3ADR011377
Vulnerability from csaf_abb - Published: 2025-01-07 00:30 - Updated: 2025-01-07 00:30Summary
AC500 V3 Multiple vulnerabilities
Notes
Summary
An update is available that resolves a publicly reported vulnerability in the product versions listed as affected in the advisory.
An attacker who successfully exploited these vulnerabilities could call shell functions (CVE-2023-6357),
crash the PLC (CVE-2024-5000), crash the web server of the PLC (CVE-2024-8175), grant read access to
files (CVE-2024-12429) or enable command execution (CVE-2024-12430).
The vulnerabilities CVE-2023-6357, CVE-2024-12429 and CVE-2024-12430 require successful authentication.
General security recommendations
For any installation of software-related ABB products we strongly recommend the following (non-exhaustive) list of cyber security practices:
– Isolate special purpose networks (e.g. for automation systems) and remote devices behind firewalls
and separate them from any general-purpose network (e.g. office or home networks).
– Install physical controls so no unauthorized personnel can access your devices, components, peripheral equipment, and networks.
– Never connect programming software or computers containing programming software to any network other than the network for the devices that it is intended for.
– Scan all data imported into your environment before use to detect potential malware infections.
– Minimize network exposure for all applications and endpoints to ensure that they are not accessible
from the Internet unless they are designed for such exposure and the intended use requires such.
– Ensure all nodes are always up to date in terms of installed software, operating system, and firmware
patches as well as anti-virus and firewall.
– When remote access is required, use secure methods, such as Virtual Private Networks (VPNs). Recognize that VPNs may have vulnerabilities and should be updated to the most current version available. Also, understand that VPNs are only as secure as the connected devices
Support
For additional instructions and support please contact your local ABB service organization. For contact
information, see www.abb.com/contactcenters.
Information about ABB’s cyber security program and capabilities can be found at www.abb.com/cybersecurity.
Notice
The information in this document is subject to change without notice, and should not be construed as a
commitment by ABB.
ABB provides no warranty, express or implied, including warranties of merchantability and fitness for a
particular purpose, for the information contained in this document, and assumes no responsibility for
any errors that may appear in this document. In no event shall ABB or any of its suppliers be liable for direct, indirect, special, incidental or consequential damages of any nature or kind arising from the use of
this document, or from the use of any hardware or software described in this document, even if ABB or
its suppliers have been advised of the possibility of such damages.
This document and parts hereof must not be reproduced or copied without written permission from
ABB, and the contents hereof must not be imparted to a third party nor used for any unauthorized purpose.
All rights to registrations and trademarks reside with their respective owners.
Workarounds
Workarounds are specific measures that a user can take to help block an attack, for example, temporarily disabling the vulnerable feature may remove the exposure with well-known impact on functionality.
ABB has tested the following workarounds. Although these workarounds will not correct the underlying
vulnerability, they can help block known attack vectors. When a workaround reduces functionality, this is
identified below as “Impact of workaround”.
To exploit the vulnerabilities CVE-2023-6357, CVE-2024-12429 and CVE-2024-12430, successful authentication is required. Therefore, the affected products shall only be used with activated user management
and by setting strong passwords. Details regarding the device user management are available from the
application note “AC500 User Management with V3”.
ABB strongly recommends using the online user management. This not only prevents an attacker from
downloading and execute malicious code, but also suppresses start, stop, debug, or other actions on a known working application that could potentially disrupt a machine or system.
Mitigating factors
Refer to section “General security recommendations” for further advise on how to keep your system secure
{
"document": {
"category": "csaf_security_advisory",
"csaf_version": "2.0",
"distribution": {
"tlp": {
"label": "WHITE"
}
},
"lang": "en",
"notes": [
{
"category": "summary",
"text": "An update is available that resolves a publicly reported vulnerability in the product versions listed as affected in the advisory. \nAn attacker who successfully exploited these vulnerabilities could call shell functions (CVE-2023-6357), \ncrash the PLC (CVE-2024-5000), crash the web server of the PLC (CVE-2024-8175), grant read access to \nfiles (CVE-2024-12429) or enable command execution (CVE-2024-12430).\nThe vulnerabilities CVE-2023-6357, CVE-2024-12429 and CVE-2024-12430 require successful authentication.\n",
"title": "Summary"
},
{
"category": "other",
"text": "For any installation of software-related ABB products we strongly recommend the following (non-exhaustive) list of cyber security practices:\n\u2013 Isolate special purpose networks (e.g. for automation systems) and remote devices behind firewalls \nand separate them from any general-purpose network (e.g. office or home networks).\n\u2013 Install physical controls so no unauthorized personnel can access your devices, components, peripheral equipment, and networks.\n\u2013 Never connect programming software or computers containing programming software to any network other than the network for the devices that it is intended for.\n\u2013 Scan all data imported into your environment before use to detect potential malware infections.\n\u2013 Minimize network exposure for all applications and endpoints to ensure that they are not accessible \nfrom the Internet unless they are designed for such exposure and the intended use requires such.\n\u2013 Ensure all nodes are always up to date in terms of installed software, operating system, and firmware \npatches as well as anti-virus and firewall.\n\u2013 When remote access is required, use secure methods, such as Virtual Private Networks (VPNs). Recognize that VPNs may have vulnerabilities and should be updated to the most current version available. Also, understand that VPNs are only as secure as the connected devices",
"title": "General security recommendations"
},
{
"category": "other",
"text": "For additional instructions and support please contact your local ABB service organization. For contact \ninformation, see www.abb.com/contactcenters.\nInformation about ABB\u2019s cyber security program and capabilities can be found at www.abb.com/cybersecurity.",
"title": "Support"
},
{
"category": "legal_disclaimer",
"text": "The information in this document is subject to change without notice, and should not be construed as a \ncommitment by ABB.\nABB provides no warranty, express or implied, including warranties of merchantability and fitness for a \nparticular purpose, for the information contained in this document, and assumes no responsibility for \nany errors that may appear in this document. In no event shall ABB or any of its suppliers be liable for direct, indirect, special, incidental or consequential damages of any nature or kind arising from the use of \nthis document, or from the use of any hardware or software described in this document, even if ABB or \nits suppliers have been advised of the possibility of such damages.\nThis document and parts hereof must not be reproduced or copied without written permission from \nABB, and the contents hereof must not be imparted to a third party nor used for any unauthorized purpose.\nAll rights to registrations and trademarks reside with their respective owners.\n",
"title": "Notice"
},
{
"category": "general",
"text": "Workarounds are specific measures that a user can take to help block an attack, for example, temporarily disabling the vulnerable feature may remove the exposure with well-known impact on functionality. \nABB has tested the following workarounds. Although these workarounds will not correct the underlying \nvulnerability, they can help block known attack vectors. When a workaround reduces functionality, this is \nidentified below as \u201cImpact of workaround\u201d.\nTo exploit the vulnerabilities CVE-2023-6357, CVE-2024-12429 and CVE-2024-12430, successful authentication is required. Therefore, the affected products shall only be used with activated user management \nand by setting strong passwords. Details regarding the device user management are available from the \napplication note \u201cAC500 User Management with V3\u201d.\nABB strongly recommends using the online user management. This not only prevents an attacker from \ndownloading and execute malicious code, but also suppresses start, stop, debug, or other actions on a known working application that could potentially disrupt a machine or system.",
"title": "Workarounds"
},
{
"category": "general",
"text": "Refer to section \u201cGeneral security recommendations\u201d for further advise on how to keep your system secure",
"title": "Mitigating factors"
}
],
"publisher": {
"category": "vendor",
"name": "ABB PSIRT",
"namespace": "https://global.abb/group/en/technology/cyber-security/alerts-and-notifications"
},
"references": [
{
"category": "self",
"summary": "ABB CYBERSECURITY ADVISORY - PDF version",
"url": "https://search.abb.com/library/Download.aspx?DocumentID=3ADR011377\u0026LanguageCode=en\u0026DocumentPartId=\u0026Action=Launch"
},
{
"summary": "CVE-2023-6357: CODESYS Control V3 on Linux and QNX operating systems\n",
"url": "https://customers.codesys.com/index.php?eID=dumpFile\u0026t=f\u0026f=18027\u0026token=43109051cf95d3445bc616e4efb8414336ebcc47\u0026download="
},
{
"summary": "CVE-2024-5000: CODESYS Control V3 - OPC UA Stack",
"url": "https://customers.codesys.com/index.php?eID=dumpFile\u0026t=f\u0026f=18355\u0026token=e3e5a937ce72602bec39718ddc2f4ba6d983ccd1\u0026download="
},
{
"summary": "CVE-2024-8175: CODESYS Control V3 web server",
"url": "https://customers.codesys.com/index.php?eID=dumpFile\u0026t=f\u0026f=18604\u0026token=d5e1e2820ee63077b875b3bb41014b1f102e88a3\u0026download="
},
{
"summary": "Application note: AC500 User Management with V3",
"url": "https://search.abb.com/library/Download.aspx?DocumentID=3ADR010315\u0026LanguageCode=en\u0026DocumentPartId=\u0026Action=Launch"
},
{
"summary": "Automation Builder 2.8.0",
"url": "https://new.abb.com/plc/automationbuilder/platform/software"
},
{
"category": "self",
"summary": "ABB CYBERSECURITY ADVISORY - CSAF version",
"url": "https://psirt.abb.com/csaf/2025/3adr011377.json"
}
],
"title": "AC500 V3 Multiple vulnerabilities",
"tracking": {
"current_release_date": "2025-01-07T00:30:00.000Z",
"generator": {
"date": "2025-09-23T17:38:21.065Z",
"engine": {
"name": "Secvisogram",
"version": "2.5.35"
}
},
"id": "3ADR011377",
"initial_release_date": "2025-01-07T00:30:00.000Z",
"revision_history": [
{
"date": "2025-01-07T00:30:00.000Z",
"legacy_version": "A",
"number": "1",
"summary": "Initial version. "
}
],
"status": "final",
"version": "1"
}
},
"product_tree": {
"branches": [
{
"branches": [
{
"branches": [
{
"category": "product_version_range",
"name": "\u003c3.8.0",
"product": {
"name": "AC500 V3 products (PM5xxx) \u003c 3.8.0",
"product_id": "AV1"
}
},
{
"category": "product_version",
"name": "3.8.0",
"product": {
"name": "AC500 V3 firmware version 3.8.0",
"product_id": "FX1"
}
}
],
"category": "product_name",
"name": "AC500 V3"
}
],
"category": "vendor",
"name": "ABB"
}
]
},
"vulnerabilities": [
{
"cve": "CVE-2023-6357",
"cwe": {
"id": "CWE-78",
"name": "Improper Neutralization of Special Elements used in an OS Command (\u0027OS Command Injection\u0027)"
},
"notes": [
{
"category": "description",
"text": "A successfully authenticated control programmer could exploit this vulnerability to inject calls to additional operating system shell functions via the SysFile or CAA file system libraries.",
"title": "CVE description"
}
],
"product_status": {
"fixed": [
"FX1"
],
"known_affected": [
"AV1"
]
},
"references": [
{
"category": "external",
"summary": "NVD - CVE-2023-6357",
"url": "https://nvd.nist.gov/vuln/detail/CVE-2023-6357"
}
],
"remediations": [
{
"category": "vendor_fix",
"details": "The problem is corrected in AC500 V3 firmware version 3.8.0.\n\nABB recommends that customers apply the update at earliest convenience. This firmware version is released for all AC500 V3 PLC types and available from Automation Builder 2.8.0. ",
"product_ids": [
"AV1"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 8.8,
"baseSeverity": "HIGH",
"confidentialityImpact": "HIGH",
"environmentalScore": 8.8,
"environmentalSeverity": "HIGH",
"integrityImpact": "HIGH",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"temporalScore": 8.8,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H",
"version": "3.1"
},
"products": [
"AV1"
]
}
],
"title": " CVE-2023-6357"
},
{
"cve": "CVE-2024-5000",
"cwe": {
"id": "CWE-131",
"name": "Incorrect Calculation of Buffer Size"
},
"notes": [
{
"category": "description",
"text": "The OPC UA stack, implemented by the CmpOPCUAStack component, is an optional part of the runtime \nsystem. Both the OPC UA Server and the OPC UA Client of the runtime system use the OPC UA Stack as a \ncommon implementation. The OPC UA protocol enables data exchange between the runtime system and \nOPC UA clients such as SCADA or HMIs, or OPC UA servers such as PLCs or other devices.\nIf a runtime system containing the CmpOPCUAStack component receives a specially crafted request/response, the required buffer size in the OPC UA server/client may be incorrectly calculated. This can lead \nto a crash of the runtime system during the subsequent initialization of the receive buffer with zero.\nAn attacker can exploit this vulnerability by using a malicious OPC UA client to send a crafted request to \nthe AC500 V3 PLC with an affected OPC UA server. Conversely, AC500 V3 PLCs with an affected OPC UA \nclient can be crashed if they have connected to a malicious OPC UA server. The runtime systems usually \ncontain both the OPC UA client and the server.\n",
"title": "CVE description"
}
],
"product_status": {
"fixed": [
"FX1"
],
"known_affected": [
"AV1"
]
},
"references": [
{
"category": "external",
"summary": "NVD - CVE-2024-5000",
"url": "https://nvd.nist.gov/vuln/detail/CVE-2024-5000"
}
],
"remediations": [
{
"category": "vendor_fix",
"details": "The problem is corrected in AC500 V3 firmware version 3.8.0.\n\nABB recommends that customers apply the update at earliest convenience. This firmware version is released for all AC500 V3 PLC types and available from Automation Builder 2.8.0. ",
"product_ids": [
"AV1"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 8.8,
"baseSeverity": "HIGH",
"confidentialityImpact": "HIGH",
"environmentalScore": 8.8,
"environmentalSeverity": "HIGH",
"integrityImpact": "HIGH",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"temporalScore": 8.8,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H",
"version": "3.1"
},
"products": [
"AV1"
]
}
],
"title": "CVE-2024-5000"
},
{
"cve": "CVE-2024-8175",
"cwe": {
"id": "CWE-754",
"name": "Improper Check for Unusual or Exceptional Conditions"
},
"notes": [
{
"category": "description",
"text": "The AC500 V3 web server, implemented by the CmpWebServer component, is an optional part of the \nruntime system. It is used by the AC500 V3 WebVisu to display visualization screens in a web browser. \nThe AC500 V3 web server supports both the HTTP and HTTPS protocols. Because the AC500 V3 web \nserver does not correctly check the return value of an underlying function, it reacts in a wrong way to \nspecifically crafted TLS packets that are received via an HTTPS connection. This causes the AC500 V3 \nweb server to access invalid memory and the web server task to crash.",
"title": "CVE description"
}
],
"product_status": {
"fixed": [
"FX1"
],
"known_affected": [
"AV1"
]
},
"references": [
{
"category": "external",
"summary": "NVD - CVE-2024-8175",
"url": "https://nvd.nist.gov/vuln/detail/CVE-2024-8175"
}
],
"remediations": [
{
"category": "vendor_fix",
"details": "The problem is corrected in AC500 V3 firmware version 3.8.0.\n\nABB recommends that customers apply the update at earliest convenience. This firmware version is released for all AC500 V3 PLC types and available from Automation Builder 2.8.0. ",
"product_ids": [
"AV1"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 7.5,
"baseSeverity": "HIGH",
"confidentialityImpact": "NONE",
"environmentalScore": 7.5,
"environmentalSeverity": "HIGH",
"integrityImpact": "NONE",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"temporalScore": 7.5,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H",
"version": "3.1"
},
"products": [
"AV1"
]
}
],
"title": "CVE-2024-8175"
},
{
"acknowledgments": [
{
"names": [
"D. Blagojevic",
"S. Dietz",
"T. Weber"
],
"organization": " CyberDanube",
"summary": "reporting the vulnerabilities through responsible disclosure"
}
],
"cve": "CVE-2024-12429",
"cwe": {
"id": "CWE-22",
"name": "Improper Limitation of a Pathname to a Restricted Directory (\u0027Path Traversal\u0027)"
},
"notes": [
{
"category": "description",
"text": "AC500 V3 PLC has a slot for memory cards that can be used e.g. for logging purposes or for updating \nthe firmware or the boot application. Because the AC500 V3 does not correctly validate the content of \nthe memory card, a specifically crafted memory card can be used for directory traversal. A successfully \nauthenticated attacker can use this vulnerability to read system-wide files and configuration",
"title": "CVE description"
}
],
"product_status": {
"fixed": [
"FX1"
],
"known_affected": [
"AV1"
]
},
"references": [
{
"category": "external",
"summary": "NVD - CVE-2024-12429",
"url": "https://nvd.nist.gov/vuln/detail/CVE-2024-12429"
}
],
"remediations": [
{
"category": "vendor_fix",
"details": "The problem is corrected in AC500 V3 firmware version 3.8.0.\n\nABB recommends that customers apply the update at earliest convenience. This firmware version is released for all AC500 V3 PLC types and available from Automation Builder 2.8.0. ",
"product_ids": [
"AV1"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "PHYSICAL",
"availabilityImpact": "NONE",
"baseScore": 4.3,
"baseSeverity": "MEDIUM",
"confidentialityImpact": "HIGH",
"environmentalScore": 4.3,
"environmentalSeverity": "MEDIUM",
"integrityImpact": "NONE",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"temporalScore": 4.3,
"temporalSeverity": "MEDIUM",
"userInteraction": "REQUIRED",
"vectorString": "CVSS:3.1/AV:P/AC:L/PR:N/UI:R/S:U/C:H/I:N/A:N",
"version": "3.1"
},
"products": [
"AV1"
]
}
],
"title": "CVE-2024-12429"
},
{
"acknowledgments": [
{
"names": [
"D. Blagojevic",
"S. Dietz",
"T. Weber"
],
"organization": " CyberDanube",
"summary": "reporting the vulnerabilities through responsible disclosure"
}
],
"cve": "CVE-2024-12430",
"cwe": {
"id": "CWE-280",
"name": "Improper Handling of Insufficient Permissions or Privileges"
},
"notes": [
{
"category": "description",
"text": "After successfully exploiting CVE-2024-12429 (directory traversal), a successfully authenticated attacker \ncan inject arbitrary commands into a specifically crafted file, which then will be executed by root user",
"title": "CVE description"
}
],
"product_status": {
"fixed": [
"FX1"
],
"known_affected": [
"AV1"
]
},
"references": [
{
"category": "external",
"summary": "NVD - CVE-2024-12430",
"url": "https://nvd.nist.gov/vuln/detail/CVE-2024-12430"
}
],
"remediations": [
{
"category": "vendor_fix",
"details": "The problem is corrected in AC500 V3 firmware version 3.8.0.\n\nABB recommends that customers apply the update at earliest convenience. This firmware version is released for all AC500 V3 PLC types and available from Automation Builder 2.8.0. ",
"product_ids": [
"AV1"
]
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "HIGH",
"attackVector": "LOCAL",
"availabilityImpact": "HIGH",
"baseScore": 7,
"baseSeverity": "HIGH",
"confidentialityImpact": "HIGH",
"environmentalScore": 7,
"environmentalSeverity": "HIGH",
"integrityImpact": "HIGH",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"temporalScore": 7,
"temporalSeverity": "HIGH",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:L/AC:H/PR:L/UI:N/S:U/C:H/I:H/A:H",
"version": "3.1"
},
"products": [
"AV1"
]
}
],
"title": "CVE-2024-12430"
}
]
}
Loading…
Loading…
Sightings
| Author | Source | Type | Date |
|---|
Nomenclature
- Seen: The vulnerability was mentioned, discussed, or observed by the user.
- Confirmed: The vulnerability has been validated from an analyst's perspective.
- Published Proof of Concept: A public proof of concept is available for this vulnerability.
- Exploited: The vulnerability was observed as exploited by the user who reported the sighting.
- Patched: The vulnerability was observed as successfully patched by the user who reported the sighting.
- Not exploited: The vulnerability was not observed as exploited by the user who reported the sighting.
- Not confirmed: The user expressed doubt about the validity of the vulnerability.
- Not patched: The vulnerability was not observed as successfully patched by the user who reported the sighting.
Loading…
Loading…