FKIE_CVE-2013-2805
Vulnerability from fkie_nvd - Published: 2019-03-26 18:29 - Updated: 2024-11-21 01:52
Severity ?
Summary
Rockwell Automation RSLinx Enterprise Software (LogReceiver.exe) CPR9, CPR9-SR1, CPR9-SR2, CPR9-SR3, CPR9-SR4, CPR9-SR5, CPR9-SR5.1, and CPR9-SR6 does not handle input correctly and results in a logic error if it receives a datagram with an incorrect value in the “Record Data Size” field. By sending a datagram to the service over Port 4444/UDP with the “Record Data Size” field modified to an oversized value, an attacker could cause an out-of-bounds read access violation that leads to a service crash. The service can be recovered with a manual reboot. The patches and details pertaining to this vulnerability can be found at the following Rockwell Automation Security Advisory link (login is required): https://rockwellautomation.custhelp.com/app/answers/detail/a_id/537599
References
| URL | Tags | ||
|---|---|---|---|
| ics-cert@hq.dhs.gov | https://ics-cert.us-cert.gov/advisories/ICSA-13-095-02 | Third Party Advisory, US Government Resource | |
| af854a3a-2127-422b-91ae-364da2661108 | https://ics-cert.us-cert.gov/advisories/ICSA-13-095-02 | Third Party Advisory, US Government Resource |
Impacted products
| Vendor | Product | Version | |
|---|---|---|---|
| rockwellautomation | rslinx_enterprise | 5.10.00 | |
| rockwellautomation | rslinx_enterprise | 5.10.01 | |
| rockwellautomation | rslinx_enterprise | 5.20.00 | |
| rockwellautomation | rslinx_enterprise | 5.21.00 | |
| rockwellautomation | rslinx_enterprise | 5.30.00 | |
| rockwellautomation | rslinx_enterprise | 5.40.00 | |
| rockwellautomation | rslinx_enterprise | 5.50.00 | |
| rockwellautomation | rslinx_enterprise | 5.51.00 | |
| rockwellautomation | rslinx_enterprise | 5.60.00 |
{
"configurations": [
{
"nodes": [
{
"cpeMatch": [
{
"criteria": "cpe:2.3:a:rockwellautomation:rslinx_enterprise:5.10.00:*:*:*:*:*:*:*",
"matchCriteriaId": "D42DF440-5AC1-4B7D-9A32-A30E2807D21B",
"vulnerable": true
},
{
"criteria": "cpe:2.3:a:rockwellautomation:rslinx_enterprise:5.10.01:*:*:*:*:*:*:*",
"matchCriteriaId": "436B1B6F-7B5F-4851-A04B-8E4FD1CCE75B",
"vulnerable": true
},
{
"criteria": "cpe:2.3:a:rockwellautomation:rslinx_enterprise:5.20.00:*:*:*:*:*:*:*",
"matchCriteriaId": "ECE341BF-F144-4F44-A232-0F4CB97CEAFF",
"vulnerable": true
},
{
"criteria": "cpe:2.3:a:rockwellautomation:rslinx_enterprise:5.21.00:*:*:*:*:*:*:*",
"matchCriteriaId": "9B9B5530-419A-4587-A1D9-9E92ABB99300",
"vulnerable": true
},
{
"criteria": "cpe:2.3:a:rockwellautomation:rslinx_enterprise:5.30.00:*:*:*:*:*:*:*",
"matchCriteriaId": "49BDD83C-D14A-434D-BA89-8451011C5F07",
"vulnerable": true
},
{
"criteria": "cpe:2.3:a:rockwellautomation:rslinx_enterprise:5.40.00:*:*:*:*:*:*:*",
"matchCriteriaId": "7C37C557-4DA4-4A4F-8F5A-33DF41D37C45",
"vulnerable": true
},
{
"criteria": "cpe:2.3:a:rockwellautomation:rslinx_enterprise:5.50.00:*:*:*:*:*:*:*",
"matchCriteriaId": "6F17A84F-CFA8-4BA9-A3D5-9044F53FC9FF",
"vulnerable": true
},
{
"criteria": "cpe:2.3:a:rockwellautomation:rslinx_enterprise:5.51.00:*:*:*:*:*:*:*",
"matchCriteriaId": "4648726F-63DB-4F97-9A20-B224FDE5AA53",
"vulnerable": true
},
{
"criteria": "cpe:2.3:a:rockwellautomation:rslinx_enterprise:5.60.00:*:*:*:*:*:*:*",
"matchCriteriaId": "33F649D7-E46D-4378-B044-ABC7C20D1AAD",
"vulnerable": true
}
],
"negate": false,
"operator": "OR"
}
]
}
],
"cveTags": [],
"descriptions": [
{
"lang": "en",
"value": "Rockwell Automation RSLinx Enterprise Software (LogReceiver.exe) CPR9, CPR9-SR1, CPR9-SR2, CPR9-SR3, CPR9-SR4, CPR9-SR5, CPR9-SR5.1, and CPR9-SR6 does not handle input correctly and results in a logic error if it receives a datagram with an incorrect value in the \u201cRecord Data Size\u201d field. By sending a datagram to the service over Port 4444/UDP with the \u201cRecord Data Size\u201d field modified to an oversized value, an attacker could cause an out-of-bounds read access violation that leads to a service crash. The service can be recovered with a manual reboot. The patches and details pertaining to this vulnerability can be found at the following Rockwell Automation Security Advisory link (login is required): https://rockwellautomation.custhelp.com/app/answers/detail/a_id/537599"
},
{
"lang": "es",
"value": "El software RSLinx Enterprise de Rockwell Automation (LogReceiver.exe) CPR9, CPR9-SR1, CPR9-SR2, CPR9-SR3, CPR9-SR4, CPR9-SR5, CPR9-SR5.1 y CPR9-SR6 no maneja la entrada correctamente y da como resultado un error l\u00f3gico si recibe un datagrama con un valor incorrecto en el campo\" Record Data Size\u201d. Al enviar un datagrama al servicio a trav\u00e9s del puerto 4444 / UDP con el campo \u201cRecord Data Size\u201d modificado a un valor demasiado grande, un atacante podr\u00eda causar una infracci\u00f3n de acceso de lectura fuera de los l\u00edmites que conduzca a un bloqueo del servicio. El servicio se puede recuperar con un reinicio manual. Los parches y detalles relacionados con esta vulnerabilidad se pueden encontrar en el siguiente enlace de aviso de seguridad de Rockwell Automation (se requiere inicio de sesi\u00f3n): https://rockwellautomation.custhelp.com/app/answers/detail/a_id/537599"
}
],
"id": "CVE-2013-2805",
"lastModified": "2024-11-21T01:52:23.820",
"metrics": {
"cvssMetricV2": [
{
"acInsufInfo": false,
"baseSeverity": "HIGH",
"cvssData": {
"accessComplexity": "LOW",
"accessVector": "NETWORK",
"authentication": "NONE",
"availabilityImpact": "COMPLETE",
"baseScore": 7.8,
"confidentialityImpact": "NONE",
"integrityImpact": "NONE",
"vectorString": "AV:N/AC:L/Au:N/C:N/I:N/A:C",
"version": "2.0"
},
"exploitabilityScore": 10.0,
"impactScore": 6.9,
"obtainAllPrivilege": false,
"obtainOtherPrivilege": false,
"obtainUserPrivilege": false,
"source": "nvd@nist.gov",
"type": "Primary",
"userInteractionRequired": false
}
],
"cvssMetricV30": [
{
"cvssData": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 7.5,
"baseSeverity": "HIGH",
"confidentialityImpact": "NONE",
"integrityImpact": "NONE",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"userInteraction": "NONE",
"vectorString": "CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H",
"version": "3.0"
},
"exploitabilityScore": 3.9,
"impactScore": 3.6,
"source": "nvd@nist.gov",
"type": "Primary"
}
]
},
"published": "2019-03-26T18:29:00.310",
"references": [
{
"source": "ics-cert@hq.dhs.gov",
"tags": [
"Third Party Advisory",
"US Government Resource"
],
"url": "https://ics-cert.us-cert.gov/advisories/ICSA-13-095-02"
},
{
"source": "af854a3a-2127-422b-91ae-364da2661108",
"tags": [
"Third Party Advisory",
"US Government Resource"
],
"url": "https://ics-cert.us-cert.gov/advisories/ICSA-13-095-02"
}
],
"sourceIdentifier": "ics-cert@hq.dhs.gov",
"vulnStatus": "Modified",
"weaknesses": [
{
"description": [
{
"lang": "en",
"value": "CWE-125"
}
],
"source": "ics-cert@hq.dhs.gov",
"type": "Secondary"
},
{
"description": [
{
"lang": "en",
"value": "CWE-125"
}
],
"source": "nvd@nist.gov",
"type": "Primary"
}
]
}
Loading…
Loading…
Sightings
| Author | Source | Type | Date |
|---|
Nomenclature
- Seen: The vulnerability was mentioned, discussed, or observed by the user.
- Confirmed: The vulnerability has been validated from an analyst's perspective.
- Published Proof of Concept: A public proof of concept is available for this vulnerability.
- Exploited: The vulnerability was observed as exploited by the user who reported the sighting.
- Patched: The vulnerability was observed as successfully patched by the user who reported the sighting.
- Not exploited: The vulnerability was not observed as exploited by the user who reported the sighting.
- Not confirmed: The user expressed doubt about the validity of the vulnerability.
- Not patched: The vulnerability was not observed as successfully patched by the user who reported the sighting.
Loading…
Loading…