icsa-22-167-05
Vulnerability from csaf_cisa
Published
2022-06-16 00:00
Modified
2022-06-16 00:00
Summary
Siemens EN100 Ethernet Module
Notes
CISA Disclaimer
This CSAF advisory was extracted from unstructured data and may contain inaccuracies. If you notice any errors, please reach out to the designated contact at CISA CSAF: central@cisa.dhs.gov
Legal Notice
All information products included in https://us-cert.cisa.gov/ics are provided "as is" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see https://us-cert.cisa.gov/tlp/.
Risk evaluation
Successful exploitation of this vulnerability could lead to the product crashing or the creation of a denial-of-service condition.
Critical infrastructure sectors
Energy
Countries/areas deployed
Worldwide
Company headquarters location
Germany
Recommended Practices
CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability. CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.
CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/icsSeveral recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.
Recommended Practices
Additional mitigation guidance and recommended practices are publicly available on the ICS webpage on cisa.gov/icsin the Technical Information Paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.
Organizations observing any suspected malicious activity should follow their established internal procedures and report their findings to CISA for tracking and correlation against other incidents.
Additional Resources
For further inquiries on security vulnerabilities in Siemens products and solutions, please contact the Siemens ProductCERT: https://www.siemens.com/cert/advisories
Exploitability
No known public exploits specifically target this vulnerability.
{ "document": { "acknowledgments": [ { "names": [ "Michael Messner" ], "organization": "Siemens Energy", "summary": "reporting this vulnerability to Siemens" } ], "category": "csaf_security_advisory", "csaf_version": "2.0", "distribution": { "text": "Disclosure is not limited", "tlp": { "label": "WHITE", "url": "https://us-cert.cisa.gov/tlp/" } }, "lang": "en-US", "notes": [ { "category": "general", "text": "This CSAF advisory was extracted from unstructured data and may contain inaccuracies. If you notice any errors, please reach out to the designated contact at CISA CSAF: central@cisa.dhs.gov", "title": "CISA Disclaimer" }, { "category": "legal_disclaimer", "text": "All information products included in https://us-cert.cisa.gov/ics are provided \"as is\" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see https://us-cert.cisa.gov/tlp/.", "title": "Legal Notice" }, { "category": "summary", "text": "Successful exploitation of this vulnerability could lead to the product crashing or the creation of a denial-of-service condition.", "title": "Risk evaluation" }, { "category": "other", "text": "Energy", "title": "Critical infrastructure sectors" }, { "category": "other", "text": "Worldwide", "title": "Countries/areas deployed" }, { "category": "other", "text": "Germany", "title": "Company headquarters location" }, { "category": "general", "text": "CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability. CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.\nCISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/icsSeveral recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.", "title": "Recommended Practices" }, { "category": "general", "text": "Additional mitigation guidance and recommended practices are publicly available on the ICS webpage on cisa.gov/icsin the Technical Information Paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.\nOrganizations observing any suspected malicious activity should follow their established internal procedures and report their findings to CISA for tracking and correlation against other incidents.", "title": "Recommended Practices" }, { "category": "general", "text": "For further inquiries on security vulnerabilities in Siemens products and solutions, please contact the Siemens ProductCERT: https://www.siemens.com/cert/advisories", "title": "Additional Resources" }, { "category": "other", "text": "No known public exploits specifically target this vulnerability.", "title": "Exploitability" } ], "publisher": { "category": "coordinator", "contact_details": "Email: CISAservicedesk@cisa.dhs.gov;\n Toll Free: 1-888-282-0870", "name": "CISA", "namespace": "https://www.cisa.gov/" }, "references": [ { "category": "external", "summary": "SSA-693555: Memory Corruption Vulnerability in EN100 Ethernet Module - CSAF Version", "url": "https://cert-portal.siemens.com/productcert/csaf/ssa-693555.json" }, { "category": "self", "summary": "ICS Advisory ICSA-22-167-05 JSON", "url": "https://raw.githubusercontent.com/cisagov/CSAF/develop/csaf_files/OT/white/2022/icsa-22-167-05.json" }, { "category": "self", "summary": "ICS Advisory ICSA-22-167-05 Web Version", "url": "https://www.cisa.gov/news-events/ics-advisories/icsa-22-167-05" }, { "category": "external", "summary": "Recommended Practices", "url": "https://www.cisa.gov/uscert/sites/default/files/recommended_practices/NCCIC_ICS-CERT_Defense_in_Depth_2016_S508C.pdf" }, { "category": "external", "summary": "Recommended Practices", "url": "https://www.cisa.gov/uscert/ics/tips/ICS-TIP-12-146-01B" }, { "category": "external", "summary": "SSA-693555: Memory Corruption Vulnerability in EN100 Ethernet Module - PDF Version", "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-693555.pdf" }, { "category": "external", "summary": "SSA-693555: Memory Corruption Vulnerability in EN100 Ethernet Module - TXT Version", "url": "https://cert-portal.siemens.com/productcert/txt/ssa-693555.txt" } ], "title": "Siemens EN100 Ethernet Module", "tracking": { "current_release_date": "2022-06-16T00:00:00.000000Z", "generator": { "engine": { "name": "CISA CSAF Generator", "version": "1.0.0" } }, "id": "ICSA-22-167-05", "initial_release_date": "2022-06-16T00:00:00.000000Z", "revision_history": [ { "date": "2022-06-16T00:00:00.000000Z", "legacy_version": "Initial", "number": "1", "summary": "ICSA-22-167-05 Siemens EN100 Ethernet Module" } ], "status": "final", "version": "1" } }, "product_tree": { "branches": [ { "branches": [ { "branches": [ { "category": "product_version_range", "name": "vers:all/*", "product": { "name": "EN100 Ethernet module DNP3 IP variant", "product_id": "CSAFPID-0001" } } ], "category": "product_name", "name": "EN100 Ethernet module DNP3 IP variant" }, { "branches": [ { "category": "product_version_range", "name": "vers:all/*", "product": { "name": "EN100 Ethernet module IEC 104 variant", "product_id": "CSAFPID-0002" } } ], "category": "product_name", "name": "EN100 Ethernet module IEC 104 variant" }, { "branches": [ { "category": "product_version_range", "name": "\u003c V4.37", "product": { "name": "EN100 Ethernet module IEC 61850 variant", "product_id": "CSAFPID-0003" } } ], "category": "product_name", "name": "EN100 Ethernet module IEC 61850 variant" }, { "branches": [ { "category": "product_version_range", "name": "vers:all/*", "product": { "name": "EN100 Ethernet module Modbus TCP variant", "product_id": "CSAFPID-0004" } } ], "category": "product_name", "name": "EN100 Ethernet module Modbus TCP variant" }, { "branches": [ { "category": "product_version_range", "name": "vers:all/*", "product": { "name": "EN100 Ethernet module PROFINET IO variant", "product_id": "CSAFPID-0005" } } ], "category": "product_name", "name": "EN100 Ethernet module PROFINET IO variant" } ], "category": "vendor", "name": "Siemens" } ] }, "vulnerabilities": [ { "cve": "CVE-2022-30937", "cwe": { "id": "CWE-119", "name": "Improper Restriction of Operations within the Bounds of a Memory Buffer" }, "notes": [ { "category": "summary", "text": "Affected applications contains a memory corruption vulnerability while parsing specially crafted HTTP packets to /txtrace endpoint. This could allow an attacker to crash the affected application leading to a denial of service condition.", "title": "Summary" } ], "product_status": { "known_affected": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005" ] }, "references": [ { "summary": "CVE-2022-30937 - EN100 Ethernet module IEC 61850 variant", "url": "https://support.industry.siemens.com/cs/us/en/view/109745821/" }, { "summary": "CVE-2022-30937 Mitre 5.0 json", "url": "https://cert-portal.siemens.com/productcert/mitre/CVE-2022-30937.json" }, { "category": "external", "summary": "web.nvd.nist.gov", "url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2022-30937" }, { "category": "external", "summary": "www.first.org", "url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:C/C:N/I:N/A:H" } ], "remediations": [ { "category": "no_fix_planned", "details": "Currently no fix is planned", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0004", "CSAFPID-0005" ] }, { "category": "vendor_fix", "details": "Update to V4.37 or later version", "product_ids": [ "CSAFPID-0003" ], "url": "https://support.industry.siemens.com/cs/us/en/view/109745821/" }, { "category": "mitigation", "details": "Disable web service within the device configuration if it is not used", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005" ] }, { "category": "workaround", "details": "Block access to port 80/tcp and 443/tcp e.g. with an external firewall", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005" ] }, { "category": "workaround", "details": "Apply secure substation concept and Defense-in-Depth (see https://www.siemens.com/gridsecurity) or contact customer care to find specific solutions", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005" ] }, { "category": "mitigation", "details": "Operators of critical power systems (e.g. TSOs or DSOs) worldwide are usually required by regulations to build resilience into the power grids by applying multi-level redundant secondary protection schemes. It is therefore recommended that the operators check whether appropriate resilient protection measures are in place. The risk of cyber incidents impacting the grid\u0027s reliability can thus be minimized by virtue of the grid design.\n\nSiemens strongly recommends applying the provided security updates using the corresponding tooling and documented procedures made available with the product. If supported by the product, an automated means to apply the security updates across multiple product instances may be used. Siemens strongly recommends prior validation of any security update before being applied, and supervision by trained staff of the update process in the target environment.\n\nAs a general security measure Siemens strongly recommends to protect network access with appropriate mechanisms (e.g. firewalls, segmentation, VPN). It is advised to configure the environment according to our operational guidelines in order to run the devices in a protected IT environment.\n\nRecommended security guidelines can be found at:\n\nhttps://www.siemens.com/gridsecurity", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005" ] } ], "scores": [ { "cvss_v3": { "baseScore": 8.6, "baseSeverity": "HIGH", "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:C/C:N/I:N/A:H/E:P/RL:O/RC:C", "version": "3.1" }, "products": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005" ] } ], "title": "CVE-2022-30937" } ] }
Loading…
Loading…
Sightings
Author | Source | Type | Date |
---|
Nomenclature
- Seen: The vulnerability was mentioned, discussed, or seen somewhere by the user.
- Confirmed: The vulnerability is confirmed from an analyst perspective.
- Exploited: This vulnerability was exploited and seen by the user reporting the sighting.
- Patched: This vulnerability was successfully patched by the user reporting the sighting.
- Not exploited: This vulnerability was not exploited or seen by the user reporting the sighting.
- Not confirmed: The user expresses doubt about the veracity of the vulnerability.
- Not patched: This vulnerability was not successfully patched by the user reporting the sighting.