SEVD-2022-193-04
Vulnerability from csaf_se - Published: 2022-07-12 08:55 - Updated: 2022-07-12 08:55Summary
Easergy P5
Notes
General Security Recommendations
We strongly recommend the following industry cybersecurity best practices.
https://www.se.com/us/en/download/document/7EN52-0390/
* Locate control and safety system networks and remote devices behind firewalls and isolate them from the business network.
* Install physical controls so no unauthorized personnel can access your industrial control and safety systems, components, peripheral equipment, and networks.
* Place all controllers in locked cabinets and never leave them in the “Program” mode.
* Never connect programming software to any network other than the network intended for that device.
* Scan all methods of mobile data exchange with the isolated network such as CDs, USB drives, etc. before use in the terminals or any node connected to these networks.
* Never allow mobile devices that have connected to any other network besides the intended network to connect to the safety or control networks without proper sanitation.
* Minimize network exposure for all control system devices and systems and ensure that they are not accessible from the Internet.
* When remote access is required, use secure methods, such as Virtual Private Networks (VPNs). Recognize that VPNs may have vulnerabilities and should be updated to the most current version available. Also, understand that VPNs are only as secure as the connected devices.
For more information refer to the Schneider Electric Recommended Cybersecurity Best Practices document.
For More Information
This document provides an overview of the identified vulnerability or vulnerabilities and actions required to mitigate. For more details and assistance on how to protect your installation, contact your local Schneider Electric representative or Schneider Electric Industrial Cybersecurity Services: https://www.se.com/ww/en/work/solutions/cybersecurity/. These organizations will be fully aware of this situation and can support you through the process.
For further information related to cybersecurity in Schneider Electric’s products, visit the company’s cybersecurity support portal page: https://www.se.com/ww/en/work/support/cybersecurity/overview.jsp
LEGAL DISCLAIMER
THIS NOTIFICATION DOCUMENT, THE INFORMATION CONTAINED HEREIN, AND ANY MATERIALS LINKED FROM IT (COLLECTIVELY, THIS “NOTIFICATION”) ARE INTENDED TO HELP PROVIDE AN OVERVIEW OF THE IDENTIFIED SITUATION AND SUGGESTED MITIGATION ACTIONS, REMEDIATION, FIX, AND/OR GENERAL SECURITY RECOMMENDATIONS AND IS PROVIDED ON AN “AS-IS” BASIS WITHOUT WARRANTY OR GUARANTEE OF ANY KIND. SCHNEIDER ELECTRIC DISCLAIMS ALL WARRANTIES RELATING TO THIS NOTIFICATION, EITHER EXPRESS OR IMPLIED, INCLUDING WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. SCHNEIDER ELECTRIC MAKES NO WARRANTY THAT THE NOTIFICATION WILL RESOLVE THE IDENTIFIED SITUATION. IN NO EVENT SHALL SCHNEIDER ELECTRIC BE LIABLE FOR ANY DAMAGES OR LOSSES WHATSOEVER IN CONNECTION WITH THIS NOTIFICATION, INCLUDING DIRECT, INDIRECT, INCIDENTAL, CONSEQUENTIAL, LOSS OF BUSINESS PROFITS OR SPECIAL DAMAGES, EVEN IF SCHNEIDER ELECTRIC HAS BEEN ADVISED OF THE POSSIBILITY OF SUCH DAMAGES. YOUR USE OF THIS NOTIFICATION IS AT YOUR OWN RISK, AND YOU ARE SOLELY LIABLE FOR ANY DAMAGES TO YOUR SYSTEMS OR ASSETS OR OTHER LOSSES THAT MAY RESULT FROM YOUR USE OF THIS NOTIFICATION. SCHNEIDER ELECTRIC RESERVES THE RIGHT TO UPDATE OR CHANGE THIS NOTIFICATION AT ANY TIME AND IN ITS SOLE DISCRETION
About Schneider Electric
At Schneider, we believe access to energy and digital is a basic human right. We empower all to do more with less, ensuring Life Is On everywhere, for everyone, at every moment.
We provide energy and automation digital solutions for efficiency and sustainability. We combine world-leading energy technologies, real-time automation, software and services into integrated solutions for Homes, Buildings, Data Centers, Infrastructure and Industries.
We are committed to unleash the infinite possibilities of an open, global, innovative community that is passionate with our Meaningful Purpose, Inclusive and Empowered values.
www.se.com
Overview
Schneider Electric is aware of multiple vulnerabilities in its Easergy P5 product line.
The Easergy P5 is a medium voltage protection relay.
Failure to apply the mitigations or remediations provided below may risk disclosure of the device’s credentials, denial of service, device reboot, or an attacker could gain full control of the relay. This could result in loss of protection of your electrical network.
{
"document": {
"category": "csaf_security_advisory",
"csaf_version": "2.0",
"distribution": {
"text": "Public",
"tlp": {
"label": "WHITE"
}
},
"lang": "en-US",
"notes": [
{
"category": "general",
"text": "We strongly recommend the following industry cybersecurity best practices.\n\nhttps://www.se.com/us/en/download/document/7EN52-0390/\n* Locate control and safety system networks and remote devices behind firewalls and isolate them from the business network.\n* Install physical controls so no unauthorized personnel can access your industrial control and safety systems, components, peripheral equipment, and networks.\n* Place all controllers in locked cabinets and never leave them in the \u201cProgram\u201d mode.\n* Never connect programming software to any network other than the network intended for that device.\n* Scan all methods of mobile data exchange with the isolated network such as CDs, USB drives, etc. before use in the terminals or any node connected to these networks.\n* Never allow mobile devices that have connected to any other network besides the intended network to connect to the safety or control networks without proper sanitation.\n* Minimize network exposure for all control system devices and systems and ensure that they are not accessible from the Internet.\n* When remote access is required, use secure methods, such as Virtual Private Networks (VPNs). Recognize that VPNs may have vulnerabilities and should be updated to the most current version available. Also, understand that VPNs are only as secure as the connected devices.\nFor more information refer to the Schneider Electric Recommended Cybersecurity Best Practices document. \n",
"title": "General Security Recommendations"
},
{
"category": "general",
"text": "This document provides an overview of the identified vulnerability or vulnerabilities and actions required to mitigate. For more details and assistance on how to protect your installation, contact your local Schneider Electric representative or Schneider Electric Industrial Cybersecurity Services: https://www.se.com/ww/en/work/solutions/cybersecurity/. These organizations will be fully aware of this situation and can support you through the process.\nFor further information related to cybersecurity in Schneider Electric\u2019s products, visit the company\u2019s cybersecurity support portal page: https://www.se.com/ww/en/work/support/cybersecurity/overview.jsp",
"title": "For More Information"
},
{
"category": "legal_disclaimer",
"text": "THIS NOTIFICATION DOCUMENT, THE INFORMATION CONTAINED HEREIN, AND ANY MATERIALS LINKED FROM IT (COLLECTIVELY, THIS \u201cNOTIFICATION\u201d) ARE INTENDED TO HELP PROVIDE AN OVERVIEW OF THE IDENTIFIED SITUATION AND SUGGESTED MITIGATION ACTIONS, REMEDIATION, FIX, AND/OR GENERAL SECURITY RECOMMENDATIONS AND IS PROVIDED ON AN \u201cAS-IS\u201d BASIS WITHOUT WARRANTY OR GUARANTEE OF ANY KIND. SCHNEIDER ELECTRIC DISCLAIMS ALL WARRANTIES RELATING TO THIS NOTIFICATION, EITHER EXPRESS OR IMPLIED, INCLUDING WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. SCHNEIDER ELECTRIC MAKES NO WARRANTY THAT THE NOTIFICATION WILL RESOLVE THE IDENTIFIED SITUATION. IN NO EVENT SHALL SCHNEIDER ELECTRIC BE LIABLE FOR ANY DAMAGES OR LOSSES WHATSOEVER IN CONNECTION WITH THIS NOTIFICATION, INCLUDING DIRECT, INDIRECT, INCIDENTAL, CONSEQUENTIAL, LOSS OF BUSINESS PROFITS OR SPECIAL DAMAGES, EVEN IF SCHNEIDER ELECTRIC HAS BEEN ADVISED OF THE POSSIBILITY OF SUCH DAMAGES. YOUR USE OF THIS NOTIFICATION IS AT YOUR OWN RISK, AND YOU ARE SOLELY LIABLE FOR ANY DAMAGES TO YOUR SYSTEMS OR ASSETS OR OTHER LOSSES THAT MAY RESULT FROM YOUR USE OF THIS NOTIFICATION. SCHNEIDER ELECTRIC RESERVES THE RIGHT TO UPDATE OR CHANGE THIS NOTIFICATION AT ANY TIME AND IN ITS SOLE DISCRETION",
"title": "LEGAL DISCLAIMER"
},
{
"category": "general",
"text": "At Schneider, we believe access to energy and digital is a basic human right. We empower all to do more with less, ensuring Life Is On everywhere, for everyone, at every moment.\n\nWe provide energy and automation digital solutions for efficiency and sustainability. We combine world-leading energy technologies, real-time automation, software and services into integrated solutions for Homes, Buildings, Data Centers, Infrastructure and Industries.\n\nWe are committed to unleash the infinite possibilities of an open, global, innovative community that is passionate with our Meaningful Purpose, Inclusive and Empowered values.\n\nwww.se.com ",
"title": "About Schneider Electric"
},
{
"category": "summary",
"text": "Schneider Electric is aware of multiple vulnerabilities in its Easergy P5 product line.\r\nThe Easergy P5 is a medium voltage protection relay.\r\nFailure to apply the mitigations or remediations provided below may risk disclosure of the device\u2019s credentials, denial of service, device reboot, or an attacker could gain full control of the relay. This could result in loss of protection of your electrical network.",
"title": "Overview"
}
],
"publisher": {
"category": "vendor",
"contact_details": "cybersecurity@se.com",
"name": "Schneider Electric CPCERT",
"namespace": "https://www.se.com/ww/en/work/support/cybersecurity/security-notifications.jsp"
},
"references": [
{
"category": "self",
"summary": "Easergy P5 - SEVD-2022-193-04 CSAF Version",
"url": "https://download.schneider-electric.com/files?p_Doc_Ref=SEVD-2022-193-04\u0026p_enDocType=Security+and+Safety+Notice\u0026p_File_Name=sevd-2022-193-04.json"
},
{
"category": "self",
"summary": "Easergy P5 - SEVD-2022-193-04 PDF Version",
"url": "https://download.schneider-electric.com/files?p_Doc_Ref=SEVD-2022-193-04\u0026p_enDocType=Security+and+Safety+Notice\u0026p_File_Name=SEVD-2022-193-04_Easergy_P5_Security_Notification.pdf"
},
{
"category": "self",
"summary": "Recommended Cybersecurity Best Practices",
"url": "https://www.se.com/us/en/download/document/7EN52-0390/"
}
],
"title": "Easergy P5",
"tracking": {
"current_release_date": "2022-07-12T08:55:42.000Z",
"generator": {
"date": "2022-07-04T09:33:15.137Z",
"engine": {
"name": "Schneider Electric CSAF Generator",
"version": "1.1"
}
},
"id": "SEVD-2022-193-04",
"initial_release_date": "2022-07-12T08:55:42.000Z",
"revision_history": [
{
"date": "2022-07-12T08:55:42.000Z",
"number": "1",
"summary": "Original Release"
}
],
"status": "final",
"version": "1"
}
},
"product_tree": {
"branches": [
{
"branches": [
{
"branches": [
{
"category": "product_version_range",
"name": "\u003c=V01.401.102",
"product": {
"name": "Schneider Electric Easergy P5 \u003c=V01.401.102",
"product_id": "1"
}
}
],
"category": "product_name",
"name": "Easergy P5"
},
{
"branches": [
{
"category": "product_version",
"name": "V01.402.101",
"product": {
"name": "Schneider Electric Easergy P5 V01.402.101",
"product_id": "2"
}
}
],
"category": "product_name",
"name": "Easergy P5"
}
],
"category": "vendor",
"name": "Schneider Electric"
}
]
},
"vulnerabilities": [
{
"acknowledgments": [
{
"names": [
"McKade Umbenhower"
],
"organization": "U.S. Department of Energy CyTRICS\u2013INL"
}
],
"cve": "CVE-2022-34756",
"cwe": {
"id": "CWE-120",
"name": "Buffer Copy without Checking Size of Input (\u0027Classic Buffer Overflow\u0027)"
},
"notes": [
{
"category": "description",
"text": "A CWE-120: Buffer Copy without Checking Size of Input vulnerability exists that could result in remote code execution or the crash of HTTPs stack which is used for the device Web HMI.",
"title": "CVE Description"
}
],
"product_status": {
"fixed": [
"2"
],
"known_affected": [
"1"
]
},
"remediations": [
{
"category": "vendor_fix",
"details": "V01.402.101 of the Easergy P5 firmware includes a fix for these vulnerabilities and is available on request from Schneider Electric\u2019s Customer Care Center.",
"product_ids": [
"1"
],
"restart_required": {
"category": "none"
}
},
{
"category": "mitigation",
"details": "Disable the device Web HMI by using the Easergy Pro to turn off the HTTPS server in the communication menu.",
"product_ids": [
"1"
],
"restart_required": {
"category": "none"
}
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "ADJACENT_NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 8.8,
"baseSeverity": "HIGH",
"confidentialityImpact": "HIGH",
"integrityImpact": "HIGH",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:A/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H",
"version": "3.1"
},
"products": [
"1"
]
}
],
"title": "CVE-2022-34756"
},
{
"acknowledgments": [
{
"names": [
"McKade Umbenhower"
]
}
],
"cve": "CVE-2022-34757",
"cwe": {
"id": "CWE-327",
"name": "Use of a Broken or Risky Cryptographic Algorithm"
},
"notes": [
{
"category": "description",
"text": "A CWE-327: Use of a Broken or Risky Cryptographic Algorithm vulnerability exists where weak cipher suites can be used for the SSH connection between Easergy Pro software and the device, which may allow an attacker to observe protected communication details.",
"title": "CVE Description"
}
],
"product_status": {
"fixed": [
"2"
],
"known_affected": [
"1"
]
},
"remediations": [
{
"category": "vendor_fix",
"details": "V01.402.101 of the Easergy P5 firmware includes a fix for these vulnerabilities and is available on request from Schneider Electric\u2019s Customer Care Center.",
"product_ids": [
"1"
],
"restart_required": {
"category": "none"
}
},
{
"category": "mitigation",
"details": "If the device firmware version is prior to V01.401.101, limit the use of Easergy Pro software to the front USB port. The option to disable SSH on the rear Ethernet board is not yet available in this version of the firmware.",
"product_ids": [
"1"
],
"restart_required": {
"category": "none"
}
},
{
"category": "mitigation",
"details": "If the device firmware is V01.401.101 to V01.402.001:\r\n\u2022 Disable the SSH on the rear Ethernet port and use\r\nonly Easergy Pro on the front USB port.\r\n\u2022 If you are using Easergy Pro software on the rear Ethernet port, disable SSH on the rear Ethernet port when it is not in use",
"product_ids": [
"1"
],
"restart_required": {
"category": "none"
}
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "HIGH",
"attackVector": "ADJACENT_NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 6.7,
"baseSeverity": "MEDIUM",
"confidentialityImpact": "LOW",
"integrityImpact": "HIGH",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"userInteraction": "REQUIRED",
"vectorString": "CVSS:3.1/AV:A/AC:H/PR:N/UI:R/S:U/C:L/I:H/A:H",
"version": "3.1"
},
"products": [
"1"
]
}
],
"title": "CVE-2022-34757"
},
{
"acknowledgments": [
{
"names": [
"Timoth\u00e9e Chauvin",
"Paul Noalhyt",
"Yuanzhe Wu"
],
"organization": "Red Balloon Security"
}
],
"cve": "CVE-2022-34758",
"cwe": {
"id": "CWE-20",
"name": "Improper Input Validation"
},
"notes": [
{
"category": "description",
"text": "A CWE-20: Improper Input Validation vulnerability exists that could cause the device watchdog function to be disabled if the attacker had access to privileged user credentials.",
"title": "CVE Description"
}
],
"product_status": {
"fixed": [
"2"
],
"known_affected": [
"1"
]
},
"remediations": [
{
"category": "vendor_fix",
"details": "V01.402.101 of the Easergy P5 firmware includes a fix for these vulnerabilities and is available on request from Schneider Electric\u2019s Customer Care Center.",
"product_ids": [
"1"
],
"restart_required": {
"category": "none"
}
},
{
"category": "mitigation",
"details": "Follow the General Security Recommendations.",
"product_ids": [
"1"
],
"restart_required": {
"category": "none"
}
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "LOCAL",
"availabilityImpact": "LOW",
"baseScore": 5.1,
"baseSeverity": "MEDIUM",
"confidentialityImpact": "NONE",
"integrityImpact": "HIGH",
"privilegesRequired": "HIGH",
"scope": "UNCHANGED",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:L/AC:L/PR:H/UI:N/S:U/C:N/I:H/A:L",
"version": "3.1"
},
"products": [
"1"
]
}
],
"title": "CVE-2022-34758"
}
]
}
Loading…
Loading…
Sightings
| Author | Source | Type | Date |
|---|
Nomenclature
- Seen: The vulnerability was mentioned, discussed, or observed by the user.
- Confirmed: The vulnerability has been validated from an analyst's perspective.
- Published Proof of Concept: A public proof of concept is available for this vulnerability.
- Exploited: The vulnerability was observed as exploited by the user who reported the sighting.
- Patched: The vulnerability was observed as successfully patched by the user who reported the sighting.
- Not exploited: The vulnerability was not observed as exploited by the user who reported the sighting.
- Not confirmed: The user expressed doubt about the validity of the vulnerability.
- Not patched: The vulnerability was not observed as successfully patched by the user who reported the sighting.