ICSA-10-316-01A

Vulnerability from csaf_cisa - Published: 2010-08-15 06:00 - Updated: 2025-06-05 22:08
Summary
Intellicom NetBiter WebSCADA Vulnerabilities

Notes

Legal Notice
All information products included in https://us-cert.cisa.gov/ics are provided "as is" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see https://us-cert.cisa.gov/tlp/.
CISA Disclaimer
This CSAF advisory was extracted from unstructured data and may contain inaccuracies. If you notice any errors, please reach out to the designated contact at CISA CSAF: central@cisa.dhs.gov
Recommended Practices
CISA recommends users take defensive measures to minimize the risk of exploitation.
Recommended Practices
Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet.
Recommended Practices
Locate control system networks and remote devices behind firewalls and isolating them from business networks.
Recommended Practices
When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs). Recognize VPNs may have vulnerabilities, should be updated to the most recent version available, and are only as secure as the connected devices.
Recommended Practices
CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.
Recommended Practices
CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.
Recommended Practices
CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.
Recommended Practices
Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.
Recommended Practices
Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.
Recommended Practices
CISA also recommends users take the following measures to protect themselves from social engineering attacks: Do not click web links or open attachments in unsolicited email messages. Refer to Recognizing and Avoiding Email Scams for more information on avoiding email scams. Refer to Avoiding Social Engineering and Phishing Attacks for more information on social engineering attacks.

{
  "document": {
    "category": "csaf_security_advisory",
    "csaf_version": "2.0",
    "distribution": {
      "text": "Disclosure is not limited",
      "tlp": {
        "label": "WHITE",
        "url": "https://us-cert.cisa.gov/tlp/"
      }
    },
    "lang": "en-US",
    "notes": [
      {
        "category": "legal_disclaimer",
        "text": "All information products included in https://us-cert.cisa.gov/ics are provided \"as is\" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see https://us-cert.cisa.gov/tlp/.",
        "title": "Legal Notice"
      },
      {
        "category": "general",
        "text": "This CSAF advisory was extracted from unstructured data and may contain inaccuracies. If you notice any errors, please reach out to the designated contact at CISA CSAF: central@cisa.dhs.gov",
        "title": "CISA Disclaimer"
      },
      {
        "category": "general",
        "text": "CISA recommends users take defensive measures to minimize the risk of exploitation.",
        "title": "Recommended Practices"
      },
      {
        "category": "general",
        "text": "Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet.",
        "title": "Recommended Practices"
      },
      {
        "category": "general",
        "text": "Locate control system networks and remote devices behind firewalls and isolating them from business networks.",
        "title": "Recommended Practices"
      },
      {
        "category": "general",
        "text": "When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs). Recognize VPNs may have vulnerabilities, should be updated to the most recent version available, and are only as secure as the connected devices.",
        "title": "Recommended Practices"
      },
      {
        "category": "general",
        "text": "CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.",
        "title": "Recommended Practices"
      },
      {
        "category": "general",
        "text": "CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.",
        "title": "Recommended Practices"
      },
      {
        "category": "general",
        "text": "CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.",
        "title": "Recommended Practices"
      },
      {
        "category": "general",
        "text": "Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.",
        "title": "Recommended Practices"
      },
      {
        "category": "general",
        "text": "Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.",
        "title": "Recommended Practices"
      },
      {
        "category": "general",
        "text": "CISA also recommends users take the following measures to protect themselves from social engineering attacks: Do not click web links or open attachments in unsolicited email messages. Refer to Recognizing and Avoiding Email Scams for more information on avoiding email scams. Refer to Avoiding Social Engineering and Phishing Attacks for more information on social engineering attacks.",
        "title": "Recommended Practices"
      }
    ],
    "publisher": {
      "category": "coordinator",
      "contact_details": "central@cisa.dhs.gov",
      "name": "CISA",
      "namespace": "https://www.cisa.gov/"
    },
    "references": [
      {
        "category": "self",
        "summary": "ICS Advisory ICSA-10-316-01 JSON",
        "url": "https://raw.githubusercontent.com/cisagov/CSAF/develop/csaf_files/OT/white/2010/icsa-10-316-01a.json"
      },
      {
        "category": "self",
        "summary": "ICS Advisory ICSA-10-316-01 - Web Version",
        "url": "https://www.cisa.gov/news-events/ics-advisories/icsa-10-316-01a"
      },
      {
        "category": "external",
        "summary": "Recommended Practices",
        "url": "https://www.cisa.gov/uscert/ics/alerts/ICS-ALERT-10-301-01"
      },
      {
        "category": "external",
        "summary": "Recommended Practices",
        "url": "https://www.cisa.gov/resources-tools/resources/ics-recommended-practices"
      },
      {
        "category": "external",
        "summary": "Recommended Practices",
        "url": "https://www.cisa.gov/topics/industrial-control-systems"
      },
      {
        "category": "external",
        "summary": "Recommended Practices",
        "url": "https://us-cert.cisa.gov/sites/default/files/recommended_practices/NCCIC_ICS-CERT_Defense_in_Depth_2016_S508C.pdf"
      },
      {
        "category": "external",
        "summary": "Recommended Practices",
        "url": "https://www.cisa.gov/sites/default/files/publications/Cybersecurity_Best_Practices_for_Industrial_Control_Systems.pdf"
      },
      {
        "category": "external",
        "summary": "Recommended Practices",
        "url": "https://www.cisa.gov/uscert/ics/tips/ICS-TIP-12-146-01B"
      },
      {
        "category": "external",
        "summary": "Recommended Practices",
        "url": "https://www.cisa.gov/uscert/sites/default/files/publications/emailscams0905.pdf"
      },
      {
        "category": "external",
        "summary": "Recommended Practices",
        "url": "https://www.cisa.gov/uscert/ncas/tips/ST04-014"
      }
    ],
    "title": "Intellicom NetBiter WebSCADA Vulnerabilities",
    "tracking": {
      "current_release_date": "2025-06-05T22:08:03.683549Z",
      "generator": {
        "date": "2025-06-05T22:08:03.683491Z",
        "engine": {
          "name": "CISA CSAF Generator",
          "version": "1.0.0"
        }
      },
      "id": "ICSA-10-316-01A",
      "initial_release_date": "2010-08-15T06:00:00.000000Z",
      "revision_history": [
        {
          "date": "2010-08-15T06:00:00.000000Z",
          "legacy_version": "Initial",
          "number": "1",
          "summary": "Initial Publication"
        },
        {
          "date": "2025-06-05T22:08:03.683549Z",
          "legacy_version": "CSAF Conversion",
          "number": "2",
          "summary": "Advisory converted into a CSAF"
        }
      ],
      "status": "final",
      "version": "2"
    }
  },
  "product_tree": {
    "branches": [
      {
        "branches": [
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "vers:all/*",
                "product": {
                  "name": "Intellicom WebSCADA (WS100): vers:all/*",
                  "product_id": "CSAFPID-0001"
                }
              }
            ],
            "category": "product_name",
            "name": "WebSCADA (WS100)"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "vers:all/*",
                "product": {
                  "name": "Intellicom WebSCADA (WS200): vers:all/*",
                  "product_id": "CSAFPID-0002"
                }
              }
            ],
            "category": "product_name",
            "name": "WebSCADA (WS200)"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "vers:all/*",
                "product": {
                  "name": "Intellicom Easy Connect (EC150): vers:all/*",
                  "product_id": "CSAFPID-0003"
                }
              }
            ],
            "category": "product_name",
            "name": "Easy Connect (EC150)"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "vers:all/*",
                "product": {
                  "name": "Intellicom Modbus RTU \u2013 TCP Gateway (MB100): vers:all/*",
                  "product_id": "CSAFPID-0004"
                }
              }
            ],
            "category": "product_name",
            "name": "Modbus RTU \u2013 TCP Gateway (MB100)"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "vers:all/*",
                "product": {
                  "name": "Intellicom Serial Ethernet Server (SS100): vers:all/*",
                  "product_id": "CSAFPID-0005"
                }
              }
            ],
            "category": "product_name",
            "name": "Serial Ethernet Server (SS100)"
          }
        ],
        "category": "vendor",
        "name": "Intellicom"
      }
    ]
  },
  "vulnerabilities": [
    {
      "cve": "CVE-2010-4733",
      "cwe": {
        "id": "CWE-1392",
        "name": "Use of Default Credentials"
      },
      "notes": [
        {
          "category": "summary",
          "text": "WebSCADA WS100 and WS200, Easy Connect EC150, Modbus RTU - TCP Gateway MB100, and Serial Ethernet Server SS100 on the IntelliCom NetBiter NB100 and NB200 platforms have a default username and password, which makes it easier for remote attackers to obtain superadmin access via the web interface, a different vulnerability than CVE-2009-4463.",
          "title": "Vulnerability Summary"
        }
      ],
      "product_status": {
        "known_affected": [
          "CSAFPID-0001",
          "CSAFPID-0002",
          "CSAFPID-0003",
          "CSAFPID-0004",
          "CSAFPID-0005"
        ]
      },
      "remediations": [
        {
          "category": "mitigation",
          "details": "The default user in NetBiter products has superadmin privileges. Therefore, it is strongly recommended that users change the default password immediately when commissioning the product. In addition, users are advised to provide only the necessary privileges to non-administrator users of the product (least privileges mode of operation).",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005"
          ]
        },
        {
          "category": "mitigation",
          "details": "IntelliCom recommendsIntelliCom, IntelliCom Security Bulletin - ISFR-4404-0010- Information. \u201cISFR-4404-0010.npb\u201d available from that users of the WS100/WS200 products apply the following patch \u201cISFR-4404-0010.npb, available from (http://support.intellicom.se).\u201d",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005"
          ],
          "url": "http://support.intellicom.se"
        },
        {
          "category": "mitigation",
          "details": "Other recommendations include: Place all control systems assets behind firewalls and isolated from the business network and the Internet. Deploy secure remote access methods such as virtual private networks (VPNs) for remote access. Remove, disable, or rename any default system accounts (where possible). Implement account lockout policies to reduce the risk from brute forcing attempts. Implement policies requiring the use of strong passwords. (http://csrc.nist.gov/publications/drafts/800-118/draft-sp800-118.pdf).  Monitor the creation of administrator level accounts by third-party vendors.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005"
          ],
          "url": "http://csrc.nist.gov/publications/drafts/800-118/draft-sp800-118.pdf"
        }
      ],
      "scores": [
        {
          "cvss_v2": {
            "baseScore": 10.0,
            "vectorString": "AV:N/AC:L/Au:N/C:C/I:C/A:C",
            "version": "2.0"
          },
          "products": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005"
          ]
        }
      ]
    },
    {
      "cve": "CVE-2010-4731",
      "cwe": {
        "id": "CWE-25",
        "name": "Path Traversal: \u0027/../filedir\u0027"
      },
      "notes": [
        {
          "category": "summary",
          "text": "Absolute path traversal vulnerability in cgi-bin/read.cgi in WebSCADA WS100 and WS200, Easy Connect EC150, Modbus RTU - TCP Gateway MB100, and Serial Ethernet Server SS100 on the IntelliCom NetBiter NB100 and NB200 platforms allows remote authenticated administrators to read arbitrary files via a full pathname in the file parameter, a different vulnerability than CVE-2009-4463.",
          "title": "Vulnerability Summary"
        }
      ],
      "product_status": {
        "known_affected": [
          "CSAFPID-0001",
          "CSAFPID-0002",
          "CSAFPID-0003",
          "CSAFPID-0004",
          "CSAFPID-0005"
        ]
      },
      "remediations": [
        {
          "category": "mitigation",
          "details": "The default user in NetBiter products has superadmin privileges. Therefore, it is strongly recommended that users change the default password immediately when commissioning the product. In addition, users are advised to provide only the necessary privileges to non-administrator users of the product (least privileges mode of operation).",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005"
          ]
        },
        {
          "category": "mitigation",
          "details": "IntelliCom recommendsIntelliCom, IntelliCom Security Bulletin - ISFR-4404-0010- Information. \u201cISFR-4404-0010.npb\u201d available from that users of the WS100/WS200 products apply the following patch \u201cISFR-4404-0010.npb, available from (http://support.intellicom.se).\u201d",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005"
          ],
          "url": "http://support.intellicom.se"
        },
        {
          "category": "mitigation",
          "details": "Other recommendations include: Place all control systems assets behind firewalls and isolated from the business network and the Internet. Deploy secure remote access methods such as virtual private networks (VPNs) for remote access. Remove, disable, or rename any default system accounts (where possible). Implement account lockout policies to reduce the risk from brute forcing attempts. Implement policies requiring the use of strong passwords. (http://csrc.nist.gov/publications/drafts/800-118/draft-sp800-118.pdf).  Monitor the creation of administrator level accounts by third-party vendors.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005"
          ],
          "url": "http://csrc.nist.gov/publications/drafts/800-118/draft-sp800-118.pdf"
        }
      ],
      "scores": [
        {
          "cvss_v2": {
            "baseScore": 6.8,
            "vectorString": "AV:N/AC:L/Au:S/C:C/I:N/A:N",
            "version": "2.0"
          },
          "products": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005"
          ]
        }
      ]
    },
    {
      "cve": "CVE-2010-4732",
      "cwe": {
        "id": "CWE-94",
        "name": "Improper Control of Generation of Code (\u0027Code Injection\u0027)"
      },
      "notes": [
        {
          "category": "summary",
          "text": "cgi-bin/read.cgi in WebSCADA WS100 and WS200, Easy Connect EC150, Modbus RTU - TCP Gateway MB100, and Serial Ethernet Server SS100 on the IntelliCom NetBiter NB100 and NB200 platforms allows remote authenticated administrators to execute arbitrary code by using a config.html 2.conf action to replace the logo page\u0027s GIF image file with a file containing this code, a different vulnerability than CVE-2009-4463.",
          "title": "Vulnerability Summary"
        }
      ],
      "product_status": {
        "known_affected": [
          "CSAFPID-0001",
          "CSAFPID-0002",
          "CSAFPID-0003",
          "CSAFPID-0004",
          "CSAFPID-0005"
        ]
      },
      "remediations": [
        {
          "category": "mitigation",
          "details": "The default user in NetBiter products has superadmin privileges. Therefore, it is strongly recommended that users change the default password immediately when commissioning the product. In addition, users are advised to provide only the necessary privileges to non-administrator users of the product (least privileges mode of operation).",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005"
          ]
        },
        {
          "category": "mitigation",
          "details": "IntelliCom recommendsIntelliCom, IntelliCom Security Bulletin - ISFR-4404-0010- Information. \u201cISFR-4404-0010.npb\u201d available from that users of the WS100/WS200 products apply the following patch \u201cISFR-4404-0010.npb, available from (http://support.intellicom.se).\u201d",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005"
          ],
          "url": "http://support.intellicom.se"
        },
        {
          "category": "mitigation",
          "details": "Other recommendations include: Place all control systems assets behind firewalls and isolated from the business network and the Internet. Deploy secure remote access methods such as virtual private networks (VPNs) for remote access. Remove, disable, or rename any default system accounts (where possible). Implement account lockout policies to reduce the risk from brute forcing attempts. Implement policies requiring the use of strong passwords. (http://csrc.nist.gov/publications/drafts/800-118/draft-sp800-118.pdf).  Monitor the creation of administrator level accounts by third-party vendors.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005"
          ],
          "url": "http://csrc.nist.gov/publications/drafts/800-118/draft-sp800-118.pdf"
        }
      ],
      "scores": [
        {
          "cvss_v2": {
            "baseScore": 9.0,
            "vectorString": "AV:N/AC:L/Au:S/C:C/I:C/A:C",
            "version": "2.0"
          },
          "products": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005"
          ]
        }
      ]
    },
    {
      "cve": "CVE-2010-4730",
      "cwe": {
        "id": "CWE-22",
        "name": "Improper Limitation of a Pathname to a Restricted Directory (\u0027Path Traversal\u0027)"
      },
      "notes": [
        {
          "category": "summary",
          "text": "Directory traversal vulnerability in cgi-bin/read.cgi in WebSCADA WS100 and WS200, Easy Connect EC150, Modbus RTU - TCP Gateway MB100, and Serial Ethernet Server SS100 on the IntelliCom NetBiter NB100 and NB200 platforms allows remote authenticated administrators to read arbitrary files via a .. (dot dot) in the page parameter, a different vulnerability than CVE-2009-4463.",
          "title": "Vulnerability Summary"
        }
      ],
      "product_status": {
        "known_affected": [
          "CSAFPID-0001",
          "CSAFPID-0002",
          "CSAFPID-0003",
          "CSAFPID-0004",
          "CSAFPID-0005"
        ]
      },
      "remediations": [
        {
          "category": "mitigation",
          "details": "The default user in NetBiter products has superadmin privileges. Therefore, it is strongly recommended that users change the default password immediately when commissioning the product. In addition, users are advised to provide only the necessary privileges to non-administrator users of the product (least privileges mode of operation).",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005"
          ]
        },
        {
          "category": "mitigation",
          "details": "IntelliCom recommendsIntelliCom, IntelliCom Security Bulletin - ISFR-4404-0010- Information. \u201cISFR-4404-0010.npb\u201d available from that users of the WS100/WS200 products apply the following patch \u201cISFR-4404-0010.npb, available from (http://support.intellicom.se).\u201d",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005"
          ],
          "url": "http://support.intellicom.se"
        },
        {
          "category": "mitigation",
          "details": "Other recommendations include: Place all control systems assets behind firewalls and isolated from the business network and the Internet. Deploy secure remote access methods such as virtual private networks (VPNs) for remote access. Remove, disable, or rename any default system accounts (where possible). Implement account lockout policies to reduce the risk from brute forcing attempts. Implement policies requiring the use of strong passwords. (http://csrc.nist.gov/publications/drafts/800-118/draft-sp800-118.pdf).  Monitor the creation of administrator level accounts by third-party vendors.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005"
          ],
          "url": "http://csrc.nist.gov/publications/drafts/800-118/draft-sp800-118.pdf"
        }
      ],
      "scores": [
        {
          "cvss_v2": {
            "baseScore": 6.8,
            "vectorString": "AV:N/AC:L/Au:S/C:C/I:N/A:N",
            "version": "2.0"
          },
          "products": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005"
          ]
        }
      ]
    }
  ]
}


Log in or create an account to share your comment.




Tags
Taxonomy of the tags.


Loading…

Loading…

Loading…

Sightings

Author Source Type Date

Nomenclature

  • Seen: The vulnerability was mentioned, discussed, or observed by the user.
  • Confirmed: The vulnerability has been validated from an analyst's perspective.
  • Published Proof of Concept: A public proof of concept is available for this vulnerability.
  • Exploited: The vulnerability was observed as exploited by the user who reported the sighting.
  • Patched: The vulnerability was observed as successfully patched by the user who reported the sighting.
  • Not exploited: The vulnerability was not observed as exploited by the user who reported the sighting.
  • Not confirmed: The user expressed doubt about the validity of the vulnerability.
  • Not patched: The vulnerability was not observed as successfully patched by the user who reported the sighting.


Loading…

Detection rules are retrieved from Rulezet.

Loading…

Loading…