
            "CSAFPID-00019",
            "CSAFPID-00020",
            "CSAFPID-00021"
          ]
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "baseScore": 7.7,
            "baseSeverity": "HIGH",
            "vectorString": "CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:C/C:H/I:N/A:N/E:P/RL:O/RC:C",
            "version": "3.1"
          },
          "products": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005",
            "CSAFPID-0006",
            "CSAFPID-0007",
            "CSAFPID-0008",
            "CSAFPID-0009",
            "CSAFPID-00010",
            "CSAFPID-00011",
            "CSAFPID-00012",
            "CSAFPID-00013",
            "CSAFPID-00014",
            "CSAFPID-00015",
            "CSAFPID-00016",
            "CSAFPID-00017",
            "CSAFPID-00018",
            "CSAFPID-00019",
            "CSAFPID-00020",
            "CSAFPID-00021"
          ]
        }
      ],
      "title": "CVE-2021-40359"
    },
    {
      "cve": "CVE-2021-40364",
      "cwe": {
        "id": "CWE-532",
        "name": "Insertion of Sensitive Information into Log File"
      },
      "notes": [
        {
          "category": "summary",
          "text": "The affected systems store sensitive information in log files. An attacker with access to the log files could publicly expose the information or reuse it to develop further attacks on the system. CVE-2021-40364 has been assigned to this vulnerability. A CVSS v3 base score of 5.5 has been calculated; the CVSS vector string is (AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:N/A:N).",
          "title": "Summary"
        }
      ],
      "product_status": {
        "known_affected": [
          "CSAFPID-00011",
          "CSAFPID-00012",
          "CSAFPID-00013",
          "CSAFPID-00017",
          "CSAFPID-00018",
          "CSAFPID-00019",
          "CSAFPID-00020",
          "CSAFPID-00021"
        ]
      },
      "references": [
        {
          "category": "external",
          "summary": "web.nvd.nist.gov",
          "url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2021-40364"
        },
        {
          "category": "external",
          "summary": "www.first.org",
          "url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:N/A:N"
        }
      ],
      "remediations": [
        {
          "category": "mitigation",
          "details": "CVE-2021-40364: Harden the application\u2019s host to prevent local access by untrusted personnel",
          "product_ids": [
            "CSAFPID-00011",
            "CSAFPID-00012",
            "CSAFPID-00013",
            "CSAFPID-00017",
            "CSAFPID-00018",
            "CSAFPID-00019",
            "CSAFPID-00020",
            "CSAFPID-00021"
          ]
        },
        {
          "category": "mitigation",
          "details": "To fix CVE-2021-40359 see chapter \"Additional Information\"",
          "product_ids": [
            "CSAFPID-00011",
            "CSAFPID-00012"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "Update to V8.2 SP1; then update SIMATIC WinCC to V7.4 SP1 Update 19 or later version to fix CVE-2021-40358 and CVE-2021-40364",
          "product_ids": [
            "CSAFPID-00011"
          ],
          "url": "https://support.industry.siemens.com/cs/ww/en/view/109806846/"
        },
        {
          "category": "vendor_fix",
          "details": "Update to V15 SP1 Update 7 or later version",
          "product_ids": [
            "CSAFPID-00017"
          ],
          "url": "https://support.industry.siemens.com/cs/us/en/view/109763890/"
        },
        {
          "category": "vendor_fix",
          "details": "Update to V16 Update 5 or later version",
          "product_ids": [
            "CSAFPID-00018"
          ],
          "url": "https://support.industry.siemens.com/cs/ww/en/view/109776017/"
        },
        {
          "category": "vendor_fix",
          "details": "Update to V17 Update 2 or later version",
          "product_ids": [
            "CSAFPID-00019"
          ],
          "url": "https://support.industry.siemens.com/cs/ww/en/view/109784441/"
        },
        {
          "category": "vendor_fix",
          "details": "Update to V7.4 SP1 Update 19 or later version",
          "product_ids": [
            "CSAFPID-00020"
          ],
          "url": "https://support.industry.siemens.com/cs/ww/en/view/109806846/"
        },
        {
          "category": "vendor_fix",
          "details": "Update to V7.5 SP2 Update 5 or later version",
          "product_ids": [
            "CSAFPID-00021"
          ],
          "url": "https://support.industry.siemens.com/cs/ww/en/view/109793460/"
        },
        {
          "category": "vendor_fix",
          "details": "Update to V9.1 SP1 or later version",
          "product_ids": [
            "CSAFPID-00013"
          ],
          "url": "https://support.industry.siemens.com/cs/ww/en/view/109805073/"
        },
        {
          "category": "vendor_fix",
          "details": "Update to V9.0 SP3 UC04 or later version to fix CVE-2021-40358 and CVE-2021-40364",
          "product_ids": [
            "CSAFPID-00012"
          ],
          "url": "https://support.industry.siemens.com/cs/ww/en/view/109780528/"
        },
        {
          "category": "mitigation",
          "details": "As a general security measure, Siemens strongly recommends to protect network access to devices with appropriate mechanisms. In order to operate the devices in a protected IT environment, Siemens recommends to configure the environment according to Siemens\u0027 operational guidelines for Industrial Security (Download: \nhttps://www.siemens.com/cert/operational-guidelines-industrial-security), and to follow the recommendations in the product manuals.\nAdditional information on Industrial Security by Siemens can be found at: https://www.siemens.com/industrialsecurity",
          "product_ids": [
            "CSAFPID-00011",
            "CSAFPID-00012",
            "CSAFPID-00013",
            "CSAFPID-00017",
            "CSAFPID-00018",
            "CSAFPID-00019",
            "CSAFPID-00020",
            "CSAFPID-00021"
          ]
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "baseScore": 5.5,
            "baseSeverity": "MEDIUM",
            "vectorString": "CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:N/A:N/E:P/RL:O/RC:C",
            "version": "3.1"
          },
          "products": [
            "CSAFPID-00011",
            "CSAFPID-00012",
            "CSAFPID-00013",
            "CSAFPID-00017",
            "CSAFPID-00018",
            "CSAFPID-00019",
            "CSAFPID-00020",
            "CSAFPID-00021"
          ]
        }
      ],
      "title": "CVE-2021-40364"
    }
  ]
}


Log in or create an account to share your comment.




Tags
Taxonomy of the tags.


Loading...

Loading...

Loading...
  • Seen: The vulnerability was mentioned, discussed, or seen somewhere by the user.
  • Confirmed: The vulnerability is confirmed from an analyst perspective.
  • Exploited: This vulnerability was exploited and seen by the user reporting the sighting.
  • Patched: This vulnerability was successfully patched by the user reporting the sighting.
  • Not exploited: This vulnerability was not exploited or seen by the user reporting the sighting.
  • Not confirmed: The user expresses doubt about the veracity of the vulnerability.
  • Not patched: This vulnerability was not successfully patched by the user reporting the sighting.