CVE-2024-37368 (GCVE-0-2024-37368)

Vulnerability from cvelistv5 – Published: 2024-06-14 14:30 – Updated: 2024-08-02 03:50
VLAI?
Summary
A user authentication vulnerability exists in the Rockwell Automation FactoryTalk® View SE. The vulnerability allows a user from a remote system with FTView to send a packet to the customer’s server to view an HMI project. Due to the lack of proper authentication, this action is allowed without proper authentication verification.
CWE
  • CWE-287 - Improper Authentication
Assigner
Impacted products
Show details on NVD website

{
  "containers": {
    "adp": [
      {
        "affected": [
          {
            "cpes": [
              "cpe:2.3:a:rockwellautomation:factorytalk_view:-:*:*:*:se:*:*:*"
            ],
            "defaultStatus": "unaffected",
            "product": "factorytalk_view",
            "vendor": "rockwellautomation",
            "versions": [
              {
                "lessThan": "v14.0",
                "status": "affected",
                "version": "v11.0",
                "versionType": "custom"
              }
            ]
          }
        ],
        "metrics": [
          {
            "other": {
              "content": {
                "id": "CVE-2024-37368",
                "options": [
                  {
                    "Exploitation": "none"
                  },
                  {
                    "Automatable": "yes"
                  },
                  {
                    "Technical Impact": "partial"
                  }
                ],
                "role": "CISA Coordinator",
                "timestamp": "2024-06-18T16:26:32.782829Z",
                "version": "2.0.3"
              },
              "type": "ssvc"
            }
          }
        ],
        "providerMetadata": {
          "dateUpdated": "2024-06-18T16:33:16.826Z",
          "orgId": "134c704f-9b21-4f2e-91b3-4a467353bcc0",
          "shortName": "CISA-ADP"
        },
        "title": "CISA ADP Vulnrichment"
      },
      {
        "providerMetadata": {
          "dateUpdated": "2024-08-02T03:50:56.219Z",
          "orgId": "af854a3a-2127-422b-91ae-364da2661108",
          "shortName": "CVE"
        },
        "references": [
          {
            "tags": [
              "x_transferred"
            ],
            "url": "https://https://www.rockwellautomation.com/en-us/trust-center/security-advisories/advisory.SD1676.html"
          }
        ],
        "title": "CVE Program Container"
      }
    ],
    "cna": {
      "affected": [
        {
          "defaultStatus": "unaffected",
          "product": "FactoryTalk\u00ae View SE",
          "vendor": "Rockwell Automation",
          "versions": [
            {
              "status": "affected",
              "version": "v11.0"
            }
          ]
        }
      ],
      "datePublic": "2024-06-13T13:00:00.000Z",
      "descriptions": [
        {
          "lang": "en",
          "supportingMedia": [
            {
              "base64": false,
              "type": "text/html",
              "value": "\n\n\u003cspan style=\"background-color: rgb(255, 255, 255);\"\u003eA user authentication vulnerability exists in the Rockwell Automation\u0026nbsp;FactoryTalk\u00ae View SE. The vulnerability allows a user from a remote system with FTView to send a packet to the customer\u2019s server to view an HMI project. Due to the lack of proper authentication, this action is allowed without proper authentication verification.\u003c/span\u003e\n\n"
            }
          ],
          "value": "A user authentication vulnerability exists in the Rockwell Automation\u00a0FactoryTalk\u00ae View SE. The vulnerability allows a user from a remote system with FTView to send a packet to the customer\u2019s server to view an HMI project. Due to the lack of proper authentication, this action is allowed without proper authentication verification."
        }
      ],
      "impacts": [
        {
          "capecId": "CAPEC-114",
          "descriptions": [
            {
              "lang": "en",
              "value": "CAPEC-114 Authentication Abuse"
            }
          ]
        }
      ],
      "metrics": [
        {
          "cvssV4_0": {
            "Automatable": "NOT_DEFINED",
            "Recovery": "NOT_DEFINED",
            "Safety": "NOT_DEFINED",
            "attackComplexity": "LOW",
            "attackRequirements": "PRESENT",
            "attackVector": "NETWORK",
            "baseScore": 8.2,
            "baseSeverity": "HIGH",
            "privilegesRequired": "NONE",
            "providerUrgency": "NOT_DEFINED",
            "subAvailabilityImpact": "NONE",
            "subConfidentialityImpact": "NONE",
            "subIntegrityImpact": "NONE",
            "userInteraction": "NONE",
            "valueDensity": "NOT_DEFINED",
            "vectorString": "CVSS:4.0/AV:N/AC:L/AT:P/PR:N/UI:N/VC:H/VI:N/VA:N/SC:N/SI:N/SA:N",
            "version": "4.0",
            "vulnAvailabilityImpact": "NONE",
            "vulnConfidentialityImpact": "HIGH",
            "vulnIntegrityImpact": "NONE",
            "vulnerabilityResponseEffort": "NOT_DEFINED"
          },
          "format": "CVSS",
          "scenarios": [
            {
              "lang": "en",
              "value": "GENERAL"
            }
          ]
        }
      ],
      "problemTypes": [
        {
          "descriptions": [
            {
              "cweId": "CWE-287",
              "description": "CWE-287 Improper Authentication",
              "lang": "en",
              "type": "CWE"
            }
          ]
        }
      ],
      "providerMetadata": {
        "dateUpdated": "2024-06-14T14:30:53.422Z",
        "orgId": "b73dd486-f505-4403-b634-40b078b177f0",
        "shortName": "Rockwell"
      },
      "references": [
        {
          "url": "https://https://www.rockwellautomation.com/en-us/trust-center/security-advisories/advisory.SD1676.html"
        }
      ],
      "solutions": [
        {
          "lang": "en",
          "supportingMedia": [
            {
              "base64": false,
              "type": "text/html",
              "value": "\u003cul\u003e\u003cli\u003eCorrected in software version v14.0.\u003c/li\u003e\u003cli\u003e\n\n\u003cp\u003eUsers using the affected software, who are not able to upgrade to one of the corrected versions, are encouraged to apply security best practices, where possible.\u202f\u202f\u202f\u003c/p\u003e\u003cul\u003e\u003cli\u003e\u003cp\u003eIt is recommended that users enforce proper access controls within the network and segment networks containing sensitive information using IPSec: \u003ca target=\"_blank\" rel=\"nofollow\" href=\"https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/1090456\"\u003ehttps://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/1090456\u003c/a\u003e\u003c/p\u003e\u003c/li\u003e\u003c/ul\u003e\u003cul\u003e\u003cli\u003e\u003cp\u003e\u003ca target=\"_blank\" rel=\"nofollow\" href=\"https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/1085012/loc/en_US#__highlight\"\u003eSecurity Best Practice\u003c/a\u003es\u003c/p\u003e\u003c/li\u003e\u003c/ul\u003e\u003c/li\u003e\u003c/ul\u003e"
            }
          ],
          "value": "*  Corrected in software version v14.0.\n  *  \n\nUsers using the affected software, who are not able to upgrade to one of the corrected versions, are encouraged to apply security best practices, where possible.\u202f\u202f\u202f\n\n  *  It is recommended that users enforce proper access controls within the network and segment networks containing sensitive information using IPSec:  https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/1090456 \n\n\n\n\n  *   Security Best Practice https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/1085012/loc/en_US#__highlight s"
        }
      ],
      "source": {
        "discovery": "INTERNAL"
      },
      "title": "Rockwell Automation FactoryTalk\u00ae View SE v11 Information Leakage Vulnerability via Authentication Restriction",
      "x_generator": {
        "engine": "Vulnogram 0.2.0"
      }
    }
  },
  "cveMetadata": {
    "assignerOrgId": "b73dd486-f505-4403-b634-40b078b177f0",
    "assignerShortName": "Rockwell",
    "cveId": "CVE-2024-37368",
    "datePublished": "2024-06-14T14:30:53.422Z",
    "dateReserved": "2024-06-06T20:18:27.551Z",
    "dateUpdated": "2024-08-02T03:50:56.219Z",
    "state": "PUBLISHED"
  },
  "dataType": "CVE_RECORD",
  "dataVersion": "5.1",
  "vulnerability-lookup:meta": {
    "fkie_nvd": {
      "descriptions": "[{\"lang\": \"en\", \"value\": \"A user authentication vulnerability exists in the Rockwell Automation\\u00a0FactoryTalk\\u00ae View SE. The vulnerability allows a user from a remote system with FTView to send a packet to the customer\\u2019s server to view an HMI project. Due to the lack of proper authentication, this action is allowed without proper authentication verification.\"}, {\"lang\": \"es\", \"value\": \"Existe una vulnerabilidad de autenticaci\\u00f3n de usuario en Rockwell Automation FactoryTalk\\u00ae View SE. La vulnerabilidad permite a un usuario desde un sistema remoto con FTView enviar un paquete al servidor del cliente para ver un proyecto HMI. Debido a la falta de autenticaci\\u00f3n adecuada, esta acci\\u00f3n se permite sin una verificaci\\u00f3n de autenticaci\\u00f3n adecuada.\"}]",
      "id": "CVE-2024-37368",
      "lastModified": "2024-11-21T09:23:43.270",
      "metrics": "{\"cvssMetricV40\": [{\"source\": \"PSIRT@rockwellautomation.com\", \"type\": \"Secondary\", \"cvssData\": {\"version\": \"4.0\", \"vectorString\": \"CVSS:4.0/AV:N/AC:L/AT:P/PR:N/UI:N/VC:H/VI:N/VA:N/SC:N/SI:N/SA:N/E:X/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:X\", \"baseScore\": 8.2, \"baseSeverity\": \"HIGH\", \"attackVector\": \"NETWORK\", \"attackComplexity\": \"LOW\", \"attackRequirements\": \"PRESENT\", \"privilegesRequired\": \"NONE\", \"userInteraction\": \"NONE\", \"vulnerableSystemConfidentiality\": \"HIGH\", \"vulnerableSystemIntegrity\": \"NONE\", \"vulnerableSystemAvailability\": \"NONE\", \"subsequentSystemConfidentiality\": \"NONE\", \"subsequentSystemIntegrity\": \"NONE\", \"subsequentSystemAvailability\": \"NONE\", \"exploitMaturity\": \"NOT_DEFINED\", \"confidentialityRequirements\": \"NOT_DEFINED\", \"integrityRequirements\": \"NOT_DEFINED\", \"availabilityRequirements\": \"NOT_DEFINED\", \"modifiedAttackVector\": \"NOT_DEFINED\", \"modifiedAttackComplexity\": \"NOT_DEFINED\", \"modifiedAttackRequirements\": \"NOT_DEFINED\", \"modifiedPrivilegesRequired\": \"NOT_DEFINED\", \"modifiedUserInteraction\": \"NOT_DEFINED\", \"modifiedVulnerableSystemConfidentiality\": \"NOT_DEFINED\", \"modifiedVulnerableSystemIntegrity\": \"NOT_DEFINED\", \"modifiedVulnerableSystemAvailability\": \"NOT_DEFINED\", \"modifiedSubsequentSystemConfidentiality\": \"NOT_DEFINED\", \"modifiedSubsequentSystemIntegrity\": \"NOT_DEFINED\", \"modifiedSubsequentSystemAvailability\": \"NOT_DEFINED\", \"safety\": \"NOT_DEFINED\", \"automatable\": \"NOT_DEFINED\", \"recovery\": \"NOT_DEFINED\", \"valueDensity\": \"NOT_DEFINED\", \"vulnerabilityResponseEffort\": \"NOT_DEFINED\", \"providerUrgency\": \"NOT_DEFINED\"}}]}",
      "published": "2024-06-14T15:15:52.100",
      "references": "[{\"url\": \"https://https://www.rockwellautomation.com/en-us/trust-center/security-advisories/advisory.SD1676.html\", \"source\": \"PSIRT@rockwellautomation.com\"}, {\"url\": \"https://https://www.rockwellautomation.com/en-us/trust-center/security-advisories/advisory.SD1676.html\", \"source\": \"af854a3a-2127-422b-91ae-364da2661108\"}]",
      "sourceIdentifier": "PSIRT@rockwellautomation.com",
      "vulnStatus": "Awaiting Analysis",
      "weaknesses": "[{\"source\": \"PSIRT@rockwellautomation.com\", \"type\": \"Secondary\", \"description\": [{\"lang\": \"en\", \"value\": \"CWE-287\"}]}]"
    },
    "nvd": "{\"cve\":{\"id\":\"CVE-2024-37368\",\"sourceIdentifier\":\"PSIRT@rockwellautomation.com\",\"published\":\"2024-06-14T15:15:52.100\",\"lastModified\":\"2025-01-31T15:44:29.627\",\"vulnStatus\":\"Analyzed\",\"cveTags\":[],\"descriptions\":[{\"lang\":\"en\",\"value\":\"A user authentication vulnerability exists in the Rockwell Automation\u00a0FactoryTalk\u00ae View SE. The vulnerability allows a user from a remote system with FTView to send a packet to the customer\u2019s server to view an HMI project. Due to the lack of proper authentication, this action is allowed without proper authentication verification.\"},{\"lang\":\"es\",\"value\":\"Existe una vulnerabilidad de autenticaci\u00f3n de usuario en Rockwell Automation FactoryTalk\u00ae View SE. La vulnerabilidad permite a un usuario desde un sistema remoto con FTView enviar un paquete al servidor del cliente para ver un proyecto HMI. Debido a la falta de autenticaci\u00f3n adecuada, esta acci\u00f3n se permite sin una verificaci\u00f3n de autenticaci\u00f3n adecuada.\"}],\"metrics\":{\"cvssMetricV40\":[{\"source\":\"PSIRT@rockwellautomation.com\",\"type\":\"Secondary\",\"cvssData\":{\"version\":\"4.0\",\"vectorString\":\"CVSS:4.0/AV:N/AC:L/AT:P/PR:N/UI:N/VC:H/VI:N/VA:N/SC:N/SI:N/SA:N/E:X/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:X\",\"baseScore\":8.2,\"baseSeverity\":\"HIGH\",\"attackVector\":\"NETWORK\",\"attackComplexity\":\"LOW\",\"attackRequirements\":\"PRESENT\",\"privilegesRequired\":\"NONE\",\"userInteraction\":\"NONE\",\"vulnConfidentialityImpact\":\"HIGH\",\"vulnIntegrityImpact\":\"NONE\",\"vulnAvailabilityImpact\":\"NONE\",\"subConfidentialityImpact\":\"NONE\",\"subIntegrityImpact\":\"NONE\",\"subAvailabilityImpact\":\"NONE\",\"exploitMaturity\":\"NOT_DEFINED\",\"confidentialityRequirement\":\"NOT_DEFINED\",\"integrityRequirement\":\"NOT_DEFINED\",\"availabilityRequirement\":\"NOT_DEFINED\",\"modifiedAttackVector\":\"NOT_DEFINED\",\"modifiedAttackComplexity\":\"NOT_DEFINED\",\"modifiedAttackRequirements\":\"NOT_DEFINED\",\"modifiedPrivilegesRequired\":\"NOT_DEFINED\",\"modifiedUserInteraction\":\"NOT_DEFINED\",\"modifiedVulnConfidentialityImpact\":\"NOT_DEFINED\",\"modifiedVulnIntegrityImpact\":\"NOT_DEFINED\",\"modifiedVulnAvailabilityImpact\":\"NOT_DEFINED\",\"modifiedSubConfidentialityImpact\":\"NOT_DEFINED\",\"modifiedSubIntegrityImpact\":\"NOT_DEFINED\",\"modifiedSubAvailabilityImpact\":\"NOT_DEFINED\",\"Safety\":\"NOT_DEFINED\",\"Automatable\":\"NOT_DEFINED\",\"Recovery\":\"NOT_DEFINED\",\"valueDensity\":\"NOT_DEFINED\",\"vulnerabilityResponseEffort\":\"NOT_DEFINED\",\"providerUrgency\":\"NOT_DEFINED\"}}],\"cvssMetricV31\":[{\"source\":\"nvd@nist.gov\",\"type\":\"Primary\",\"cvssData\":{\"version\":\"3.1\",\"vectorString\":\"CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N\",\"baseScore\":7.5,\"baseSeverity\":\"HIGH\",\"attackVector\":\"NETWORK\",\"attackComplexity\":\"LOW\",\"privilegesRequired\":\"NONE\",\"userInteraction\":\"NONE\",\"scope\":\"UNCHANGED\",\"confidentialityImpact\":\"HIGH\",\"integrityImpact\":\"NONE\",\"availabilityImpact\":\"NONE\"},\"exploitabilityScore\":3.9,\"impactScore\":3.6}]},\"weaknesses\":[{\"source\":\"PSIRT@rockwellautomation.com\",\"type\":\"Secondary\",\"description\":[{\"lang\":\"en\",\"value\":\"CWE-287\"}]},{\"source\":\"nvd@nist.gov\",\"type\":\"Primary\",\"description\":[{\"lang\":\"en\",\"value\":\"CWE-306\"}]}],\"configurations\":[{\"nodes\":[{\"operator\":\"OR\",\"negate\":false,\"cpeMatch\":[{\"vulnerable\":true,\"criteria\":\"cpe:2.3:a:rockwellautomation:factorytalk_view:*:*:*:*:se:*:*:*\",\"versionStartIncluding\":\"11.0\",\"versionEndExcluding\":\"14.0\",\"matchCriteriaId\":\"A0FFEADC-A55F-449A-9063-B0152A366906\"}]}]}],\"references\":[{\"url\":\"https://https://www.rockwellautomation.com/en-us/trust-center/security-advisories/advisory.SD1676.html\",\"source\":\"PSIRT@rockwellautomation.com\",\"tags\":[\"Vendor Advisory\"]},{\"url\":\"https://https://www.rockwellautomation.com/en-us/trust-center/security-advisories/advisory.SD1676.html\",\"source\":\"af854a3a-2127-422b-91ae-364da2661108\",\"tags\":[\"Vendor Advisory\"]}]}}",
    "vulnrichment": {
      "containers": "{\"adp\": [{\"title\": \"CISA ADP Vulnrichment\", \"metrics\": [{\"other\": {\"type\": \"ssvc\", \"content\": {\"id\": \"CVE-2024-37368\", \"role\": \"CISA Coordinator\", \"options\": [{\"Exploitation\": \"none\"}, {\"Automatable\": \"yes\"}, {\"Technical Impact\": \"partial\"}], \"version\": \"2.0.3\", \"timestamp\": \"2024-06-18T16:26:32.782829Z\"}}}], \"affected\": [{\"cpes\": [\"cpe:2.3:a:rockwellautomation:factorytalk_view:-:*:*:*:se:*:*:*\"], \"vendor\": \"rockwellautomation\", \"product\": \"factorytalk_view\", \"versions\": [{\"status\": \"affected\", \"version\": \"v11.0\", \"lessThan\": \"v14.0\", \"versionType\": \"custom\"}], \"defaultStatus\": \"unaffected\"}], \"providerMetadata\": {\"orgId\": \"134c704f-9b21-4f2e-91b3-4a467353bcc0\", \"shortName\": \"CISA-ADP\", \"dateUpdated\": \"2024-06-18T16:33:00.957Z\"}}], \"cna\": {\"title\": \"Rockwell Automation FactoryTalk\\u00ae View SE v11 Information Leakage Vulnerability via Authentication Restriction\", \"source\": {\"discovery\": \"INTERNAL\"}, \"impacts\": [{\"capecId\": \"CAPEC-114\", \"descriptions\": [{\"lang\": \"en\", \"value\": \"CAPEC-114 Authentication Abuse\"}]}], \"metrics\": [{\"format\": \"CVSS\", \"cvssV4_0\": {\"Safety\": \"NOT_DEFINED\", \"version\": \"4.0\", \"Recovery\": \"NOT_DEFINED\", \"baseScore\": 8.2, \"Automatable\": \"NOT_DEFINED\", \"attackVector\": \"NETWORK\", \"baseSeverity\": \"HIGH\", \"valueDensity\": \"NOT_DEFINED\", \"vectorString\": \"CVSS:4.0/AV:N/AC:L/AT:P/PR:N/UI:N/VC:H/VI:N/VA:N/SC:N/SI:N/SA:N\", \"providerUrgency\": \"NOT_DEFINED\", \"userInteraction\": \"NONE\", \"attackComplexity\": \"LOW\", \"attackRequirements\": \"PRESENT\", \"privilegesRequired\": \"NONE\", \"subIntegrityImpact\": \"NONE\", \"vulnIntegrityImpact\": \"NONE\", \"subAvailabilityImpact\": \"NONE\", \"vulnAvailabilityImpact\": \"NONE\", \"subConfidentialityImpact\": \"NONE\", \"vulnConfidentialityImpact\": \"HIGH\", \"vulnerabilityResponseEffort\": \"NOT_DEFINED\"}, \"scenarios\": [{\"lang\": \"en\", \"value\": \"GENERAL\"}]}], \"affected\": [{\"vendor\": \"Rockwell Automation\", \"product\": \"FactoryTalk\\u00ae View SE\", \"versions\": [{\"status\": \"affected\", \"version\": \"v11.0\"}], \"defaultStatus\": \"unaffected\"}], \"solutions\": [{\"lang\": \"en\", \"value\": \"*  Corrected in software version v14.0.\\n  *  \\n\\nUsers using the affected software, who are not able to upgrade to one of the corrected versions, are encouraged to apply security best practices, where possible.\\u202f\\u202f\\u202f\\n\\n  *  It is recommended that users enforce proper access controls within the network and segment networks containing sensitive information using IPSec:  https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/1090456 \\n\\n\\n\\n\\n  *   Security Best Practice https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/1085012/loc/en_US#__highlight s\", \"supportingMedia\": [{\"type\": \"text/html\", \"value\": \"\u003cul\u003e\u003cli\u003eCorrected in software version v14.0.\u003c/li\u003e\u003cli\u003e\\n\\n\u003cp\u003eUsers using the affected software, who are not able to upgrade to one of the corrected versions, are encouraged to apply security best practices, where possible.\\u202f\\u202f\\u202f\u003c/p\u003e\u003cul\u003e\u003cli\u003e\u003cp\u003eIt is recommended that users enforce proper access controls within the network and segment networks containing sensitive information using IPSec: \u003ca target=\\\"_blank\\\" rel=\\\"nofollow\\\" href=\\\"https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/1090456\\\"\u003ehttps://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/1090456\u003c/a\u003e\u003c/p\u003e\u003c/li\u003e\u003c/ul\u003e\u003cul\u003e\u003cli\u003e\u003cp\u003e\u003ca target=\\\"_blank\\\" rel=\\\"nofollow\\\" href=\\\"https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/1085012/loc/en_US#__highlight\\\"\u003eSecurity Best Practice\u003c/a\u003es\u003c/p\u003e\u003c/li\u003e\u003c/ul\u003e\u003c/li\u003e\u003c/ul\u003e\", \"base64\": false}]}], \"datePublic\": \"2024-06-13T13:00:00.000Z\", \"references\": [{\"url\": \"https://https://www.rockwellautomation.com/en-us/trust-center/security-advisories/advisory.SD1676.html\"}], \"x_generator\": {\"engine\": \"Vulnogram 0.2.0\"}, \"descriptions\": [{\"lang\": \"en\", \"value\": \"A user authentication vulnerability exists in the Rockwell Automation\\u00a0FactoryTalk\\u00ae View SE. The vulnerability allows a user from a remote system with FTView to send a packet to the customer\\u2019s server to view an HMI project. Due to the lack of proper authentication, this action is allowed without proper authentication verification.\", \"supportingMedia\": [{\"type\": \"text/html\", \"value\": \"\\n\\n\u003cspan style=\\\"background-color: rgb(255, 255, 255);\\\"\u003eA user authentication vulnerability exists in the Rockwell Automation\u0026nbsp;FactoryTalk\\u00ae View SE. The vulnerability allows a user from a remote system with FTView to send a packet to the customer\\u2019s server to view an HMI project. Due to the lack of proper authentication, this action is allowed without proper authentication verification.\u003c/span\u003e\\n\\n\", \"base64\": false}]}], \"problemTypes\": [{\"descriptions\": [{\"lang\": \"en\", \"type\": \"CWE\", \"cweId\": \"CWE-287\", \"description\": \"CWE-287 Improper Authentication\"}]}], \"providerMetadata\": {\"orgId\": \"b73dd486-f505-4403-b634-40b078b177f0\", \"shortName\": \"Rockwell\", \"dateUpdated\": \"2024-06-14T14:30:53.422Z\"}}}",
      "cveMetadata": "{\"cveId\": \"CVE-2024-37368\", \"state\": \"PUBLISHED\", \"dateUpdated\": \"2024-06-18T16:33:16.826Z\", \"dateReserved\": \"2024-06-06T20:18:27.551Z\", \"assignerOrgId\": \"b73dd486-f505-4403-b634-40b078b177f0\", \"datePublished\": \"2024-06-14T14:30:53.422Z\", \"assignerShortName\": \"Rockwell\"}",
      "dataType": "CVE_RECORD",
      "dataVersion": "5.1"
    }
  }
}


Log in or create an account to share your comment.




Tags
Taxonomy of the tags.


Loading…

Loading…

Loading…

Sightings

Author Source Type Date

Nomenclature

  • Seen: The vulnerability was mentioned, discussed, or observed by the user.
  • Confirmed: The vulnerability has been validated from an analyst's perspective.
  • Published Proof of Concept: A public proof of concept is available for this vulnerability.
  • Exploited: The vulnerability was observed as exploited by the user who reported the sighting.
  • Patched: The vulnerability was observed as successfully patched by the user who reported the sighting.
  • Not exploited: The vulnerability was not observed as exploited by the user who reported the sighting.
  • Not confirmed: The user expressed doubt about the validity of the vulnerability.
  • Not patched: The vulnerability was not observed as successfully patched by the user who reported the sighting.


Loading…

Detection rules are retrieved from Rulezet.

Loading…

Loading…