icsa-18-107-04
Vulnerability from csaf_cisa
Published
2018-04-17 00:00
Modified
2018-04-17 00:00
Summary
Rockwell Automation Stratix and ArmorStratix Switches
Notes
CISA Disclaimer
This CSAF advisory was extracted from unstructured data and may contain inaccuracies. If you notice any errors, please reach out to the designated contact at CISA CSAF: central@cisa.dhs.gov
Legal Notice
All information products included in https://us-cert.cisa.gov/ics are provided "as is" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see https://us-cert.cisa.gov/tlp/.
Risk evaluation
Successful exploitation of these vulnerabilities could result in loss of availability, confidentiality, and/or integrity caused by memory exhaustion, module restart, information corruption, and/or information exposure.
Critical infrastructure sectors
Critical Manufacturing, Energy, Water and Wastewater Systems
Countries/areas deployed
Worldwide
Company headquarters location
Wisconsin, USA
Recommended Practices
NCCIC reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.
Recommended Practices
NCCIC also provides a section for control systems security recommended practices on the ICS-CERT web page. Several recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.
Recommended Practices
Organizations observing any suspected malicious activity should follow their established internal procedures and report their findings to NCCIC for tracking and correlation against other incidents.
Recommended Practices
Additional mitigation guidance and recommended practices are publicly available in the ICS-CERT Technical Information Paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies, that is available for download from the ICS-CERT website.
Exploitability
No known public exploits specifically target these vulnerabilities.
{ "document": { "acknowledgments": [ { "organization": "Rockwell Automation", "summary": "reporting these vulnerabilities to NCCIC from the semi-annual Cisco IOS and IOS XE Software Security Advisory Bundled Publication" } ], "category": "csaf_security_advisory", "csaf_version": "2.0", "distribution": { "text": "Disclosure is not limited", "tlp": { "label": "WHITE", "url": "https://us-cert.cisa.gov/tlp/" } }, "lang": "en-US", "notes": [ { "category": "general", "text": "This CSAF advisory was extracted from unstructured data and may contain inaccuracies. If you notice any errors, please reach out to the designated contact at CISA CSAF: central@cisa.dhs.gov", "title": "CISA Disclaimer" }, { "category": "legal_disclaimer", "text": "All information products included in https://us-cert.cisa.gov/ics are provided \"as is\" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see https://us-cert.cisa.gov/tlp/.", "title": "Legal Notice" }, { "category": "summary", "text": "Successful exploitation of these vulnerabilities could result in loss of availability, confidentiality, and/or integrity caused by memory exhaustion, module restart, information corruption, and/or information exposure.", "title": "Risk evaluation" }, { "category": "other", "text": "Critical Manufacturing, Energy, Water and Wastewater Systems", "title": "Critical infrastructure sectors" }, { "category": "other", "text": "Worldwide", "title": "Countries/areas deployed" }, { "category": "other", "text": "Wisconsin, USA", "title": "Company headquarters location" }, { "category": "general", "text": "NCCIC reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.", "title": "Recommended Practices" }, { "category": "general", "text": "NCCIC also provides a section for control systems security recommended practices on the ICS-CERT web page. Several recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.", "title": "Recommended Practices" }, { "category": "general", "text": "Organizations observing any suspected malicious activity should follow their established internal procedures and report their findings to NCCIC for tracking and correlation against other incidents.", "title": "Recommended Practices" }, { "category": "general", "text": "Additional mitigation guidance and recommended practices are publicly available in the ICS-CERT Technical Information Paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies, that is available for download from the ICS-CERT website.", "title": "Recommended Practices" }, { "category": "other", "text": "No known public exploits specifically target these vulnerabilities.", "title": "Exploitability" } ], "publisher": { "category": "coordinator", "contact_details": "Email: CISAservicedesk@cisa.dhs.gov;\n Toll Free: 1-888-282-0870", "name": "CISA", "namespace": "https://www.cisa.gov/" }, "references": [ { "category": "self", "summary": "ICS Advisory ICSA-18-107-04 JSON", "url": "https://raw.githubusercontent.com/cisagov/CSAF/develop/csaf_files/OT/white/2018/icsa-18-107-04.json" }, { "category": "self", "summary": "ICS Advisory ICSA-18-107-04 Web Version", "url": "https://www.cisa.gov/news-events/ics-advisories/icsa-18-107-04" }, { "category": "external", "summary": "Recommended Practices", "url": "https://www.cisa.gov/news-events/ics-advisories/icsa-18-107-04" }, { "category": "external", "summary": "Recommended Practices", "url": "https://www.cisa.gov/uscert/sites/default/files/recommended_practices/NCCIC_ICS-CERT_Defense_in_Depth_2016_S508C.pdf" } ], "title": "Rockwell Automation Stratix and ArmorStratix Switches", "tracking": { "current_release_date": "2018-04-17T00:00:00.000000Z", "generator": { "engine": { "name": "CISA CSAF Generator", "version": "1.0.0" } }, "id": "ICSA-18-107-04", "initial_release_date": "2018-04-17T00:00:00.000000Z", "revision_history": [ { "date": "2018-04-17T00:00:00.000000Z", "legacy_version": "Initial", "number": "1", "summary": "ICSA-18-107-04 Rockwell Automation Stratix and ArmorStratix Switches" } ], "status": "final", "version": "1" } }, "product_tree": { "branches": [ { "branches": [ { "branches": [ { "category": "product_version_range", "name": "\u003c= 15.2(6)E0a", "product": { "name": "Allen-Bradley Stratix 5400 Industrial Ethernet Switches: versions 15.2(6)E0a and earlier;", "product_id": "CSAFPID-0001" } } ], "category": "product_name", "name": "Allen-Bradley Stratix 5400 Industrial Ethernet Switches" }, { "branches": [ { "category": "product_version_range", "name": "\u003c= 15.2(6)E0a", "product": { "name": "Allen-Bradley Stratix 8000 Modular Managed Ethernet Switches: versions 15.2(6)E0a and earlier;", "product_id": "CSAFPID-0002" } } ], "category": "product_name", "name": "Allen-Bradley Stratix 8000 Modular Managed Ethernet Switches" }, { "branches": [ { "category": "product_version_range", "name": "\u003c= 15.2(6)E0a", "product": { "name": "Allen-Bradley Stratix 5410 Industrial Distribution Switches: versions 15.2(6)E0a and earlier;", "product_id": "CSAFPID-0003" } } ], "category": "product_name", "name": "Allen-Bradley Stratix 5410 Industrial Distribution Switches" }, { "branches": [ { "category": "product_version_range", "name": "\u003c= 15.2(6)E0a", "product": { "name": "Allen-Bradley Stratix 5700 Industrial Managed Ethernet Switches: versions 15.2(6)E0a and earlier;", "product_id": "CSAFPID-0004" } } ], "category": "product_name", "name": "Allen-Bradley Stratix 5700 Industrial Managed Ethernet Switches" }, { "branches": [ { "category": "product_version_range", "name": "\u003c= 15.2(6)E0a", "product": { "name": "Allen-Bradley ArmorStratix 5700 Industrial Managed Ethernet Switches for extreme environments: versions 15.2(6)E0a and earlier", "product_id": "CSAFPID-0005" } } ], "category": "product_name", "name": "Allen-Bradley ArmorStratix 5700 Industrial Managed Ethernet Switches for extreme environments" } ], "category": "vendor", "name": "Rockwell Automation" } ] }, "vulnerabilities": [ { "cve": "CVE-2018-0171", "cwe": { "id": "CWE-20", "name": "Improper Input Validation" }, "notes": [ { "category": "summary", "text": "A vulnerability in the Smart Install feature of Cisco IOS Software and Cisco IOS XE Software could allow an unauthenticated remote attacker to trigger a reload of an affected device, resulting in a denial of service (DoS) condition, or to execute arbitrary code on an affected device. The vulnerability is due to improper validation of packet data. An attacker could exploit this vulnerability by sending a crafted Smart Install message to an affected device on TCP port 4786. A successful exploit could allow the attacker to cause a buffer overflow on the affected device.CVE-2018-0171 has been assigned to this vulnerability. A CVSS v3 base score of 9.8 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).", "title": "Vulnerability Summary" } ], "product_status": { "known_affected": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005" ] }, "references": [ { "category": "external", "summary": "web.nvd.nist.gov", "url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2018-0171" }, { "category": "external", "summary": "www.first.org", "url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H" } ], "remediations": [ { "category": "mitigation", "details": "Rockwell Automation recommends users upgrade to FRN 15.2(6)E1 or later. ", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005" ], "url": "http://compatibility.rockwellautomation.com/Pages/MultiProductDownload.aspx?famID=15" }, { "category": "mitigation", "details": "Rockwell Automation has provided knowledge base article number 1073268 on their website ", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005" ], "url": "https://rockwellautomation.custhelp.com/app/answers/detail/a_id/1073268/" }, { "category": "mitigation", "details": "Cisco has released new Snort Rules at https://www.cisco.com/web/software/286271056/117258/sf-rules-2018-03-29-new.htm", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005" ], "url": "https://www.cisco.com/web/software/286271056/117258/sf-rules-2018-03-29-new.html" }, { "category": "mitigation", "details": "CVE-2018-0171 - Snort Rule 46096 and 46097", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005" ] }, { "category": "mitigation", "details": "Cisco adds the following notes for the Smart Install vulnerabilities (CVE-2018-0171 and CVE-2018-0156): Smart Install is turned off by express setup; however, upgraded switches but not re-setup may have it enabled. Disable the Smart Install feature with the no vstack configuration command if it is not needed or once setup is complete. Users who do use the feature\u2014and need to leave it enabled\u2014can use ACLs to block incoming traffic on TCP port 4786.", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005" ] }, { "category": "mitigation", "details": "Help minimize network exposure for all control system devices and/or systems, and confirm that they are not accessible from the Internet.", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005" ] }, { "category": "mitigation", "details": "Locate control system networks and devices behind firewalls, and isolate them from the business network.", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005" ] }, { "category": "mitigation", "details": "When remote access is required, use secure methods, such as Virtual Private Networks (VPNs), recognizing that VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize that VPN is only as secure as the connected devices.", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005" ] } ], "scores": [ { "cvss_v3": { "baseScore": 9.8, "baseSeverity": "CRITICAL", "vectorString": "CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H", "version": "3.0" }, "products": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005" ] } ] }, { "cve": "CVE-2018-0156", "cwe": { "id": "CWE-20", "name": "Improper Input Validation" }, "notes": [ { "category": "summary", "text": "A vulnerability in the Smart Install feature of Cisco IOS Software and Cisco IOS XE Software could allow an unauthenticated remote attacker to trigger a reload of an affected device, resulting in a DoS condition. The vulnerability is due to improper validation of packet data. An attacker could exploit this vulnerability by sending a crafted packet to an affected device on TCP port 4786.CVE-2018-0156 has been assigned to this vulnerability. A CVSS v3 base score of 8.6 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:C/C:N/I:N/A:H).", "title": "Vulnerability Summary" } ], "product_status": { "known_affected": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005" ] }, "references": [ { "category": "external", "summary": "web.nvd.nist.gov", "url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2018-0156" }, { "category": "external", "summary": "www.first.org", "url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:C/C:N/I:N/A:H" } ], "remediations": [ { "category": "mitigation", "details": "Rockwell Automation recommends users upgrade to FRN 15.2(6)E1 or later. ", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005" ], "url": "http://compatibility.rockwellautomation.com/Pages/MultiProductDownload.aspx?famID=15" }, { "category": "mitigation", "details": "Rockwell Automation has provided knowledge base article number 1073268 on their website ", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005" ], "url": "https://rockwellautomation.custhelp.com/app/answers/detail/a_id/1073268/" }, { "category": "mitigation", "details": "Cisco has released new Snort Rules at https://www.cisco.com/web/software/286271056/117258/sf-rules-2018-03-29-new.htm", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005" ], "url": "https://www.cisco.com/web/software/286271056/117258/sf-rules-2018-03-29-new.html" }, { "category": "mitigation", "details": "CVE-2018-0156 - Snort Rule 41725", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005" ] }, { "category": "mitigation", "details": "Cisco adds the following notes for the Smart Install vulnerabilities (CVE-2018-0171 and CVE-2018-0156): Smart Install is turned off by express setup; however, upgraded switches but not re-setup may have it enabled. Disable the Smart Install feature with the no vstack configuration command if it is not needed or once setup is complete. Users who do use the feature\u2014and need to leave it enabled\u2014can use ACLs to block incoming traffic on TCP port 4786.", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005" ] }, { "category": "mitigation", "details": "Help minimize network exposure for all control system devices and/or systems, and confirm that they are not accessible from the Internet.", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005" ] }, { "category": "mitigation", "details": "Locate control system networks and devices behind firewalls, and isolate them from the business network.", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005" ] }, { "category": "mitigation", "details": "When remote access is required, use secure methods, such as Virtual Private Networks (VPNs), recognizing that VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize that VPN is only as secure as the connected devices.", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005" ] } ], "scores": [ { "cvss_v3": { "baseScore": 8.6, "baseSeverity": "HIGH", "vectorString": "CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:C/C:N/I:N/A:H", "version": "3.0" }, "products": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005" ] } ] }, { "cve": "CVE-2018-0174", "cwe": { "id": "CWE-20", "name": "Improper Input Validation" }, "notes": [ { "category": "summary", "text": "A vulnerability in the DHCP option 82 encapsulation functionality of Cisco IOS Software and Cisco IOS XE Software could allow an unauthenticated remote attacker to cause an affected device to reload, resulting in a DoS condition. The vulnerability exists because the affected software performs incomplete input validation of option 82 information that it receives in DHCP Version 4 (DHCPv4) packets from DHCP relay agents. An attacker could exploit this vulnerability by sending a crafted DHCPv4 packet to an affected device. A successful exploit could allow the attacker to cause the affected device to reload, resulting in a DoS condition.CVE-2018-0174 has been assigned to this vulnerability. A CVSS v3 base score of 8.6 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:C/C:N/I:N/A:H).", "title": "Vulnerability Summary" } ], "product_status": { "known_affected": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005" ] }, "references": [ { "category": "external", "summary": "web.nvd.nist.gov", "url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2018-0174" }, { "category": "external", "summary": "www.first.org", "url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:C/C:N/I:N/A:H" } ], "remediations": [ { "category": "mitigation", "details": "Rockwell Automation recommends users upgrade to FRN 15.2(6)E1 or later. ", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005" ], "url": "http://compatibility.rockwellautomation.com/Pages/MultiProductDownload.aspx?famID=15" }, { "category": "mitigation", "details": "Rockwell Automation has provided knowledge base article number 1073268 on their website ", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005" ], "url": "https://rockwellautomation.custhelp.com/app/answers/detail/a_id/1073268/" }, { "category": "mitigation", "details": "Cisco has released new Snort Rules at https://www.cisco.com/web/software/286271056/117258/sf-rules-2018-03-29-new.htm", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005" ], "url": "https://www.cisco.com/web/software/286271056/117258/sf-rules-2018-03-29-new.html" }, { "category": "mitigation", "details": "CVE-2018-0174 - Snort Rule 46120", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005" ] }, { "category": "mitigation", "details": "Help minimize network exposure for all control system devices and/or systems, and confirm that they are not accessible from the Internet.", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005" ] }, { "category": "mitigation", "details": "Locate control system networks and devices behind firewalls, and isolate them from the business network.", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005" ] }, { "category": "mitigation", "details": "When remote access is required, use secure methods, such as Virtual Private Networks (VPNs), recognizing that VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize that VPN is only as secure as the connected devices.", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005" ] } ], "scores": [ { "cvss_v3": { "baseScore": 8.6, "baseSeverity": "HIGH", "vectorString": "CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:C/C:N/I:N/A:H", "version": "3.0" }, "products": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005" ] } ] }, { "cve": "CVE-2018-0172", "cwe": { "id": "CWE-20", "name": "Improper Input Validation" }, "notes": [ { "category": "summary", "text": "A vulnerability in the DHCP option 82 encapsulation functionality of Cisco IOS Software and Cisco IOS XE Software could allow an unauthenticated remote attacker to cause an affected device to reload, resulting in a DoS condition. The vulnerability exists because the affected software performs incomplete input validation of option 82 information that it receives in DHCP Version 4 (DHCPv4) packets from DHCP relay agents. An attacker could exploit this vulnerability by sending a crafted DHCPv4 packet to an affected device. A successful exploit could allow the attacker to cause a heap overflow condition on the affected device, which will cause the device to reload and result in a DoS condition.CVE-2018-0172 has been assigned to this vulnerability. A CVSS v3 base score of 8.6 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:C/C:N/I:N/A:H).", "title": "Vulnerability Summary" } ], "product_status": { "known_affected": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005" ] }, "references": [ { "category": "external", "summary": "web.nvd.nist.gov", "url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2018-0172" }, { "category": "external", "summary": "www.first.org", "url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:C/C:N/I:N/A:H" } ], "remediations": [ { "category": "mitigation", "details": "Rockwell Automation recommends users upgrade to FRN 15.2(6)E1 or later. ", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005" ], "url": "http://compatibility.rockwellautomation.com/Pages/MultiProductDownload.aspx?famID=15" }, { "category": "mitigation", "details": "Rockwell Automation has provided knowledge base article number 1073268 on their website ", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005" ], "url": "https://rockwellautomation.custhelp.com/app/answers/detail/a_id/1073268/" }, { "category": "mitigation", "details": "Cisco has released new Snort Rules at https://www.cisco.com/web/software/286271056/117258/sf-rules-2018-03-29-new.htm", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005" ], "url": "https://www.cisco.com/web/software/286271056/117258/sf-rules-2018-03-29-new.html" }, { "category": "mitigation", "details": "CVE-2018-0172 - Snort Rule 46104", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005" ] }, { "category": "mitigation", "details": "Help minimize network exposure for all control system devices and/or systems, and confirm that they are not accessible from the Internet.", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005" ] }, { "category": "mitigation", "details": "Locate control system networks and devices behind firewalls, and isolate them from the business network.", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005" ] }, { "category": "mitigation", "details": "When remote access is required, use secure methods, such as Virtual Private Networks (VPNs), recognizing that VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize that VPN is only as secure as the connected devices.", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005" ] } ], "scores": [ { "cvss_v3": { "baseScore": 8.6, "baseSeverity": "HIGH", "vectorString": "CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:C/C:N/I:N/A:H", "version": "3.0" }, "products": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005" ] } ] }, { "cve": "CVE-2018-0173", "cwe": { "id": "CWE-20", "name": "Improper Input Validation" }, "notes": [ { "category": "summary", "text": "A vulnerability in the Cisco IOS Software and Cisco IOS XE Software function that restores encapsulated option 82 information in DHCP Version 4 (DHCPv4) packets could allow an unauthenticated remote attacker to cause an affected device to reload, resulting in a DoS condition. The vulnerability exists because the affected software performs incomplete input validation of encapsulated option 82 information that it receives in DHCPOFFER messages from DHCPv4 servers. An attacker could exploit this vulnerability by sending a crafted DHCPv4 packet to an affected device, which the device would then forward to a DHCPv4 server. When the affected software processes the option 82 information that is encapsulated in the response from the server, an error could occur. A successful exploit could allow the attacker to cause the affected device to reload, resulting in a DoS condition.CVE-2018-0173 has been assigned to this vulnerability. A CVSS v3 base score of 8.6 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:C/C:N/I:N/A:H).", "title": "Vulnerability Summary" } ], "product_status": { "known_affected": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005" ] }, "references": [ { "category": "external", "summary": "web.nvd.nist.gov", "url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2018-0173" }, { "category": "external", "summary": "www.first.org", "url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:C/C:N/I:N/A:H" } ], "remediations": [ { "category": "mitigation", "details": "Rockwell Automation recommends users upgrade to FRN 15.2(6)E1 or later. ", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005" ], "url": "http://compatibility.rockwellautomation.com/Pages/MultiProductDownload.aspx?famID=15" }, { "category": "mitigation", "details": "Rockwell Automation has provided knowledge base article number 1073268 on their website ", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005" ], "url": "https://rockwellautomation.custhelp.com/app/answers/detail/a_id/1073268/" }, { "category": "mitigation", "details": "Cisco has released new Snort Rules at https://www.cisco.com/web/software/286271056/117258/sf-rules-2018-03-29-new.htm", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005" ], "url": "https://www.cisco.com/web/software/286271056/117258/sf-rules-2018-03-29-new.html" }, { "category": "mitigation", "details": "CVE-2018-0173 - Snort Rule 46119", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005" ] }, { "category": "mitigation", "details": "Help minimize network exposure for all control system devices and/or systems, and confirm that they are not accessible from the Internet.", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005" ] }, { "category": "mitigation", "details": "Locate control system networks and devices behind firewalls, and isolate them from the business network.", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005" ] }, { "category": "mitigation", "details": "When remote access is required, use secure methods, such as Virtual Private Networks (VPNs), recognizing that VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize that VPN is only as secure as the connected devices.", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005" ] } ], "scores": [ { "cvss_v3": { "baseScore": 8.6, "baseSeverity": "HIGH", "vectorString": "CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:C/C:N/I:N/A:H", "version": "3.0" }, "products": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005" ] } ] }, { "cve": "CVE-2018-0158", "cwe": { "id": "CWE-20", "name": "Improper Input Validation" }, "notes": [ { "category": "summary", "text": "A vulnerability in the Internet Key Exchange Version 2 (IKEv2) module of Cisco IOS Software and Cisco IOS XE Software could allow an unauthenticated remote attacker to cause a memory leak or a reload of an affected device that leads to a DoS condition. The vulnerability is due to incorrect processing of certain IKEv2 packets. An attacker could exploit this vulnerability by sending crafted IKEv2 packets to an affected device to be processed. A successful exploit could cause an affected device to continuously consume memory and eventually reload, resulting in a DoS condition.CVE-2018-0158 has been assigned to this vulnerability. A CVSS v3 base score of 8.6 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:C/C:N/I:N/A:H).", "title": "Vulnerability Summary" } ], "product_status": { "known_affected": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005" ] }, "references": [ { "category": "external", "summary": "web.nvd.nist.gov", "url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2018-0158" }, { "category": "external", "summary": "www.first.org", "url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:C/C:N/I:N/A:H" } ], "remediations": [ { "category": "mitigation", "details": "Rockwell Automation recommends users upgrade to FRN 15.2(6)E1 or later. ", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005" ], "url": "http://compatibility.rockwellautomation.com/Pages/MultiProductDownload.aspx?famID=15" }, { "category": "mitigation", "details": "Rockwell Automation has provided knowledge base article number 1073268 on their website ", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005" ], "url": "https://rockwellautomation.custhelp.com/app/answers/detail/a_id/1073268/" }, { "category": "mitigation", "details": "Cisco has released new Snort Rules at https://www.cisco.com/web/software/286271056/117258/sf-rules-2018-03-29-new.htm", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005" ], "url": "https://www.cisco.com/web/software/286271056/117258/sf-rules-2018-03-29-new.html" }, { "category": "mitigation", "details": "CVE-2018-0158 - Snort Rule 46110", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005" ] }, { "category": "mitigation", "details": "Help minimize network exposure for all control system devices and/or systems, and confirm that they are not accessible from the Internet.", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005" ] }, { "category": "mitigation", "details": "Locate control system networks and devices behind firewalls, and isolate them from the business network.", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005" ] }, { "category": "mitigation", "details": "When remote access is required, use secure methods, such as Virtual Private Networks (VPNs), recognizing that VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize that VPN is only as secure as the connected devices.", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005" ] } ], "scores": [ { "cvss_v3": { "baseScore": 8.6, "baseSeverity": "HIGH", "vectorString": "CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:C/C:N/I:N/A:H", "version": "3.0" }, "products": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005" ] } ] }, { "cve": "CVE-2018-0167", "cwe": { "id": "CWE-119", "name": "Improper Restriction of Operations within the Bounds of a Memory Buffer" }, "notes": [ { "category": "summary", "text": "A buffer overflow vulnerability in the LLDP subsystem of Cisco IOS Software, Cisco IOS XE Software, and Cisco IOS XR Software could allow an adjacent, unauthenticated attacker to cause a DoS condition or execute arbitrary code with elevated privileges.CVE-2018-0167 has been assigned to this vulnerability. A CVSS v3 base score of 8.8 has been calculated; the CVSS vector string is (AV:A/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).", "title": "Vulnerability Summary" } ], "product_status": { "known_affected": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005" ] }, "references": [ { "category": "external", "summary": "web.nvd.nist.gov", "url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2018-0167" }, { "category": "external", "summary": "www.first.org", "url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:A/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H" } ], "remediations": [ { "category": "mitigation", "details": "Rockwell Automation recommends users upgrade to FRN 15.2(6)E1 or later. ", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005" ], "url": "http://compatibility.rockwellautomation.com/Pages/MultiProductDownload.aspx?famID=15" }, { "category": "mitigation", "details": "Rockwell Automation has provided knowledge base article number 1073268 on their website ", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005" ], "url": "https://rockwellautomation.custhelp.com/app/answers/detail/a_id/1073268/" }, { "category": "mitigation", "details": "Cisco has released new Snort Rules at https://www.cisco.com/web/software/286271056/117258/sf-rules-2018-03-29-new.htm", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005" ], "url": "https://www.cisco.com/web/software/286271056/117258/sf-rules-2018-03-29-new.html" }, { "category": "mitigation", "details": "CVE-2018-0167 and CVE-2018-0175: have no specific mitigations in place. See the following Cisco Vulnerability advisory for more details", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005" ], "url": "https://tools.cisco.com/security/center/content/CiscoSecurityAdvisory/cisco-sa-20180328-lldp" }, { "category": "mitigation", "details": "Help minimize network exposure for all control system devices and/or systems, and confirm that they are not accessible from the Internet.", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005" ] }, { "category": "mitigation", "details": "Locate control system networks and devices behind firewalls, and isolate them from the business network.", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005" ] }, { "category": "mitigation", "details": "When remote access is required, use secure methods, such as Virtual Private Networks (VPNs), recognizing that VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize that VPN is only as secure as the connected devices.", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005" ] } ], "scores": [ { "cvss_v3": { "baseScore": 8.8, "baseSeverity": "HIGH", "vectorString": "CVSS:3.0/AV:A/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H", "version": "3.0" }, "products": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005" ] } ] }, { "cve": "CVE-2018-0175", "cwe": { "id": "CWE-134", "name": "Use of Externally-Controlled Format String" }, "notes": [ { "category": "summary", "text": "A format string vulnerability in the LLDP subsystem of Cisco IOS Software and Cisco IOS XE Software could allow an adjacent, unauthenticated attacker to cause a DoS condition or execute arbitrary code with elevated privileges.CVE-2018-0175 has been assigned to this vulnerability. A CVSS v3 base score of 8.8 has been calculated; the CVSS vector string is (AV:A/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).", "title": "Vulnerability Summary" } ], "product_status": { "known_affected": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005" ] }, "references": [ { "category": "external", "summary": "web.nvd.nist.gov", "url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2018-0175" }, { "category": "external", "summary": "www.first.org", "url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:A/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H" } ], "remediations": [ { "category": "mitigation", "details": "Rockwell Automation recommends users upgrade to FRN 15.2(6)E1 or later. ", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005" ], "url": "http://compatibility.rockwellautomation.com/Pages/MultiProductDownload.aspx?famID=15" }, { "category": "mitigation", "details": "Rockwell Automation has provided knowledge base article number 1073268 on their website ", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005" ], "url": "https://rockwellautomation.custhelp.com/app/answers/detail/a_id/1073268/" }, { "category": "mitigation", "details": "Cisco has released new Snort Rules at https://www.cisco.com/web/software/286271056/117258/sf-rules-2018-03-29-new.htm", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005" ], "url": "https://www.cisco.com/web/software/286271056/117258/sf-rules-2018-03-29-new.html" }, { "category": "mitigation", "details": "CVE-2018-0167 and CVE-2018-0175: have no specific mitigations in place. See the following Cisco Vulnerability advisory for more details", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005" ], "url": "https://tools.cisco.com/security/center/content/CiscoSecurityAdvisory/cisco-sa-20180328-lldp" }, { "category": "mitigation", "details": "Help minimize network exposure for all control system devices and/or systems, and confirm that they are not accessible from the Internet.", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005" ] }, { "category": "mitigation", "details": "Locate control system networks and devices behind firewalls, and isolate them from the business network.", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005" ] }, { "category": "mitigation", "details": "When remote access is required, use secure methods, such as Virtual Private Networks (VPNs), recognizing that VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize that VPN is only as secure as the connected devices.", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005" ] } ], "scores": [ { "cvss_v3": { "baseScore": 8.8, "baseSeverity": "HIGH", "vectorString": "CVSS:3.0/AV:A/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H", "version": "3.0" }, "products": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005" ] } ] } ] }
Loading...
Loading...
Sightings
Author | Source | Type | Date |
---|
Nomenclature
- Seen: The vulnerability was mentioned, discussed, or seen somewhere by the user.
- Confirmed: The vulnerability is confirmed from an analyst perspective.
- Exploited: This vulnerability was exploited and seen by the user reporting the sighting.
- Patched: This vulnerability was successfully patched by the user reporting the sighting.
- Not exploited: This vulnerability was not exploited or seen by the user reporting the sighting.
- Not confirmed: The user expresses doubt about the veracity of the vulnerability.
- Not patched: This vulnerability was not successfully patched by the user reporting the sighting.