CVE-2019-6829 (GCVE-0-2019-6829)

Vulnerability from cvelistv5 – Published: 2019-09-17 19:44 – Updated: 2026-05-29 14:35
VLAI
Summary
A CWE-248: Uncaught Exception vulnerability exists in Modicon M580 (firmware version prior to V2.90) and Modicon M340 (firmware version prior to V3.10), which could cause a possible denial of service when writing to specific memory addresses in the controller over Modbus.
SSVC
Exploitation: poc Automatable: yes Technical Impact: partial
CISA Coordinator · CISA-ADP (v2.0.3)
Decision recorded 2026-05-29 14:34 UTC
CWE
  • CWE-248 - A CWE-248: Uncaught Exception
References
Impacted products
Vendor Product Version CPE status
Schneider Electric SE Modicon M580 Affected: firmware version prior to V2.90
guessed Create a notification for this product.
Schneider Electric SE Modicon M340 Affected: firmware version prior to V3.10
guessed Create a notification for this product.
Show details on NVD website

{
  "containers": {
    "adp": [
      {
        "providerMetadata": {
          "dateUpdated": "2024-08-04T20:31:04.339Z",
          "orgId": "af854a3a-2127-422b-91ae-364da2661108",
          "shortName": "CVE"
        },
        "references": [
          {
            "tags": [
              "x_refsource_CONFIRM",
              "x_transferred"
            ],
            "url": "https://www.schneider-electric.com/en/download/document/SEVD-2019-134-11/"
          }
        ],
        "title": "CVE Program Container"
      },
      {
        "metrics": [
          {
            "cvssV3_1": {
              "attackComplexity": "LOW",
              "attackVector": "NETWORK",
              "availabilityImpact": "HIGH",
              "baseScore": 7.5,
              "baseSeverity": "HIGH",
              "confidentialityImpact": "NONE",
              "integrityImpact": "NONE",
              "privilegesRequired": "NONE",
              "scope": "UNCHANGED",
              "userInteraction": "NONE",
              "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H",
              "version": "3.1"
            }
          },
          {
            "other": {
              "content": {
                "id": "CVE-2019-6829",
                "options": [
                  {
                    "Exploitation": "poc"
                  },
                  {
                    "Automatable": "yes"
                  },
                  {
                    "Technical Impact": "partial"
                  }
                ],
                "role": "CISA Coordinator",
                "timestamp": "2026-05-29T14:34:30.342289Z",
                "version": "2.0.3"
              },
              "type": "ssvc"
            }
          }
        ],
        "providerMetadata": {
          "dateUpdated": "2026-05-29T14:35:20.646Z",
          "orgId": "134c704f-9b21-4f2e-91b3-4a467353bcc0",
          "shortName": "CISA-ADP"
        },
        "title": "CISA ADP Vulnrichment"
      }
    ],
    "cna": {
      "affected": [
        {
          "product": "Modicon M580",
          "vendor": "Schneider Electric SE",
          "versions": [
            {
              "status": "affected",
              "version": "firmware version prior to V2.90"
            }
          ]
        },
        {
          "product": "Modicon M340",
          "vendor": "Schneider Electric SE",
          "versions": [
            {
              "status": "affected",
              "version": "firmware version prior to V3.10"
            }
          ]
        }
      ],
      "descriptions": [
        {
          "lang": "en",
          "value": "A CWE-248: Uncaught Exception vulnerability exists in Modicon M580 (firmware version prior to V2.90) and Modicon M340 (firmware version prior to V3.10), which could cause a possible denial of service when writing to specific memory addresses in the controller over Modbus."
        }
      ],
      "problemTypes": [
        {
          "descriptions": [
            {
              "cweId": "CWE-248",
              "description": "A CWE-248: Uncaught Exception",
              "lang": "en",
              "type": "CWE"
            }
          ]
        }
      ],
      "providerMetadata": {
        "dateUpdated": "2019-09-17T19:44:12.000Z",
        "orgId": "076d1eb6-cfab-4401-b34d-6dfc2a413bdb",
        "shortName": "schneider"
      },
      "references": [
        {
          "tags": [
            "x_refsource_CONFIRM"
          ],
          "url": "https://www.schneider-electric.com/en/download/document/SEVD-2019-134-11/"
        }
      ],
      "x_legacyV4Record": {
        "CVE_data_meta": {
          "ASSIGNER": "cybersecurity@schneider-electric.com",
          "ID": "CVE-2019-6829",
          "STATE": "PUBLIC"
        },
        "affects": {
          "vendor": {
            "vendor_data": [
              {
                "product": {
                  "product_data": [
                    {
                      "product_name": "Modicon M580",
                      "version": {
                        "version_data": [
                          {
                            "version_value": "firmware version prior to V2.90"
                          }
                        ]
                      }
                    },
                    {
                      "product_name": "Modicon M340",
                      "version": {
                        "version_data": [
                          {
                            "version_value": "firmware version prior to V3.10"
                          }
                        ]
                      }
                    }
                  ]
                },
                "vendor_name": "Schneider Electric SE"
              }
            ]
          }
        },
        "data_format": "MITRE",
        "data_type": "CVE",
        "data_version": "4.0",
        "description": {
          "description_data": [
            {
              "lang": "eng",
              "value": "A CWE-248: Uncaught Exception vulnerability exists in Modicon M580 (firmware version prior to V2.90) and Modicon M340 (firmware version prior to V3.10), which could cause a possible denial of service when writing to specific memory addresses in the controller over Modbus."
            }
          ]
        },
        "problemtype": {
          "problemtype_data": [
            {
              "description": [
                {
                  "lang": "eng",
                  "value": "A CWE-248: Uncaught Exception"
                }
              ]
            }
          ]
        },
        "references": {
          "reference_data": [
            {
              "name": "https://www.schneider-electric.com/en/download/document/SEVD-2019-134-11/",
              "refsource": "CONFIRM",
              "url": "https://www.schneider-electric.com/en/download/document/SEVD-2019-134-11/"
            }
          ]
        }
      }
    }
  },
  "cveMetadata": {
    "assignerOrgId": "076d1eb6-cfab-4401-b34d-6dfc2a413bdb",
    "assignerShortName": "schneider",
    "cveId": "CVE-2019-6829",
    "datePublished": "2019-09-17T19:44:12.000Z",
    "dateReserved": "2019-01-25T00:00:00.000Z",
    "dateUpdated": "2026-05-29T14:35:20.646Z",
    "state": "PUBLISHED"
  },
  "dataType": "CVE_RECORD",
  "dataVersion": "5.2",
  "vulnerability-lookup:meta": {
    "epss": {
      "cve": "CVE-2019-6829",
      "date": "2026-09-28",
      "epss": "0.01609",
      "percentile": "0.74949"
    },
    "fkie_nvd": {
      "configurations": [
        {
          "nodes": [
            {
              "cpeMatch": [
                {
                  "criteria": "cpe:2.3:o:schneider-electric:modicon_m580_firmware:*:*:*:*:*:*:*:*",
                  "matchCriteriaId": "B9C5B0D1-D3A4-468A-807E-6BB3F98CC116",
                  "versionEndExcluding": "2.90",
                  "vulnerable": true
                }
              ],
              "negate": false,
              "operator": "OR"
            },
            {
              "cpeMatch": [
                {
                  "criteria": "cpe:2.3:h:schneider-electric:modicon_m580:-:*:*:*:*:*:*:*",
                  "matchCriteriaId": "E876C738-ABF6-4864-98A6-1E06E96A0DF4",
                  "vulnerable": false
                }
              ],
              "negate": false,
              "operator": "OR"
            }
          ],
          "operator": "AND"
        },
        {
          "nodes": [
            {
              "cpeMatch": [
                {
                  "criteria": "cpe:2.3:o:schneider-electric:modicon_m340_firmware:*:*:*:*:*:*:*:*",
                  "matchCriteriaId": "3FD2397C-67A1-4AFD-BC42-6ECC3BD88C24",
                  "versionEndExcluding": "3.10",
                  "vulnerable": true
                }
              ],
              "negate": false,
              "operator": "OR"
            },
            {
              "cpeMatch": [
                {
                  "criteria": "cpe:2.3:h:schneider-electric:modicon_m340:-:*:*:*:*:*:*:*",
                  "matchCriteriaId": "138681A2-0146-492B-8E10-06849FC27C6E",
                  "vulnerable": false
                }
              ],
              "negate": false,
              "operator": "OR"
            }
          ],
          "operator": "AND"
        }
      ],
      "descriptions": [
        {
          "lang": "en",
          "value": "A CWE-248: Uncaught Exception vulnerability exists in Modicon M580 (firmware version prior to V2.90) and Modicon M340 (firmware version prior to V3.10), which could cause a possible denial of service when writing to specific memory addresses in the controller over Modbus."
        },
        {
          "lang": "es",
          "value": "Una CWE-248: Se presenta una vulnerabilidad de Excepci\u00f3n No Capturada en Modicon M580 (versi\u00f3n de firmware anterior a V2.90) y Modicon M340 (versi\u00f3n de firmware anterior a V3.10), lo que podr\u00eda causar una posible denegaci\u00f3n de servicio durante la escritura en direcciones espec\u00edficas de memoria  en el controlador sobre protocolo Modbus."
        }
      ],
      "id": "CVE-2019-6829",
      "lastModified": "2024-11-21T04:47:14.157",
      "metrics": {
        "cvssMetricV2": [
          {
            "acInsufInfo": false,
            "baseSeverity": "HIGH",
            "cvssData": {
              "accessComplexity": "LOW",
              "accessVector": "NETWORK",
              "authentication": "NONE",
              "availabilityImpact": "COMPLETE",
              "baseScore": 7.8,
              "confidentialityImpact": "NONE",
              "integrityImpact": "NONE",
              "vectorString": "AV:N/AC:L/Au:N/C:N/I:N/A:C",
              "version": "2.0"
            },
            "exploitabilityScore": 10.0,
            "impactScore": 6.9,
            "obtainAllPrivilege": false,
            "obtainOtherPrivilege": false,
            "obtainUserPrivilege": false,
            "source": "nvd@nist.gov",
            "type": "Primary",
            "userInteractionRequired": false
          }
        ],
        "cvssMetricV31": [
          {
            "cvssData": {
              "attackComplexity": "LOW",
              "attackVector": "NETWORK",
              "availabilityImpact": "HIGH",
              "baseScore": 7.5,
              "baseSeverity": "HIGH",
              "confidentialityImpact": "NONE",
              "integrityImpact": "NONE",
              "privilegesRequired": "NONE",
              "scope": "UNCHANGED",
              "userInteraction": "NONE",
              "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H",
              "version": "3.1"
            },
            "exploitabilityScore": 3.9,
            "impactScore": 3.6,
            "source": "nvd@nist.gov",
            "type": "Primary"
          }
        ]
      },
      "published": "2019-09-17T20:15:12.203",
      "references": [
        {
          "source": "cybersecurity@se.com",
          "tags": [
            "Vendor Advisory"
          ],
          "url": "https://www.schneider-electric.com/en/download/document/SEVD-2019-134-11/"
        },
        {
          "source": "af854a3a-2127-422b-91ae-364da2661108",
          "tags": [
            "Vendor Advisory"
          ],
          "url": "https://www.schneider-electric.com/en/download/document/SEVD-2019-134-11/"
        }
      ],
      "sourceIdentifier": "cybersecurity@se.com",
      "vulnStatus": "Modified",
      "weaknesses": [
        {
          "description": [
            {
              "lang": "en",
              "value": "CWE-248"
            }
          ],
          "source": "cybersecurity@se.com",
          "type": "Secondary"
        },
        {
          "description": [
            {
              "lang": "en",
              "value": "CWE-755"
            }
          ],
          "source": "nvd@nist.gov",
          "type": "Primary"
        }
      ]
    },
    "nvd": {
      "cve": {
        "configurations": [
          {
            "nodes": [
              {
                "cpeMatch": [
                  {
                    "criteria": "cpe:2.3:o:schneider-electric:modicon_m580_firmware:*:*:*:*:*:*:*:*",
                    "matchCriteriaId": "B9C5B0D1-D3A4-468A-807E-6BB3F98CC116",
                    "versionEndExcluding": "2.90",
                    "vulnerable": true
                  }
                ],
                "negate": false,
                "operator": "OR"
              },
              {
                "cpeMatch": [
                  {
                    "criteria": "cpe:2.3:h:schneider-electric:modicon_m580:-:*:*:*:*:*:*:*",
                    "matchCriteriaId": "E876C738-ABF6-4864-98A6-1E06E96A0DF4",
                    "vulnerable": false
                  }
                ],
                "negate": false,
                "operator": "OR"
              }
            ],
            "operator": "AND"
          },
          {
            "nodes": [
              {
                "cpeMatch": [
                  {
                    "criteria": "cpe:2.3:o:schneider-electric:modicon_m340_firmware:*:*:*:*:*:*:*:*",
                    "matchCriteriaId": "3FD2397C-67A1-4AFD-BC42-6ECC3BD88C24",
                    "versionEndExcluding": "3.10",
                    "vulnerable": true
                  }
                ],
                "negate": false,
                "operator": "OR"
              },
              {
                "cpeMatch": [
                  {
                    "criteria": "cpe:2.3:h:schneider-electric:modicon_m340:-:*:*:*:*:*:*:*",
                    "matchCriteriaId": "138681A2-0146-492B-8E10-06849FC27C6E",
                    "vulnerable": false
                  }
                ],
                "negate": false,
                "operator": "OR"
              }
            ],
            "operator": "AND"
          }
        ],
        "cveTags": [],
        "descriptions": [
          {
            "lang": "en",
            "value": "A CWE-248: Uncaught Exception vulnerability exists in Modicon M580 (firmware version prior to V2.90) and Modicon M340 (firmware version prior to V3.10), which could cause a possible denial of service when writing to specific memory addresses in the controller over Modbus."
          },
          {
            "lang": "es",
            "value": "Una CWE-248: Se presenta una vulnerabilidad de Excepci\u00f3n No Capturada en Modicon M580 (versi\u00f3n de firmware anterior a V2.90) y Modicon M340 (versi\u00f3n de firmware anterior a V3.10), lo que podr\u00eda causar una posible denegaci\u00f3n de servicio durante la escritura en direcciones espec\u00edficas de memoria  en el controlador sobre protocolo Modbus."
          }
        ],
        "id": "CVE-2019-6829",
        "lastModified": "2026-05-29T15:16:17.713",
        "metrics": {
          "cvssMetricV2": [
            {
              "acInsufInfo": false,
              "baseSeverity": "HIGH",
              "cvssData": {
                "accessComplexity": "LOW",
                "accessVector": "NETWORK",
                "authentication": "NONE",
                "availabilityImpact": "COMPLETE",
                "baseScore": 7.8,
                "confidentialityImpact": "NONE",
                "integrityImpact": "NONE",
                "vectorString": "AV:N/AC:L/Au:N/C:N/I:N/A:C",
                "version": "2.0"
              },
              "exploitabilityScore": 10.0,
              "impactScore": 6.9,
              "obtainAllPrivilege": false,
              "obtainOtherPrivilege": false,
              "obtainUserPrivilege": false,
              "source": "nvd@nist.gov",
              "type": "Primary",
              "userInteractionRequired": false
            }
          ],
          "cvssMetricV31": [
            {
              "cvssData": {
                "attackComplexity": "LOW",
                "attackVector": "NETWORK",
                "availabilityImpact": "HIGH",
                "baseScore": 7.5,
                "baseSeverity": "HIGH",
                "confidentialityImpact": "NONE",
                "integrityImpact": "NONE",
                "privilegesRequired": "NONE",
                "scope": "UNCHANGED",
                "userInteraction": "NONE",
                "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H",
                "version": "3.1"
              },
              "exploitabilityScore": 3.9,
              "impactScore": 3.6,
              "source": "nvd@nist.gov",
              "type": "Primary"
            },
            {
              "cvssData": {
                "attackComplexity": "LOW",
                "attackVector": "NETWORK",
                "availabilityImpact": "HIGH",
                "baseScore": 7.5,
                "baseSeverity": "HIGH",
                "confidentialityImpact": "NONE",
                "integrityImpact": "NONE",
                "privilegesRequired": "NONE",
                "scope": "UNCHANGED",
                "userInteraction": "NONE",
                "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H",
                "version": "3.1"
              },
              "exploitabilityScore": 3.9,
              "impactScore": 3.6,
              "source": "134c704f-9b21-4f2e-91b3-4a467353bcc0",
              "type": "Secondary"
            }
          ]
        },
        "published": "2019-09-17T20:15:12.203",
        "references": [
          {
            "source": "cybersecurity@se.com",
            "tags": [
              "Vendor Advisory"
            ],
            "url": "https://www.schneider-electric.com/en/download/document/SEVD-2019-134-11/"
          },
          {
            "source": "af854a3a-2127-422b-91ae-364da2661108",
            "tags": [
              "Vendor Advisory"
            ],
            "url": "https://www.schneider-electric.com/en/download/document/SEVD-2019-134-11/"
          }
        ],
        "sourceIdentifier": "cybersecurity@se.com",
        "vulnStatus": "Modified",
        "weaknesses": [
          {
            "description": [
              {
                "lang": "en",
                "value": "CWE-248"
              }
            ],
            "source": "cybersecurity@se.com",
            "type": "Secondary"
          },
          {
            "description": [
              {
                "lang": "en",
                "value": "CWE-755"
              }
            ],
            "source": "nvd@nist.gov",
            "type": "Primary"
          }
        ]
      }
    },
    "vulnrichment": {
      "containers": {
        "adp": [
          {
            "providerMetadata": {
              "dateUpdated": "2024-08-04T20:31:04.339Z",
              "orgId": "af854a3a-2127-422b-91ae-364da2661108",
              "shortName": "CVE"
            },
            "references": [
              {
                "tags": [
                  "x_refsource_CONFIRM",
                  "x_transferred"
                ],
                "url": "https://www.schneider-electric.com/en/download/document/SEVD-2019-134-11/"
              }
            ],
            "title": "CVE Program Container"
          },
          {
            "metrics": [
              {
                "cvssV3_1": {
                  "attackComplexity": "LOW",
                  "attackVector": "NETWORK",
                  "availabilityImpact": "HIGH",
                  "baseScore": 7.5,
                  "baseSeverity": "HIGH",
                  "confidentialityImpact": "NONE",
                  "integrityImpact": "NONE",
                  "privilegesRequired": "NONE",
                  "scope": "UNCHANGED",
                  "userInteraction": "NONE",
                  "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H",
                  "version": "3.1"
                }
              },
              {
                "other": {
                  "content": {
                    "id": "CVE-2019-6829",
                    "options": [
                      {
                        "Exploitation": "poc"
                      },
                      {
                        "Automatable": "yes"
                      },
                      {
                        "Technical Impact": "partial"
                      }
                    ],
                    "role": "CISA Coordinator",
                    "timestamp": "2026-05-29T14:34:30.342289Z",
                    "version": "2.0.3"
                  },
                  "type": "ssvc"
                }
              }
            ],
            "providerMetadata": {
              "dateUpdated": "2026-05-29T14:32:20.976Z",
              "orgId": "134c704f-9b21-4f2e-91b3-4a467353bcc0",
              "shortName": "CISA-ADP"
            },
            "title": "CISA ADP Vulnrichment"
          }
        ],
        "cna": {
          "affected": [
            {
              "product": "Modicon M580",
              "vendor": "Schneider Electric SE",
              "versions": [
                {
                  "status": "affected",
                  "version": "firmware version prior to V2.90"
                }
              ]
            },
            {
              "product": "Modicon M340",
              "vendor": "Schneider Electric SE",
              "versions": [
                {
                  "status": "affected",
                  "version": "firmware version prior to V3.10"
                }
              ]
            }
          ],
          "descriptions": [
            {
              "lang": "en",
              "value": "A CWE-248: Uncaught Exception vulnerability exists in Modicon M580 (firmware version prior to V2.90) and Modicon M340 (firmware version prior to V3.10), which could cause a possible denial of service when writing to specific memory addresses in the controller over Modbus."
            }
          ],
          "problemTypes": [
            {
              "descriptions": [
                {
                  "cweId": "CWE-248",
                  "description": "A CWE-248: Uncaught Exception",
                  "lang": "en",
                  "type": "CWE"
                }
              ]
            }
          ],
          "providerMetadata": {
            "dateUpdated": "2019-09-17T19:44:12.000Z",
            "orgId": "076d1eb6-cfab-4401-b34d-6dfc2a413bdb",
            "shortName": "schneider"
          },
          "references": [
            {
              "tags": [
                "x_refsource_CONFIRM"
              ],
              "url": "https://www.schneider-electric.com/en/download/document/SEVD-2019-134-11/"
            }
          ],
          "x_legacyV4Record": {
            "CVE_data_meta": {
              "ASSIGNER": "cybersecurity@schneider-electric.com",
              "ID": "CVE-2019-6829",
              "STATE": "PUBLIC"
            },
            "affects": {
              "vendor": {
                "vendor_data": [
                  {
                    "product": {
                      "product_data": [
                        {
                          "product_name": "Modicon M580",
                          "version": {
                            "version_data": [
                              {
                                "version_value": "firmware version prior to V2.90"
                              }
                            ]
                          }
                        },
                        {
                          "product_name": "Modicon M340",
                          "version": {
                            "version_data": [
                              {
                                "version_value": "firmware version prior to V3.10"
                              }
                            ]
                          }
                        }
                      ]
                    },
                    "vendor_name": "Schneider Electric SE"
                  }
                ]
              }
            },
            "data_format": "MITRE",
            "data_type": "CVE",
            "data_version": "4.0",
            "description": {
              "description_data": [
                {
                  "lang": "eng",
                  "value": "A CWE-248: Uncaught Exception vulnerability exists in Modicon M580 (firmware version prior to V2.90) and Modicon M340 (firmware version prior to V3.10), which could cause a possible denial of service when writing to specific memory addresses in the controller over Modbus."
                }
              ]
            },
            "problemtype": {
              "problemtype_data": [
                {
                  "description": [
                    {
                      "lang": "eng",
                      "value": "A CWE-248: Uncaught Exception"
                    }
                  ]
                }
              ]
            },
            "references": {
              "reference_data": [
                {
                  "name": "https://www.schneider-electric.com/en/download/document/SEVD-2019-134-11/",
                  "refsource": "CONFIRM",
                  "url": "https://www.schneider-electric.com/en/download/document/SEVD-2019-134-11/"
                }
              ]
            }
          }
        }
      },
      "cveMetadata": {
        "assignerOrgId": "076d1eb6-cfab-4401-b34d-6dfc2a413bdb",
        "assignerShortName": "schneider",
        "cveId": "CVE-2019-6829",
        "datePublished": "2019-09-17T19:44:12.000Z",
        "dateReserved": "2019-01-25T00:00:00.000Z",
        "dateUpdated": "2026-05-29T14:35:20.646Z",
        "state": "PUBLISHED"
      },
      "dataType": "CVE_RECORD",
      "dataVersion": "5.2"
    }
  }
}



Log in or create an account to share your comment.




Tags
Taxonomy of the tags.


Loading…

Loading…

Loading…

Forecast uses a logistic model when the trend is rising, or an exponential decay model when the trend is falling. Fitted via linearized least squares.

Sightings

Author Source Type Date Other

Nomenclature

  • Seen: The vulnerability was mentioned, discussed, or observed by the user.
  • Confirmed: The vulnerability has been validated from an analyst's perspective.
  • Published Proof of Concept: A public proof of concept is available for this vulnerability.
  • Exploited: The vulnerability was observed as exploited by the user who reported the sighting.
  • Patched: The vulnerability was observed as successfully patched by the user who reported the sighting.
  • Not exploited: The vulnerability was not observed as exploited by the user who reported the sighting.
  • Not confirmed: The user expressed doubt about the validity of the vulnerability.
  • Not patched: The vulnerability was not observed as successfully patched by the user who reported the sighting.

Loading…

Loading…

Loading…

Related by attack behaviour

Vulnerabilities whose description is nearest to this one in the vector space of the CIRCL/vulnerability-attack-technique-biencoder model. This is a similarity search over the bi-encoder space (plain cosine), not a classification, and it has no measured accuracy.


Loading…