CVE-2018-7798 (GCVE-0-2018-7798)

Vulnerability from cvelistv5 – Published: 2018-11-02 17:00 – Updated: 2026-05-29 14:09
VLAI
Summary
A Insufficient Verification of Data Authenticity (CWE-345) vulnerability exists in the Modicon M221, all versions, which could cause a change of IPv4 configuration (IP address, mask and gateway) when remotely connected to the device.
SSVC
Exploitation: none Automatable: yes Technical Impact: partial
CISA Coordinator · CISA-ADP (v2.0.3)
Decision recorded 2026-05-29 14:08 UTC
CWE
  • Insufficient Verification of Data Authenticity
  • CWE-345 - Insufficient Verification of Data Authenticity
References
Impacted products
Vendor Product Version CPE status
Schneider Electric SE Modicon M221, All Versions Affected: Modicon M221, All Versions
guessed Create a notification for this product.
Date Public
2018-11-02 00:00
Show details on NVD website

{
  "containers": {
    "adp": [
      {
        "providerMetadata": {
          "dateUpdated": "2024-08-05T06:37:59.359Z",
          "orgId": "af854a3a-2127-422b-91ae-364da2661108",
          "shortName": "CVE"
        },
        "references": [
          {
            "name": "105970",
            "tags": [
              "vdb-entry",
              "x_refsource_BID",
              "x_transferred"
            ],
            "url": "http://www.securityfocus.com/bid/105970"
          },
          {
            "tags": [
              "x_refsource_CONFIRM",
              "x_transferred"
            ],
            "url": "https://www.schneider-electric.com/en/download/document/SEVD-2018-270-01/"
          }
        ],
        "title": "CVE Program Container"
      },
      {
        "metrics": [
          {
            "cvssV3_1": {
              "attackComplexity": "LOW",
              "attackVector": "NETWORK",
              "availabilityImpact": "LOW",
              "baseScore": 8.2,
              "baseSeverity": "HIGH",
              "confidentialityImpact": "NONE",
              "integrityImpact": "HIGH",
              "privilegesRequired": "NONE",
              "scope": "UNCHANGED",
              "userInteraction": "NONE",
              "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:H/A:L",
              "version": "3.1"
            }
          },
          {
            "other": {
              "content": {
                "id": "CVE-2018-7798",
                "options": [
                  {
                    "Exploitation": "none"
                  },
                  {
                    "Automatable": "yes"
                  },
                  {
                    "Technical Impact": "partial"
                  }
                ],
                "role": "CISA Coordinator",
                "timestamp": "2026-05-29T14:08:28.530951Z",
                "version": "2.0.3"
              },
              "type": "ssvc"
            }
          }
        ],
        "problemTypes": [
          {
            "descriptions": [
              {
                "cweId": "CWE-345",
                "description": "CWE-345 Insufficient Verification of Data Authenticity",
                "lang": "en",
                "type": "CWE"
              }
            ]
          }
        ],
        "providerMetadata": {
          "dateUpdated": "2026-05-29T14:09:12.112Z",
          "orgId": "134c704f-9b21-4f2e-91b3-4a467353bcc0",
          "shortName": "CISA-ADP"
        },
        "title": "CISA ADP Vulnrichment"
      }
    ],
    "cna": {
      "affected": [
        {
          "product": "Modicon M221, All Versions",
          "vendor": "Schneider Electric SE",
          "versions": [
            {
              "status": "affected",
              "version": "Modicon M221, All Versions"
            }
          ]
        }
      ],
      "datePublic": "2018-11-02T00:00:00.000Z",
      "descriptions": [
        {
          "lang": "en",
          "value": "A Insufficient Verification of Data Authenticity (CWE-345) vulnerability exists in the Modicon M221, all versions, which could cause a change of IPv4 configuration (IP address, mask and gateway) when remotely connected to the device."
        }
      ],
      "problemTypes": [
        {
          "descriptions": [
            {
              "description": "Insufficient Verification of Data Authenticity",
              "lang": "en",
              "type": "text"
            }
          ]
        }
      ],
      "providerMetadata": {
        "dateUpdated": "2018-11-21T10:57:01.000Z",
        "orgId": "076d1eb6-cfab-4401-b34d-6dfc2a413bdb",
        "shortName": "schneider"
      },
      "references": [
        {
          "name": "105970",
          "tags": [
            "vdb-entry",
            "x_refsource_BID"
          ],
          "url": "http://www.securityfocus.com/bid/105970"
        },
        {
          "tags": [
            "x_refsource_CONFIRM"
          ],
          "url": "https://www.schneider-electric.com/en/download/document/SEVD-2018-270-01/"
        }
      ],
      "x_legacyV4Record": {
        "CVE_data_meta": {
          "ASSIGNER": "cybersecurity@schneider-electric.com",
          "ID": "CVE-2018-7798",
          "STATE": "PUBLIC"
        },
        "affects": {
          "vendor": {
            "vendor_data": [
              {
                "product": {
                  "product_data": [
                    {
                      "product_name": "Modicon M221, All Versions",
                      "version": {
                        "version_data": [
                          {
                            "version_value": "Modicon M221, All Versions"
                          }
                        ]
                      }
                    }
                  ]
                },
                "vendor_name": "Schneider Electric SE"
              }
            ]
          }
        },
        "data_format": "MITRE",
        "data_type": "CVE",
        "data_version": "4.0",
        "description": {
          "description_data": [
            {
              "lang": "eng",
              "value": "A Insufficient Verification of Data Authenticity (CWE-345) vulnerability exists in the Modicon M221, all versions, which could cause a change of IPv4 configuration (IP address, mask and gateway) when remotely connected to the device."
            }
          ]
        },
        "problemtype": {
          "problemtype_data": [
            {
              "description": [
                {
                  "lang": "eng",
                  "value": "Insufficient Verification of Data Authenticity"
                }
              ]
            }
          ]
        },
        "references": {
          "reference_data": [
            {
              "name": "105970",
              "refsource": "BID",
              "url": "http://www.securityfocus.com/bid/105970"
            },
            {
              "name": "https://www.schneider-electric.com/en/download/document/SEVD-2018-270-01/",
              "refsource": "CONFIRM",
              "url": "https://www.schneider-electric.com/en/download/document/SEVD-2018-270-01/"
            }
          ]
        }
      }
    }
  },
  "cveMetadata": {
    "assignerOrgId": "076d1eb6-cfab-4401-b34d-6dfc2a413bdb",
    "assignerShortName": "schneider",
    "cveId": "CVE-2018-7798",
    "datePublished": "2018-11-02T17:00:00.000Z",
    "dateReserved": "2018-03-08T00:00:00.000Z",
    "dateUpdated": "2026-05-29T14:09:12.112Z",
    "state": "PUBLISHED"
  },
  "dataType": "CVE_RECORD",
  "dataVersion": "5.2",
  "vulnerability-lookup:meta": {
    "epss": {
      "cve": "CVE-2018-7798",
      "date": "2026-09-24",
      "epss": "0.00655",
      "percentile": "0.49135"
    },
    "fkie_nvd": {
      "configurations": [
        {
          "nodes": [
            {
              "cpeMatch": [
                {
                  "criteria": "cpe:2.3:a:schneider-electric:somachine_basic:*:*:*:*:*:*:*:*",
                  "matchCriteriaId": "2BCEA269-6242-41FD-B141-F72CAFC8F114",
                  "vulnerable": true
                }
              ],
              "negate": false,
              "operator": "OR"
            },
            {
              "cpeMatch": [
                {
                  "criteria": "cpe:2.3:h:schneider-electric:modicon_m221:-:*:*:*:*:*:*:*",
                  "matchCriteriaId": "BB0D83F4-B718-47AB-AFB8-B576CB138AAC",
                  "vulnerable": false
                }
              ],
              "negate": false,
              "operator": "OR"
            }
          ],
          "operator": "AND"
        }
      ],
      "descriptions": [
        {
          "lang": "en",
          "value": "A Insufficient Verification of Data Authenticity (CWE-345) vulnerability exists in the Modicon M221, all versions, which could cause a change of IPv4 configuration (IP address, mask and gateway) when remotely connected to the device."
        },
        {
          "lang": "es",
          "value": "Existe una vulnerabilidad de verificaci\u00f3n insuficiente de autenticidad de datos (CWE-345) en Modicon Modicon M221, todas las versiones, lo que podr\u00eda provocar un cambio en la configuraci\u00f3n IPv4 (direcci\u00f3n IP, m\u00e1scara y puerta de enlace) al conectarse remotamente al dispositivo."
        }
      ],
      "id": "CVE-2018-7798",
      "lastModified": "2024-11-21T04:12:45.347",
      "metrics": {
        "cvssMetricV2": [
          {
            "acInsufInfo": false,
            "baseSeverity": "MEDIUM",
            "cvssData": {
              "accessComplexity": "LOW",
              "accessVector": "NETWORK",
              "authentication": "NONE",
              "availabilityImpact": "PARTIAL",
              "baseScore": 6.4,
              "confidentialityImpact": "NONE",
              "integrityImpact": "PARTIAL",
              "vectorString": "AV:N/AC:L/Au:N/C:N/I:P/A:P",
              "version": "2.0"
            },
            "exploitabilityScore": 10.0,
            "impactScore": 4.9,
            "obtainAllPrivilege": false,
            "obtainOtherPrivilege": false,
            "obtainUserPrivilege": false,
            "source": "nvd@nist.gov",
            "type": "Primary",
            "userInteractionRequired": false
          }
        ],
        "cvssMetricV31": [
          {
            "cvssData": {
              "attackComplexity": "LOW",
              "attackVector": "NETWORK",
              "availabilityImpact": "LOW",
              "baseScore": 8.2,
              "baseSeverity": "HIGH",
              "confidentialityImpact": "NONE",
              "integrityImpact": "HIGH",
              "privilegesRequired": "NONE",
              "scope": "UNCHANGED",
              "userInteraction": "NONE",
              "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:H/A:L",
              "version": "3.1"
            },
            "exploitabilityScore": 3.9,
            "impactScore": 4.2,
            "source": "nvd@nist.gov",
            "type": "Primary"
          }
        ]
      },
      "published": "2018-11-02T17:29:00.680",
      "references": [
        {
          "source": "cybersecurity@se.com",
          "tags": [
            "Third Party Advisory",
            "VDB Entry"
          ],
          "url": "http://www.securityfocus.com/bid/105970"
        },
        {
          "source": "cybersecurity@se.com",
          "tags": [
            "Mitigation",
            "Vendor Advisory"
          ],
          "url": "https://www.schneider-electric.com/en/download/document/SEVD-2018-270-01/"
        },
        {
          "source": "af854a3a-2127-422b-91ae-364da2661108",
          "tags": [
            "Third Party Advisory",
            "VDB Entry"
          ],
          "url": "http://www.securityfocus.com/bid/105970"
        },
        {
          "source": "af854a3a-2127-422b-91ae-364da2661108",
          "tags": [
            "Mitigation",
            "Vendor Advisory"
          ],
          "url": "https://www.schneider-electric.com/en/download/document/SEVD-2018-270-01/"
        }
      ],
      "sourceIdentifier": "cybersecurity@se.com",
      "vulnStatus": "Modified",
      "weaknesses": [
        {
          "description": [
            {
              "lang": "en",
              "value": "CWE-345"
            }
          ],
          "source": "nvd@nist.gov",
          "type": "Primary"
        }
      ]
    },
    "nvd": {
      "cve": {
        "configurations": [
          {
            "nodes": [
              {
                "cpeMatch": [
                  {
                    "criteria": "cpe:2.3:a:schneider-electric:somachine_basic:*:*:*:*:*:*:*:*",
                    "matchCriteriaId": "2BCEA269-6242-41FD-B141-F72CAFC8F114",
                    "vulnerable": true
                  }
                ],
                "negate": false,
                "operator": "OR"
              },
              {
                "cpeMatch": [
                  {
                    "criteria": "cpe:2.3:h:schneider-electric:modicon_m221:-:*:*:*:*:*:*:*",
                    "matchCriteriaId": "BB0D83F4-B718-47AB-AFB8-B576CB138AAC",
                    "vulnerable": false
                  }
                ],
                "negate": false,
                "operator": "OR"
              }
            ],
            "operator": "AND"
          }
        ],
        "cveTags": [],
        "descriptions": [
          {
            "lang": "en",
            "value": "A Insufficient Verification of Data Authenticity (CWE-345) vulnerability exists in the Modicon M221, all versions, which could cause a change of IPv4 configuration (IP address, mask and gateway) when remotely connected to the device."
          },
          {
            "lang": "es",
            "value": "Existe una vulnerabilidad de verificaci\u00f3n insuficiente de autenticidad de datos (CWE-345) en Modicon Modicon M221, todas las versiones, lo que podr\u00eda provocar un cambio en la configuraci\u00f3n IPv4 (direcci\u00f3n IP, m\u00e1scara y puerta de enlace) al conectarse remotamente al dispositivo."
          }
        ],
        "id": "CVE-2018-7798",
        "lastModified": "2026-05-29T15:16:16.993",
        "metrics": {
          "cvssMetricV2": [
            {
              "acInsufInfo": false,
              "baseSeverity": "MEDIUM",
              "cvssData": {
                "accessComplexity": "LOW",
                "accessVector": "NETWORK",
                "authentication": "NONE",
                "availabilityImpact": "PARTIAL",
                "baseScore": 6.4,
                "confidentialityImpact": "NONE",
                "integrityImpact": "PARTIAL",
                "vectorString": "AV:N/AC:L/Au:N/C:N/I:P/A:P",
                "version": "2.0"
              },
              "exploitabilityScore": 10.0,
              "impactScore": 4.9,
              "obtainAllPrivilege": false,
              "obtainOtherPrivilege": false,
              "obtainUserPrivilege": false,
              "source": "nvd@nist.gov",
              "type": "Primary",
              "userInteractionRequired": false
            }
          ],
          "cvssMetricV31": [
            {
              "cvssData": {
                "attackComplexity": "LOW",
                "attackVector": "NETWORK",
                "availabilityImpact": "LOW",
                "baseScore": 8.2,
                "baseSeverity": "HIGH",
                "confidentialityImpact": "NONE",
                "integrityImpact": "HIGH",
                "privilegesRequired": "NONE",
                "scope": "UNCHANGED",
                "userInteraction": "NONE",
                "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:H/A:L",
                "version": "3.1"
              },
              "exploitabilityScore": 3.9,
              "impactScore": 4.2,
              "source": "nvd@nist.gov",
              "type": "Primary"
            },
            {
              "cvssData": {
                "attackComplexity": "LOW",
                "attackVector": "NETWORK",
                "availabilityImpact": "LOW",
                "baseScore": 8.2,
                "baseSeverity": "HIGH",
                "confidentialityImpact": "NONE",
                "integrityImpact": "HIGH",
                "privilegesRequired": "NONE",
                "scope": "UNCHANGED",
                "userInteraction": "NONE",
                "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:H/A:L",
                "version": "3.1"
              },
              "exploitabilityScore": 3.9,
              "impactScore": 4.2,
              "source": "134c704f-9b21-4f2e-91b3-4a467353bcc0",
              "type": "Secondary"
            }
          ]
        },
        "published": "2018-11-02T17:29:00.680",
        "references": [
          {
            "source": "cybersecurity@se.com",
            "tags": [
              "Third Party Advisory",
              "VDB Entry"
            ],
            "url": "http://www.securityfocus.com/bid/105970"
          },
          {
            "source": "cybersecurity@se.com",
            "tags": [
              "Mitigation",
              "Vendor Advisory"
            ],
            "url": "https://www.schneider-electric.com/en/download/document/SEVD-2018-270-01/"
          },
          {
            "source": "af854a3a-2127-422b-91ae-364da2661108",
            "tags": [
              "Third Party Advisory",
              "VDB Entry"
            ],
            "url": "http://www.securityfocus.com/bid/105970"
          },
          {
            "source": "af854a3a-2127-422b-91ae-364da2661108",
            "tags": [
              "Mitigation",
              "Vendor Advisory"
            ],
            "url": "https://www.schneider-electric.com/en/download/document/SEVD-2018-270-01/"
          }
        ],
        "sourceIdentifier": "cybersecurity@se.com",
        "vulnStatus": "Modified",
        "weaknesses": [
          {
            "description": [
              {
                "lang": "en",
                "value": "CWE-345"
              }
            ],
            "source": "nvd@nist.gov",
            "type": "Primary"
          },
          {
            "description": [
              {
                "lang": "en",
                "value": "CWE-345"
              }
            ],
            "source": "134c704f-9b21-4f2e-91b3-4a467353bcc0",
            "type": "Secondary"
          }
        ]
      }
    },
    "vulnrichment": {
      "containers": {
        "adp": [
          {
            "providerMetadata": {
              "dateUpdated": "2024-08-05T06:37:59.359Z",
              "orgId": "af854a3a-2127-422b-91ae-364da2661108",
              "shortName": "CVE"
            },
            "references": [
              {
                "name": "105970",
                "tags": [
                  "vdb-entry",
                  "x_refsource_BID",
                  "x_transferred"
                ],
                "url": "http://www.securityfocus.com/bid/105970"
              },
              {
                "tags": [
                  "x_refsource_CONFIRM",
                  "x_transferred"
                ],
                "url": "https://www.schneider-electric.com/en/download/document/SEVD-2018-270-01/"
              }
            ],
            "title": "CVE Program Container"
          },
          {
            "metrics": [
              {
                "cvssV3_1": {
                  "attackComplexity": "LOW",
                  "attackVector": "NETWORK",
                  "availabilityImpact": "LOW",
                  "baseScore": 8.2,
                  "baseSeverity": "HIGH",
                  "confidentialityImpact": "NONE",
                  "integrityImpact": "HIGH",
                  "privilegesRequired": "NONE",
                  "scope": "UNCHANGED",
                  "userInteraction": "NONE",
                  "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:H/A:L",
                  "version": "3.1"
                }
              },
              {
                "other": {
                  "content": {
                    "id": "CVE-2018-7798",
                    "options": [
                      {
                        "Exploitation": "none"
                      },
                      {
                        "Automatable": "yes"
                      },
                      {
                        "Technical Impact": "partial"
                      }
                    ],
                    "role": "CISA Coordinator",
                    "timestamp": "2026-05-29T14:08:28.530951Z",
                    "version": "2.0.3"
                  },
                  "type": "ssvc"
                }
              }
            ],
            "problemTypes": [
              {
                "descriptions": [
                  {
                    "cweId": "CWE-345",
                    "description": "CWE-345 Insufficient Verification of Data Authenticity",
                    "lang": "en",
                    "type": "CWE"
                  }
                ]
              }
            ],
            "providerMetadata": {
              "dateUpdated": "2026-05-29T14:09:00.678Z",
              "orgId": "134c704f-9b21-4f2e-91b3-4a467353bcc0",
              "shortName": "CISA-ADP"
            },
            "title": "CISA ADP Vulnrichment"
          }
        ],
        "cna": {
          "affected": [
            {
              "product": "Modicon M221, All Versions",
              "vendor": "Schneider Electric SE",
              "versions": [
                {
                  "status": "affected",
                  "version": "Modicon M221, All Versions"
                }
              ]
            }
          ],
          "datePublic": "2018-11-02T00:00:00.000Z",
          "descriptions": [
            {
              "lang": "en",
              "value": "A Insufficient Verification of Data Authenticity (CWE-345) vulnerability exists in the Modicon M221, all versions, which could cause a change of IPv4 configuration (IP address, mask and gateway) when remotely connected to the device."
            }
          ],
          "problemTypes": [
            {
              "descriptions": [
                {
                  "description": "Insufficient Verification of Data Authenticity",
                  "lang": "en",
                  "type": "text"
                }
              ]
            }
          ],
          "providerMetadata": {
            "dateUpdated": "2018-11-21T10:57:01.000Z",
            "orgId": "076d1eb6-cfab-4401-b34d-6dfc2a413bdb",
            "shortName": "schneider"
          },
          "references": [
            {
              "name": "105970",
              "tags": [
                "vdb-entry",
                "x_refsource_BID"
              ],
              "url": "http://www.securityfocus.com/bid/105970"
            },
            {
              "tags": [
                "x_refsource_CONFIRM"
              ],
              "url": "https://www.schneider-electric.com/en/download/document/SEVD-2018-270-01/"
            }
          ],
          "x_legacyV4Record": {
            "CVE_data_meta": {
              "ASSIGNER": "cybersecurity@schneider-electric.com",
              "ID": "CVE-2018-7798",
              "STATE": "PUBLIC"
            },
            "affects": {
              "vendor": {
                "vendor_data": [
                  {
                    "product": {
                      "product_data": [
                        {
                          "product_name": "Modicon M221, All Versions",
                          "version": {
                            "version_data": [
                              {
                                "version_value": "Modicon M221, All Versions"
                              }
                            ]
                          }
                        }
                      ]
                    },
                    "vendor_name": "Schneider Electric SE"
                  }
                ]
              }
            },
            "data_format": "MITRE",
            "data_type": "CVE",
            "data_version": "4.0",
            "description": {
              "description_data": [
                {
                  "lang": "eng",
                  "value": "A Insufficient Verification of Data Authenticity (CWE-345) vulnerability exists in the Modicon M221, all versions, which could cause a change of IPv4 configuration (IP address, mask and gateway) when remotely connected to the device."
                }
              ]
            },
            "problemtype": {
              "problemtype_data": [
                {
                  "description": [
                    {
                      "lang": "eng",
                      "value": "Insufficient Verification of Data Authenticity"
                    }
                  ]
                }
              ]
            },
            "references": {
              "reference_data": [
                {
                  "name": "105970",
                  "refsource": "BID",
                  "url": "http://www.securityfocus.com/bid/105970"
                },
                {
                  "name": "https://www.schneider-electric.com/en/download/document/SEVD-2018-270-01/",
                  "refsource": "CONFIRM",
                  "url": "https://www.schneider-electric.com/en/download/document/SEVD-2018-270-01/"
                }
              ]
            }
          }
        }
      },
      "cveMetadata": {
        "assignerOrgId": "076d1eb6-cfab-4401-b34d-6dfc2a413bdb",
        "assignerShortName": "schneider",
        "cveId": "CVE-2018-7798",
        "datePublished": "2018-11-02T17:00:00.000Z",
        "dateReserved": "2018-03-08T00:00:00.000Z",
        "dateUpdated": "2026-05-29T14:09:12.112Z",
        "state": "PUBLISHED"
      },
      "dataType": "CVE_RECORD",
      "dataVersion": "5.2"
    }
  }
}



Log in or create an account to share your comment.




Tags
Taxonomy of the tags.


Loading…

Loading…

Loading…

Forecast uses a logistic model when the trend is rising, or an exponential decay model when the trend is falling. Fitted via linearized least squares.

Sightings

Author Source Type Date Other

Nomenclature

  • Seen: The vulnerability was mentioned, discussed, or observed by the user.
  • Confirmed: The vulnerability has been validated from an analyst's perspective.
  • Published Proof of Concept: A public proof of concept is available for this vulnerability.
  • Exploited: The vulnerability was observed as exploited by the user who reported the sighting.
  • Patched: The vulnerability was observed as successfully patched by the user who reported the sighting.
  • Not exploited: The vulnerability was not observed as exploited by the user who reported the sighting.
  • Not confirmed: The user expressed doubt about the validity of the vulnerability.
  • Not patched: The vulnerability was not observed as successfully patched by the user who reported the sighting.

Loading…

Loading…

Loading…

Related by attack behaviour

Vulnerabilities whose description is nearest to this one in the vector space of the CIRCL/vulnerability-attack-technique-biencoder model. This is a similarity search over the bi-encoder space (plain cosine), not a classification, and it has no measured accuracy.


Loading…