CVE-2025-27253 (GCVE-0-2025-27253)

Vulnerability from cvelistv5 – Published: 2025-03-10 09:04 – Updated: 2025-10-07 14:16
VLAI
Summary
A CWE-15 "External Control of System or Configuration Setting" in GE Vernova UR IED family devices from version 7.0 up to 8.60 allows an attacker to provide input that establishes a TCP connection through a port forwarding. The lack of the IP address and port validation may allow the attacker to bypass firewall rules or to send malicious traffic in the network.
SSVC
Exploitation: none Automatable: no Technical Impact: partial
CISA Coordinator · CISA-ADP (v2.0.3)
Decision recorded 2025-03-10 15:33 UTC
CWE
  • CWE-15 - External Control of System or Configuration Setting
Impacted products
Vendor Product Version CPE status
GE Vernova N60 multilin Affected: 7.0 , ≤ 8.60 (custom)
guessed Create a notification for this product.
GE Vernova B30 Multilin Affected: 7.0 , ≤ 8.60 (custom)
guessed Create a notification for this product.
GE Vernova B90 Multilin Affected: 7.0 , ≤ 8.60 (custom)
guessed Create a notification for this product.
GE Vernova C30 Multilin Affected: 7.0 , ≤ 8.60 (custom)
guessed Create a notification for this product.
GE Vernova C60 Multilin Affected: 7.0 , ≤ 8.60 (custom)
guessed Create a notification for this product.
GE Vernova C70 Multilin Affected: 7.0 , ≤ 8.60 (custom)
guessed Create a notification for this product.
GE Vernova C95 Multilin Affected: 7.0 , ≤ 8.60 (custom)
guessed Create a notification for this product.
GE Vernova D30 Multilin Affected: 7.0 , ≤ 8.60 (custom)
guessed Create a notification for this product.
GE Vernova D60 Multilin Affected: 7.0 , ≤ 8.60 (custom)
guessed Create a notification for this product.
GE Vernova F35 Multilin Affected: 7.0 , ≤ 8.60 (custom)
guessed Create a notification for this product.
GE Vernova F60 Multilin Affected: 7.0 , ≤ 8.60 (custom)
guessed Create a notification for this product.
GE Vernova G30 Multilin Affected: 7.0 , ≤ 8.60 (custom)
guessed Create a notification for this product.
GE Vernova G60 Multilin Affected: 7.0 , ≤ 8.60 (custom)
guessed Create a notification for this product.
GE Vernova L30 Multilin Affected: 7.0 , ≤ 8.60 (custom)
guessed Create a notification for this product.
GE Vernova L60 Multilin Affected: 7.0 , ≤ 8.60 (custom)
guessed Create a notification for this product.
GE Vernova L90 Multilin Affected: 7.0 , ≤ 8.60 (custom)
guessed Create a notification for this product.
GE Vernova M60 Multilin Affected: 7.0 , ≤ 8.60 (custom)
guessed Create a notification for this product.
GE Vernova T35 Multilin Affected: 7.0 , ≤ 8.60 (custom)
guessed Create a notification for this product.
GE Vernova T60 Multilin Affected: 7.0 , ≤ 8.60 (custom)
guessed Create a notification for this product.
Show details on NVD website

{
  "containers": {
    "adp": [
      {
        "metrics": [
          {
            "other": {
              "content": {
                "id": "CVE-2025-27253",
                "options": [
                  {
                    "Exploitation": "none"
                  },
                  {
                    "Automatable": "no"
                  },
                  {
                    "Technical Impact": "partial"
                  }
                ],
                "role": "CISA Coordinator",
                "timestamp": "2025-03-10T15:33:39.489617Z",
                "version": "2.0.3"
              },
              "type": "ssvc"
            }
          }
        ],
        "providerMetadata": {
          "dateUpdated": "2025-03-10T15:33:49.185Z",
          "orgId": "134c704f-9b21-4f2e-91b3-4a467353bcc0",
          "shortName": "CISA-ADP"
        },
        "title": "CISA ADP Vulnrichment"
      }
    ],
    "cna": {
      "affected": [
        {
          "defaultStatus": "unaffected",
          "product": "N60 multilin",
          "vendor": "GE Vernova",
          "versions": [
            {
              "lessThanOrEqual": "8.60",
              "status": "affected",
              "version": "7.0",
              "versionType": "custom"
            }
          ]
        },
        {
          "defaultStatus": "unaffected",
          "product": "B30 Multilin",
          "vendor": "GE Vernova",
          "versions": [
            {
              "lessThanOrEqual": "8.60",
              "status": "affected",
              "version": "7.0",
              "versionType": "custom"
            }
          ]
        },
        {
          "defaultStatus": "unaffected",
          "product": "B90 Multilin",
          "vendor": "GE Vernova",
          "versions": [
            {
              "lessThanOrEqual": "8.60",
              "status": "affected",
              "version": "7.0",
              "versionType": "custom"
            }
          ]
        },
        {
          "defaultStatus": "unaffected",
          "product": "C30 Multilin",
          "vendor": "GE Vernova",
          "versions": [
            {
              "lessThanOrEqual": "8.60",
              "status": "affected",
              "version": "7.0",
              "versionType": "custom"
            }
          ]
        },
        {
          "defaultStatus": "unaffected",
          "product": "C60 Multilin",
          "vendor": "GE Vernova",
          "versions": [
            {
              "lessThanOrEqual": "8.60",
              "status": "affected",
              "version": "7.0",
              "versionType": "custom"
            }
          ]
        },
        {
          "defaultStatus": "unaffected",
          "product": "C70 Multilin",
          "vendor": "GE Vernova",
          "versions": [
            {
              "lessThanOrEqual": "8.60",
              "status": "affected",
              "version": "7.0",
              "versionType": "custom"
            }
          ]
        },
        {
          "defaultStatus": "unaffected",
          "product": "C95 Multilin",
          "vendor": "GE Vernova",
          "versions": [
            {
              "lessThanOrEqual": "8.60",
              "status": "affected",
              "version": "7.0",
              "versionType": "custom"
            }
          ]
        },
        {
          "defaultStatus": "unaffected",
          "product": "D30 Multilin",
          "vendor": "GE Vernova",
          "versions": [
            {
              "lessThanOrEqual": "8.60",
              "status": "affected",
              "version": "7.0",
              "versionType": "custom"
            }
          ]
        },
        {
          "defaultStatus": "unaffected",
          "product": "D60 Multilin",
          "vendor": "GE Vernova",
          "versions": [
            {
              "lessThanOrEqual": "8.60",
              "status": "affected",
              "version": "7.0",
              "versionType": "custom"
            }
          ]
        },
        {
          "defaultStatus": "unaffected",
          "product": "F35 Multilin",
          "vendor": "GE Vernova",
          "versions": [
            {
              "lessThanOrEqual": "8.60",
              "status": "affected",
              "version": "7.0",
              "versionType": "custom"
            }
          ]
        },
        {
          "defaultStatus": "unaffected",
          "product": "F60 Multilin",
          "vendor": "GE Vernova",
          "versions": [
            {
              "lessThanOrEqual": "8.60",
              "status": "affected",
              "version": "7.0",
              "versionType": "custom"
            }
          ]
        },
        {
          "defaultStatus": "unaffected",
          "product": "G30 Multilin",
          "vendor": "GE Vernova",
          "versions": [
            {
              "lessThanOrEqual": "8.60",
              "status": "affected",
              "version": "7.0",
              "versionType": "custom"
            }
          ]
        },
        {
          "defaultStatus": "unaffected",
          "product": "G60 Multilin",
          "vendor": "GE Vernova",
          "versions": [
            {
              "lessThanOrEqual": "8.60",
              "status": "affected",
              "version": "7.0",
              "versionType": "custom"
            }
          ]
        },
        {
          "defaultStatus": "unaffected",
          "product": "L30 Multilin",
          "vendor": "GE Vernova",
          "versions": [
            {
              "lessThanOrEqual": "8.60",
              "status": "affected",
              "version": "7.0",
              "versionType": "custom"
            }
          ]
        },
        {
          "defaultStatus": "unaffected",
          "product": "L60 Multilin",
          "vendor": "GE Vernova",
          "versions": [
            {
              "lessThanOrEqual": "8.60",
              "status": "affected",
              "version": "7.0",
              "versionType": "custom"
            }
          ]
        },
        {
          "defaultStatus": "unaffected",
          "product": "L90 Multilin",
          "vendor": "GE Vernova",
          "versions": [
            {
              "lessThanOrEqual": "8.60",
              "status": "affected",
              "version": "7.0",
              "versionType": "custom"
            }
          ]
        },
        {
          "defaultStatus": "unaffected",
          "product": "M60 Multilin",
          "vendor": "GE Vernova",
          "versions": [
            {
              "lessThanOrEqual": "8.60",
              "status": "affected",
              "version": "7.0",
              "versionType": "custom"
            }
          ]
        },
        {
          "defaultStatus": "unaffected",
          "product": "T35 Multilin",
          "vendor": "GE Vernova",
          "versions": [
            {
              "lessThanOrEqual": "8.60",
              "status": "affected",
              "version": "7.0",
              "versionType": "custom"
            }
          ]
        },
        {
          "defaultStatus": "unaffected",
          "product": "T60 Multilin",
          "vendor": "GE Vernova",
          "versions": [
            {
              "lessThanOrEqual": "8.60",
              "status": "affected",
              "version": "7.0",
              "versionType": "custom"
            }
          ]
        },
        {
          "defaultStatus": "unaffected",
          "product": "M60 Multilin",
          "vendor": "GE Vernova",
          "versions": [
            {
              "lessThanOrEqual": "8.60",
              "status": "affected",
              "version": "7.0",
              "versionType": "custom"
            }
          ]
        }
      ],
      "descriptions": [
        {
          "lang": "en",
          "supportingMedia": [
            {
              "base64": false,
              "type": "text/html",
              "value": "A\u0026nbsp;CWE-15 \"External Control of System or Configuration Setting\"\u0026nbsp;in GE Vernova UR IED family devices from version 7.0 up to 8.60 allows an attacker to provide input that establishes a TCP connection through a port forwarding. The lack of the IP address and port validation may allow the attacker to bypass firewall rules or to send malicious traffic in the network."
            }
          ],
          "value": "A\u00a0CWE-15 \"External Control of System or Configuration Setting\"\u00a0in GE Vernova UR IED family devices from version 7.0 up to 8.60 allows an attacker to provide input that establishes a TCP connection through a port forwarding. The lack of the IP address and port validation may allow the attacker to bypass firewall rules or to send malicious traffic in the network."
        }
      ],
      "impacts": [
        {
          "capecId": "CAPEC-1",
          "descriptions": [
            {
              "lang": "en",
              "value": "CAPEC-1 Accessing Functionality Not Properly Constrained by ACLs"
            }
          ]
        }
      ],
      "metrics": [
        {
          "cvssV3_1": {
            "attackComplexity": "LOW",
            "attackVector": "ADJACENT_NETWORK",
            "availabilityImpact": "LOW",
            "baseScore": 6.1,
            "baseSeverity": "MEDIUM",
            "confidentialityImpact": "LOW",
            "integrityImpact": "NONE",
            "privilegesRequired": "NONE",
            "scope": "CHANGED",
            "userInteraction": "NONE",
            "vectorString": "CVSS:3.1/AV:A/AC:L/PR:N/UI:N/S:C/C:L/I:N/A:L",
            "version": "3.1"
          },
          "format": "CVSS",
          "scenarios": [
            {
              "lang": "en",
              "value": "GENERAL"
            }
          ]
        }
      ],
      "problemTypes": [
        {
          "descriptions": [
            {
              "cweId": "CWE-15",
              "description": "CWE-15 External Control of System or Configuration Setting",
              "lang": "en",
              "type": "CWE"
            }
          ]
        }
      ],
      "providerMetadata": {
        "dateUpdated": "2025-10-07T14:16:49.710Z",
        "orgId": "bec8025f-a851-46e5-b3a3-058e6b0aa23c",
        "shortName": "Nozomi"
      },
      "references": [
        {
          "url": "https://www.gevernova.com/grid-solutions/app/DownloadFile.aspx?prod=urfamily\u0026type=21\u0026file=76"
        },
        {
          "url": "https://www.nozominetworks.com/labs/vulnerability-advisories-cve-2025-27253"
        }
      ],
      "source": {
        "discovery": "UNKNOWN"
      },
      "x_generator": {
        "engine": "Vulnogram 0.2.0"
      }
    }
  },
  "cveMetadata": {
    "assignerOrgId": "bec8025f-a851-46e5-b3a3-058e6b0aa23c",
    "assignerShortName": "Nozomi",
    "cveId": "CVE-2025-27253",
    "datePublished": "2025-03-10T09:04:34.413Z",
    "dateReserved": "2025-02-21T08:32:26.973Z",
    "dateUpdated": "2025-10-07T14:16:49.710Z",
    "state": "PUBLISHED"
  },
  "dataType": "CVE_RECORD",
  "dataVersion": "5.1",
  "vulnerability-lookup:meta": {
    "epss": {
      "cve": "CVE-2025-27253",
      "date": "2026-09-26",
      "epss": "0.00229",
      "percentile": "0.12342"
    },
    "nvd": {
      "cve": {
        "affected": [
          {
            "affectedData": [
              {
                "defaultStatus": "unaffected",
                "product": "N60 multilin",
                "vendor": "GE Vernova",
                "versions": [
                  {
                    "lessThanOrEqual": "8.60",
                    "status": "affected",
                    "version": "7.0",
                    "versionType": "custom"
                  }
                ]
              },
              {
                "defaultStatus": "unaffected",
                "product": "B30 Multilin",
                "vendor": "GE Vernova",
                "versions": [
                  {
                    "lessThanOrEqual": "8.60",
                    "status": "affected",
                    "version": "7.0",
                    "versionType": "custom"
                  }
                ]
              },
              {
                "defaultStatus": "unaffected",
                "product": "B90 Multilin",
                "vendor": "GE Vernova",
                "versions": [
                  {
                    "lessThanOrEqual": "8.60",
                    "status": "affected",
                    "version": "7.0",
                    "versionType": "custom"
                  }
                ]
              },
              {
                "defaultStatus": "unaffected",
                "product": "C30 Multilin",
                "vendor": "GE Vernova",
                "versions": [
                  {
                    "lessThanOrEqual": "8.60",
                    "status": "affected",
                    "version": "7.0",
                    "versionType": "custom"
                  }
                ]
              },
              {
                "defaultStatus": "unaffected",
                "product": "C60 Multilin",
                "vendor": "GE Vernova",
                "versions": [
                  {
                    "lessThanOrEqual": "8.60",
                    "status": "affected",
                    "version": "7.0",
                    "versionType": "custom"
                  }
                ]
              },
              {
                "defaultStatus": "unaffected",
                "product": "C70 Multilin",
                "vendor": "GE Vernova",
                "versions": [
                  {
                    "lessThanOrEqual": "8.60",
                    "status": "affected",
                    "version": "7.0",
                    "versionType": "custom"
                  }
                ]
              },
              {
                "defaultStatus": "unaffected",
                "product": "C95 Multilin",
                "vendor": "GE Vernova",
                "versions": [
                  {
                    "lessThanOrEqual": "8.60",
                    "status": "affected",
                    "version": "7.0",
                    "versionType": "custom"
                  }
                ]
              },
              {
                "defaultStatus": "unaffected",
                "product": "D30 Multilin",
                "vendor": "GE Vernova",
                "versions": [
                  {
                    "lessThanOrEqual": "8.60",
                    "status": "affected",
                    "version": "7.0",
                    "versionType": "custom"
                  }
                ]
              },
              {
                "defaultStatus": "unaffected",
                "product": "D60 Multilin",
                "vendor": "GE Vernova",
                "versions": [
                  {
                    "lessThanOrEqual": "8.60",
                    "status": "affected",
                    "version": "7.0",
                    "versionType": "custom"
                  }
                ]
              },
              {
                "defaultStatus": "unaffected",
                "product": "F35 Multilin",
                "vendor": "GE Vernova",
                "versions": [
                  {
                    "lessThanOrEqual": "8.60",
                    "status": "affected",
                    "version": "7.0",
                    "versionType": "custom"
                  }
                ]
              },
              {
                "defaultStatus": "unaffected",
                "product": "F60 Multilin",
                "vendor": "GE Vernova",
                "versions": [
                  {
                    "lessThanOrEqual": "8.60",
                    "status": "affected",
                    "version": "7.0",
                    "versionType": "custom"
                  }
                ]
              },
              {
                "defaultStatus": "unaffected",
                "product": "G30 Multilin",
                "vendor": "GE Vernova",
                "versions": [
                  {
                    "lessThanOrEqual": "8.60",
                    "status": "affected",
                    "version": "7.0",
                    "versionType": "custom"
                  }
                ]
              },
              {
                "defaultStatus": "unaffected",
                "product": "G60 Multilin",
                "vendor": "GE Vernova",
                "versions": [
                  {
                    "lessThanOrEqual": "8.60",
                    "status": "affected",
                    "version": "7.0",
                    "versionType": "custom"
                  }
                ]
              },
              {
                "defaultStatus": "unaffected",
                "product": "L30 Multilin",
                "vendor": "GE Vernova",
                "versions": [
                  {
                    "lessThanOrEqual": "8.60",
                    "status": "affected",
                    "version": "7.0",
                    "versionType": "custom"
                  }
                ]
              },
              {
                "defaultStatus": "unaffected",
                "product": "L60 Multilin",
                "vendor": "GE Vernova",
                "versions": [
                  {
                    "lessThanOrEqual": "8.60",
                    "status": "affected",
                    "version": "7.0",
                    "versionType": "custom"
                  }
                ]
              },
              {
                "defaultStatus": "unaffected",
                "product": "L90 Multilin",
                "vendor": "GE Vernova",
                "versions": [
                  {
                    "lessThanOrEqual": "8.60",
                    "status": "affected",
                    "version": "7.0",
                    "versionType": "custom"
                  }
                ]
              },
              {
                "defaultStatus": "unaffected",
                "product": "M60 Multilin",
                "vendor": "GE Vernova",
                "versions": [
                  {
                    "lessThanOrEqual": "8.60",
                    "status": "affected",
                    "version": "7.0",
                    "versionType": "custom"
                  }
                ]
              },
              {
                "defaultStatus": "unaffected",
                "product": "T35 Multilin",
                "vendor": "GE Vernova",
                "versions": [
                  {
                    "lessThanOrEqual": "8.60",
                    "status": "affected",
                    "version": "7.0",
                    "versionType": "custom"
                  }
                ]
              },
              {
                "defaultStatus": "unaffected",
                "product": "T60 Multilin",
                "vendor": "GE Vernova",
                "versions": [
                  {
                    "lessThanOrEqual": "8.60",
                    "status": "affected",
                    "version": "7.0",
                    "versionType": "custom"
                  }
                ]
              },
              {
                "defaultStatus": "unaffected",
                "product": "M60 Multilin",
                "vendor": "GE Vernova",
                "versions": [
                  {
                    "lessThanOrEqual": "8.60",
                    "status": "affected",
                    "version": "7.0",
                    "versionType": "custom"
                  }
                ]
              }
            ],
            "source": "prodsec@nozominetworks.com"
          }
        ],
        "cveTags": [],
        "descriptions": [
          {
            "lang": "en",
            "value": "A\u00a0CWE-15 \"External Control of System or Configuration Setting\"\u00a0in GE Vernova UR IED family devices from version 7.0 up to 8.60 allows an attacker to provide input that establishes a TCP connection through a port forwarding. The lack of the IP address and port validation may allow the attacker to bypass firewall rules or to send malicious traffic in the network."
          },
          {
            "lang": "es",
            "value": "Una validaci\u00f3n de entrada incorrecta en los dispositivos de la familia GE Vernova UR IED de la versi\u00f3n 7.0 a la 8.60 permite a un atacante proporcionar una entrada que establezca una conexi\u00f3n TCP a trav\u00e9s de un reenv\u00edo de puerto. La falta de validaci\u00f3n de la direcci\u00f3n IP y del puerto puede permitir al atacante eludir las reglas del firewall o enviar tr\u00e1fico malicioso en la red."
          }
        ],
        "id": "CVE-2025-27253",
        "lastModified": "2026-06-17T09:03:16.997",
        "metrics": {
          "cvssMetricV31": [
            {
              "cvssData": {
                "attackComplexity": "LOW",
                "attackVector": "ADJACENT_NETWORK",
                "availabilityImpact": "LOW",
                "baseScore": 6.1,
                "baseSeverity": "MEDIUM",
                "confidentialityImpact": "LOW",
                "integrityImpact": "NONE",
                "privilegesRequired": "NONE",
                "scope": "CHANGED",
                "userInteraction": "NONE",
                "vectorString": "CVSS:3.1/AV:A/AC:L/PR:N/UI:N/S:C/C:L/I:N/A:L",
                "version": "3.1"
              },
              "exploitabilityScore": 2.8,
              "impactScore": 2.7,
              "source": "prodsec@nozominetworks.com",
              "type": "Secondary"
            }
          ],
          "ssvcV203": [
            {
              "source": "134c704f-9b21-4f2e-91b3-4a467353bcc0",
              "ssvcData": {
                "id": "CVE-2025-27253",
                "options": [
                  {
                    "exploitation": "none"
                  },
                  {
                    "automatable": "no"
                  },
                  {
                    "technicalImpact": "partial"
                  }
                ],
                "role": "CISA Coordinator",
                "timestamp": "2025-03-10T15:33:39.489617Z",
                "version": "2.0.3"
              }
            }
          ]
        },
        "published": "2025-03-10T09:15:10.897",
        "references": [
          {
            "source": "prodsec@nozominetworks.com",
            "url": "https://www.gevernova.com/grid-solutions/app/DownloadFile.aspx?prod=urfamily\u0026type=21\u0026file=76"
          },
          {
            "source": "prodsec@nozominetworks.com",
            "url": "https://www.nozominetworks.com/labs/vulnerability-advisories-cve-2025-27253"
          }
        ],
        "sourceIdentifier": "prodsec@nozominetworks.com",
        "vulnStatus": "Deferred",
        "weaknesses": [
          {
            "description": [
              {
                "lang": "en",
                "value": "CWE-15"
              }
            ],
            "source": "prodsec@nozominetworks.com",
            "type": "Secondary"
          }
        ]
      }
    },
    "redhat_vex": {
      "current_release_date": "2025-10-07T15:22:53+00:00",
      "cve": "CVE-2025-27253",
      "id": "CVE-2025-27253",
      "initial_release_date": "2025-01-01T00:00:00+00:00",
      "product_status:known_not_affected": "1",
      "source": "Red Hat CSAF VEX",
      "status": "final",
      "title": "CVE-2025-27253",
      "url": "https://security.access.redhat.com/data/csaf/v2/vex/2025/cve-2025-27253.json",
      "version": "3"
    },
    "vulnrichment": {
      "containers": {
        "adp": [
          {
            "metrics": [
              {
                "other": {
                  "content": {
                    "id": "CVE-2025-27253",
                    "options": [
                      {
                        "Exploitation": "none"
                      },
                      {
                        "Automatable": "no"
                      },
                      {
                        "Technical Impact": "partial"
                      }
                    ],
                    "role": "CISA Coordinator",
                    "timestamp": "2025-03-10T15:33:39.489617Z",
                    "version": "2.0.3"
                  },
                  "type": "ssvc"
                }
              }
            ],
            "providerMetadata": {
              "dateUpdated": "2025-03-10T15:33:45.461Z",
              "orgId": "134c704f-9b21-4f2e-91b3-4a467353bcc0",
              "shortName": "CISA-ADP"
            },
            "title": "CISA ADP Vulnrichment"
          }
        ],
        "cna": {
          "affected": [
            {
              "defaultStatus": "unaffected",
              "product": "N60 multilin",
              "vendor": "GE Vernova",
              "versions": [
                {
                  "lessThanOrEqual": "8.60",
                  "status": "affected",
                  "version": "7.0",
                  "versionType": "custom"
                }
              ]
            },
            {
              "defaultStatus": "unaffected",
              "product": "B30 Multilin",
              "vendor": "GE Vernova",
              "versions": [
                {
                  "lessThanOrEqual": "8.60",
                  "status": "affected",
                  "version": "7.0",
                  "versionType": "custom"
                }
              ]
            },
            {
              "defaultStatus": "unaffected",
              "product": "B90 Multilin",
              "vendor": "GE Vernova",
              "versions": [
                {
                  "lessThanOrEqual": "8.60",
                  "status": "affected",
                  "version": "7.0",
                  "versionType": "custom"
                }
              ]
            },
            {
              "defaultStatus": "unaffected",
              "product": "C30 Multilin",
              "vendor": "GE Vernova",
              "versions": [
                {
                  "lessThanOrEqual": "8.60",
                  "status": "affected",
                  "version": "7.0",
                  "versionType": "custom"
                }
              ]
            },
            {
              "defaultStatus": "unaffected",
              "product": "C60 Multilin",
              "vendor": "GE Vernova",
              "versions": [
                {
                  "lessThanOrEqual": "8.60",
                  "status": "affected",
                  "version": "7.0",
                  "versionType": "custom"
                }
              ]
            },
            {
              "defaultStatus": "unaffected",
              "product": "C70 Multilin",
              "vendor": "GE Vernova",
              "versions": [
                {
                  "lessThanOrEqual": "8.60",
                  "status": "affected",
                  "version": "7.0",
                  "versionType": "custom"
                }
              ]
            },
            {
              "defaultStatus": "unaffected",
              "product": "C95 Multilin",
              "vendor": "GE Vernova",
              "versions": [
                {
                  "lessThanOrEqual": "8.60",
                  "status": "affected",
                  "version": "7.0",
                  "versionType": "custom"
                }
              ]
            },
            {
              "defaultStatus": "unaffected",
              "product": "D30 Multilin",
              "vendor": "GE Vernova",
              "versions": [
                {
                  "lessThanOrEqual": "8.60",
                  "status": "affected",
                  "version": "7.0",
                  "versionType": "custom"
                }
              ]
            },
            {
              "defaultStatus": "unaffected",
              "product": "D60 Multilin",
              "vendor": "GE Vernova",
              "versions": [
                {
                  "lessThanOrEqual": "8.60",
                  "status": "affected",
                  "version": "7.0",
                  "versionType": "custom"
                }
              ]
            },
            {
              "defaultStatus": "unaffected",
              "product": "F35 Multilin",
              "vendor": "GE Vernova",
              "versions": [
                {
                  "lessThanOrEqual": "8.60",
                  "status": "affected",
                  "version": "7.0",
                  "versionType": "custom"
                }
              ]
            },
            {
              "defaultStatus": "unaffected",
              "product": "F60 Multilin",
              "vendor": "GE Vernova",
              "versions": [
                {
                  "lessThanOrEqual": "8.60",
                  "status": "affected",
                  "version": "7.0",
                  "versionType": "custom"
                }
              ]
            },
            {
              "defaultStatus": "unaffected",
              "product": "G30 Multilin",
              "vendor": "GE Vernova",
              "versions": [
                {
                  "lessThanOrEqual": "8.60",
                  "status": "affected",
                  "version": "7.0",
                  "versionType": "custom"
                }
              ]
            },
            {
              "defaultStatus": "unaffected",
              "product": "G60 Multilin",
              "vendor": "GE Vernova",
              "versions": [
                {
                  "lessThanOrEqual": "8.60",
                  "status": "affected",
                  "version": "7.0",
                  "versionType": "custom"
                }
              ]
            },
            {
              "defaultStatus": "unaffected",
              "product": "L30 Multilin",
              "vendor": "GE Vernova",
              "versions": [
                {
                  "lessThanOrEqual": "8.60",
                  "status": "affected",
                  "version": "7.0",
                  "versionType": "custom"
                }
              ]
            },
            {
              "defaultStatus": "unaffected",
              "product": "L60 Multilin",
              "vendor": "GE Vernova",
              "versions": [
                {
                  "lessThanOrEqual": "8.60",
                  "status": "affected",
                  "version": "7.0",
                  "versionType": "custom"
                }
              ]
            },
            {
              "defaultStatus": "unaffected",
              "product": "L90 Multilin",
              "vendor": "GE Vernova",
              "versions": [
                {
                  "lessThanOrEqual": "8.60",
                  "status": "affected",
                  "version": "7.0",
                  "versionType": "custom"
                }
              ]
            },
            {
              "defaultStatus": "unaffected",
              "product": "M60 Multilin",
              "vendor": "GE Vernova",
              "versions": [
                {
                  "lessThanOrEqual": "8.60",
                  "status": "affected",
                  "version": "7.0",
                  "versionType": "custom"
                }
              ]
            },
            {
              "defaultStatus": "unaffected",
              "product": "T35 Multilin",
              "vendor": "GE Vernova",
              "versions": [
                {
                  "lessThanOrEqual": "8.60",
                  "status": "affected",
                  "version": "7.0",
                  "versionType": "custom"
                }
              ]
            },
            {
              "defaultStatus": "unaffected",
              "product": "T60 Multilin",
              "vendor": "GE Vernova",
              "versions": [
                {
                  "lessThanOrEqual": "8.60",
                  "status": "affected",
                  "version": "7.0",
                  "versionType": "custom"
                }
              ]
            },
            {
              "defaultStatus": "unaffected",
              "product": "M60 Multilin",
              "vendor": "GE Vernova",
              "versions": [
                {
                  "lessThanOrEqual": "8.60",
                  "status": "affected",
                  "version": "7.0",
                  "versionType": "custom"
                }
              ]
            }
          ],
          "descriptions": [
            {
              "lang": "en",
              "supportingMedia": [
                {
                  "base64": false,
                  "type": "text/html",
                  "value": "A\u0026nbsp;CWE-15 \"External Control of System or Configuration Setting\"\u0026nbsp;in GE Vernova UR IED family devices from version 7.0 up to 8.60 allows an attacker to provide input that establishes a TCP connection through a port forwarding. The lack of the IP address and port validation may allow the attacker to bypass firewall rules or to send malicious traffic in the network."
                }
              ],
              "value": "A\u00a0CWE-15 \"External Control of System or Configuration Setting\"\u00a0in GE Vernova UR IED family devices from version 7.0 up to 8.60 allows an attacker to provide input that establishes a TCP connection through a port forwarding. The lack of the IP address and port validation may allow the attacker to bypass firewall rules or to send malicious traffic in the network."
            }
          ],
          "impacts": [
            {
              "capecId": "CAPEC-1",
              "descriptions": [
                {
                  "lang": "en",
                  "value": "CAPEC-1 Accessing Functionality Not Properly Constrained by ACLs"
                }
              ]
            }
          ],
          "metrics": [
            {
              "cvssV3_1": {
                "attackComplexity": "LOW",
                "attackVector": "ADJACENT_NETWORK",
                "availabilityImpact": "LOW",
                "baseScore": 6.1,
                "baseSeverity": "MEDIUM",
                "confidentialityImpact": "LOW",
                "integrityImpact": "NONE",
                "privilegesRequired": "NONE",
                "scope": "CHANGED",
                "userInteraction": "NONE",
                "vectorString": "CVSS:3.1/AV:A/AC:L/PR:N/UI:N/S:C/C:L/I:N/A:L",
                "version": "3.1"
              },
              "format": "CVSS",
              "scenarios": [
                {
                  "lang": "en",
                  "value": "GENERAL"
                }
              ]
            }
          ],
          "problemTypes": [
            {
              "descriptions": [
                {
                  "cweId": "CWE-15",
                  "description": "CWE-15 External Control of System or Configuration Setting",
                  "lang": "en",
                  "type": "CWE"
                }
              ]
            }
          ],
          "providerMetadata": {
            "dateUpdated": "2025-10-07T14:16:49.710Z",
            "orgId": "bec8025f-a851-46e5-b3a3-058e6b0aa23c",
            "shortName": "Nozomi"
          },
          "references": [
            {
              "url": "https://www.gevernova.com/grid-solutions/app/DownloadFile.aspx?prod=urfamily\u0026type=21\u0026file=76"
            },
            {
              "url": "https://www.nozominetworks.com/labs/vulnerability-advisories-cve-2025-27253"
            }
          ],
          "source": {
            "discovery": "UNKNOWN"
          },
          "x_generator": {
            "engine": "Vulnogram 0.2.0"
          }
        }
      },
      "cveMetadata": {
        "assignerOrgId": "bec8025f-a851-46e5-b3a3-058e6b0aa23c",
        "assignerShortName": "Nozomi",
        "cveId": "CVE-2025-27253",
        "datePublished": "2025-03-10T09:04:34.413Z",
        "dateReserved": "2025-02-21T08:32:26.973Z",
        "dateUpdated": "2025-10-07T14:16:49.710Z",
        "state": "PUBLISHED"
      },
      "dataType": "CVE_RECORD",
      "dataVersion": "5.1"
    }
  }
}



Log in or create an account to share your comment.




Tags
Taxonomy of the tags.


Loading…

Loading…

Loading…

Forecast uses a logistic model when the trend is rising, or an exponential decay model when the trend is falling. Fitted via linearized least squares.

Sightings

Author Source Type Date Other

Nomenclature

  • Seen: The vulnerability was mentioned, discussed, or observed by the user.
  • Confirmed: The vulnerability has been validated from an analyst's perspective.
  • Published Proof of Concept: A public proof of concept is available for this vulnerability.
  • Exploited: The vulnerability was observed as exploited by the user who reported the sighting.
  • Patched: The vulnerability was observed as successfully patched by the user who reported the sighting.
  • Not exploited: The vulnerability was not observed as exploited by the user who reported the sighting.
  • Not confirmed: The user expressed doubt about the validity of the vulnerability.
  • Not patched: The vulnerability was not observed as successfully patched by the user who reported the sighting.

Loading…

Loading…

Loading…

Related by attack behaviour

Vulnerabilities whose description is nearest to this one in the vector space of the CIRCL/vulnerability-attack-technique-biencoder model. This is a similarity search over the bi-encoder space (plain cosine), not a classification, and it has no measured accuracy.


Loading…