ICSA-20-154-03

Vulnerability from csaf_cisa - Published: 2020-06-02 00:00 - Updated: 2020-06-02 00:00
Summary
ABB Multiple System 800xA Products

Notes

CISA Disclaimer
This CSAF advisory was extracted from unstructured data and may contain inaccuracies. If you notice any errors, please reach out to the designated contact at CISA CSAF: central@cisa.dhs.gov
Legal Notice
All information products included in https://us-cert.cisa.gov/ics are provided "as is" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see https://us-cert.cisa.gov/tlp/.
Risk evaluation
Successful exploitation of these vulnerabilities could allow an attacker to make the system node inaccessible or tamper with runtime data in the system.
Critical infrastructure sectors
Chemical, Critical Manufacturing, Dams, Energy, Food and Agriculture, Water and Wastewater
Countries/areas deployed
Worldwide
Company headquarters location
Switzerland
Recommended Practices
CISA recommends users take defensive measures to minimize the risk of exploitation of these vulnerabilities. Specifically, users should:
Recommended Practices
CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures. CISA also provides a section for control systems security recommended practices on the ICS webpage onus-cert.gov. Several recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.
Recommended Practices
Additional mitigation guidance and recommended practices are publicly available on the ICS webpage on us-cert.gov in the Technical Information Paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies. Organizations observing any suspected malicious activity should follow their established internal procedures and report their findings to CISA for tracking and correlation against other incidents.

{
  "document": {
    "acknowledgments": [
      {
        "names": [
          "William Knowles"
        ],
        "organization": "Applied Risk",
        "summary": "reporting these vulnerabilities to ABB"
      }
    ],
    "category": "csaf_security_advisory",
    "csaf_version": "2.0",
    "distribution": {
      "text": "Disclosure is not limited",
      "tlp": {
        "label": "WHITE",
        "url": "https://us-cert.cisa.gov/tlp/"
      }
    },
    "lang": "en-US",
    "notes": [
      {
        "category": "general",
        "text": "This CSAF advisory was extracted from unstructured data and may contain inaccuracies. If you notice any errors, please reach out to the designated contact at CISA CSAF: central@cisa.dhs.gov",
        "title": "CISA Disclaimer"
      },
      {
        "category": "legal_disclaimer",
        "text": "All information products included in https://us-cert.cisa.gov/ics are provided \"as is\" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see https://us-cert.cisa.gov/tlp/.",
        "title": "Legal Notice"
      },
      {
        "category": "summary",
        "text": "Successful exploitation of these vulnerabilities could allow an attacker to make the system node inaccessible or tamper with runtime data in the system.",
        "title": "Risk evaluation"
      },
      {
        "category": "other",
        "text": "Chemical, Critical Manufacturing, Dams, Energy, Food and Agriculture, Water and Wastewater",
        "title": "Critical infrastructure sectors"
      },
      {
        "category": "other",
        "text": "Worldwide",
        "title": "Countries/areas deployed"
      },
      {
        "category": "other",
        "text": "Switzerland",
        "title": "Company headquarters location"
      },
      {
        "category": "general",
        "text": "CISA recommends users take defensive measures to minimize the risk of exploitation of these vulnerabilities. Specifically, users should:",
        "title": "Recommended Practices"
      },
      {
        "category": "general",
        "text": "CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.\nCISA also provides a section for control systems security recommended practices on the ICS webpage onus-cert.gov. Several recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.",
        "title": "Recommended Practices"
      },
      {
        "category": "general",
        "text": "Additional mitigation guidance and recommended practices are publicly available on the ICS webpage on us-cert.gov in the Technical Information Paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.\nOrganizations observing any suspected malicious activity should follow their established internal procedures and report their findings to CISA for tracking and correlation against other incidents.",
        "title": "Recommended Practices"
      }
    ],
    "publisher": {
      "category": "coordinator",
      "contact_details": "Email: CISAservicedesk@cisa.dhs.gov;\n Toll Free: 1-888-282-0870",
      "name": "CISA",
      "namespace": "https://www.cisa.gov/"
    },
    "references": [
      {
        "category": "self",
        "summary": "ICS Advisory ICSA-20-154-03 JSON",
        "url": "https://raw.githubusercontent.com/cisagov/CSAF/develop/csaf_files/OT/white/2020/icsa-20-154-03.json"
      },
      {
        "category": "self",
        "summary": "ICS Advisory ICSA-20-154-03 Web Version",
        "url": "https://www.cisa.gov/news-events/ics-advisories/icsa-20-154-03"
      },
      {
        "category": "external",
        "summary": "Recommended Practices",
        "url": "https://www.cisa.gov/news-events/ics-advisories/icsa-20-154-03"
      },
      {
        "category": "external",
        "summary": "Recommended Practices",
        "url": "https://www.us-cert.gov/sites/default/files/recommended_practices/NCCIC_ICS-CERT_Defense_in_Depth_2016_S508C.pdf"
      },
      {
        "category": "external",
        "summary": "Recommended Practices",
        "url": "https://www.us-cert.gov/ics/tips/ICS-TIP-12-146-01B"
      }
    ],
    "title": "ABB Multiple System 800xA Products",
    "tracking": {
      "current_release_date": "2020-06-02T00:00:00.000000Z",
      "generator": {
        "engine": {
          "name": "CISA CSAF Generator",
          "version": "1.0.0"
        }
      },
      "id": "ICSA-20-154-03",
      "initial_release_date": "2020-06-02T00:00:00.000000Z",
      "revision_history": [
        {
          "date": "2020-06-02T00:00:00.000000Z",
          "legacy_version": "Initial",
          "number": "1",
          "summary": "ICSA-20-154-03 ABB Multiple System 800xA Products"
        }
      ],
      "status": "final",
      "version": "1"
    }
  },
  "product_tree": {
    "branches": [
      {
        "branches": [
          {
            "branches": [
              {
                "category": "product_version",
                "name": "vers:all/*",
                "product": {
                  "name": "800xA for DCI: all versions",
                  "product_id": "CSAFPID-0001"
                }
              }
            ],
            "category": "product_name",
            "name": "800xA for DCI"
          },
          {
            "branches": [
              {
                "category": "product_version",
                "name": "vers:all/*",
                "product": {
                  "name": "800xA Batch Management: all versions",
                  "product_id": "CSAFPID-0002"
                }
              }
            ],
            "category": "product_name",
            "name": "800xA Batch Management"
          },
          {
            "branches": [
              {
                "category": "product_version",
                "name": "vers:all/*",
                "product": {
                  "name": "800xA Information Management: all versions",
                  "product_id": "CSAFPID-0003"
                }
              }
            ],
            "category": "product_name",
            "name": "800xA Information Management"
          },
          {
            "branches": [
              {
                "category": "product_version",
                "name": "vers:all/*",
                "product": {
                  "name": "MMS Server for AC 800M: all versions",
                  "product_id": "CSAFPID-0004"
                }
              }
            ],
            "category": "product_name",
            "name": "MMS Server for AC 800M"
          },
          {
            "branches": [
              {
                "category": "product_version",
                "name": "vers:all/*",
                "product": {
                  "name": "Base Software for SoftControl: all versions",
                  "product_id": "CSAFPID-0005"
                }
              }
            ],
            "category": "product_name",
            "name": "Base Software for SoftControl"
          },
          {
            "branches": [
              {
                "category": "product_version",
                "name": "vers:all/*",
                "product": {
                  "name": "OPC Server for AC 800M: all versions",
                  "product_id": "CSAFPID-0006"
                }
              }
            ],
            "category": "product_name",
            "name": "OPC Server for AC 800M"
          },
          {
            "branches": [
              {
                "category": "product_version",
                "name": "vers:all/*",
                "product": {
                  "name": "800xA RNRP: all versions",
                  "product_id": "CSAFPID-0007"
                }
              }
            ],
            "category": "product_name",
            "name": "800xA RNRP"
          },
          {
            "branches": [
              {
                "category": "product_version",
                "name": "vers:all/*",
                "product": {
                  "name": "800xA for MOD 300: all versions",
                  "product_id": "CSAFPID-0008"
                }
              }
            ],
            "category": "product_name",
            "name": "800xA for MOD 300"
          },
          {
            "branches": [
              {
                "category": "product_version",
                "name": "vers:all/*",
                "product": {
                  "name": "ABB System 800xA Base: all versions",
                  "product_id": "CSAFPID-0009"
                }
              }
            ],
            "category": "product_name",
            "name": "ABB System 800xA Base"
          }
        ],
        "category": "vendor",
        "name": "ABB"
      }
    ]
  },
  "vulnerabilities": [
    {
      "cve": "CVE-2020-8478",
      "cwe": {
        "id": "CWE-276",
        "name": "Incorrect Default Permissions"
      },
      "notes": [
        {
          "category": "summary",
          "text": "The vulnerability is caused by weak access control settings for objects used to exchange information between System 800xA processes on the same machine. An attacker could exploit this vulnerability by injecting garbage data or specially crafted data. An attacker who successfully exploits this vulnerability would be able to affect the online view of runtime data shown in Control Builder.CVE-2020-8478 has been assigned to this vulnerability. A CVSS v3 base score of 5.3 has been calculated; the CVSS vector string is (AV:L/AC:L/PR:L/UI:N/S:U/C:L/I:L/A:L).",
          "title": "Vulnerability Summary"
        }
      ],
      "product_status": {
        "known_affected": [
          "CSAFPID-0001",
          "CSAFPID-0002",
          "CSAFPID-0003",
          "CSAFPID-0004",
          "CSAFPID-0005",
          "CSAFPID-0006",
          "CSAFPID-0007",
          "CSAFPID-0008",
          "CSAFPID-0009"
        ]
      },
      "references": [
        {
          "category": "external",
          "summary": "web.nvd.nist.gov",
          "url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2020-8478"
        },
        {
          "category": "external",
          "summary": "www.first.org",
          "url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:L/AC:L/PR:L/UI:N/S:U/C:L/I:L/A:L"
        }
      ],
      "remediations": [
        {
          "category": "mitigation",
          "details": "ABB recommends changing any user account passwords suspected to be known by an unauthorized person. ABB recommends users disable interactive logon (both local and remote) for the service account.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005",
            "CSAFPID-0006",
            "CSAFPID-0007",
            "CSAFPID-0008",
            "CSAFPID-0009"
          ]
        },
        {
          "category": "mitigation",
          "details": "Please note these vulnerabilities can only be exploited by authenticated users. ABB recommendeds users ensure only authorized persons have access to user accounts in System 800xA.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005",
            "CSAFPID-0006",
            "CSAFPID-0007",
            "CSAFPID-0008",
            "CSAFPID-0009"
          ]
        },
        {
          "category": "mitigation",
          "details": "ABB plans to correct these vulnerabilities in future product versions.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005",
            "CSAFPID-0006",
            "CSAFPID-0007",
            "CSAFPID-0008",
            "CSAFPID-0009"
          ]
        },
        {
          "category": "mitigation",
          "details": "For more information, please refer to ABB\u0027s Cybersecurity Advisory.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005",
            "CSAFPID-0006",
            "CSAFPID-0007",
            "CSAFPID-0008",
            "CSAFPID-0009"
          ],
          "url": "https://search.abb.com/library/Download.aspx?DocumentID=2PAA121236\u0026LanguageCode=en\u0026DocumentPartId=\u0026Action=Launch"
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "baseScore": 5.3,
            "baseSeverity": "MEDIUM",
            "vectorString": "CVSS:3.0/AV:L/AC:L/PR:L/UI:N/S:U/C:L/I:L/A:L",
            "version": "3.0"
          },
          "products": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005",
            "CSAFPID-0006",
            "CSAFPID-0007",
            "CSAFPID-0008",
            "CSAFPID-0009"
          ]
        }
      ]
    },
    {
      "cve": "CVE-2020-8484",
      "cwe": {
        "id": "CWE-276",
        "name": "Incorrect Default Permissions"
      },
      "notes": [
        {
          "category": "summary",
          "text": "The vulnerability is caused by weak access control settings for objects used to exchange information between System 800xA processes on the same machine. An attacker could exploit this vulnerability by injecting garbage data or specially crafted data. An attacker who successfully exploits this vulnerability would be able to manipulate the data to allow reads and writes to the controllers or cause the 800xA for DCI processes to crash.CVE-2020-8484 has been assigned to this vulnerability. A CVSS v3 base score of 7.8 has been calculated; the CVSS vector string is (AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H).",
          "title": "Vulnerability Summary"
        }
      ],
      "product_status": {
        "known_affected": [
          "CSAFPID-0001",
          "CSAFPID-0002",
          "CSAFPID-0003",
          "CSAFPID-0004",
          "CSAFPID-0005",
          "CSAFPID-0006",
          "CSAFPID-0007",
          "CSAFPID-0008",
          "CSAFPID-0009"
        ]
      },
      "references": [
        {
          "category": "external",
          "summary": "web.nvd.nist.gov",
          "url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2020-8484"
        },
        {
          "category": "external",
          "summary": "www.first.org",
          "url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H"
        }
      ],
      "remediations": [
        {
          "category": "mitigation",
          "details": "ABB recommends changing any user account passwords suspected to be known by an unauthorized person. ABB recommends users disable interactive logon (both local and remote) for the service account.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005",
            "CSAFPID-0006",
            "CSAFPID-0007",
            "CSAFPID-0008",
            "CSAFPID-0009"
          ]
        },
        {
          "category": "mitigation",
          "details": "Please note these vulnerabilities can only be exploited by authenticated users. ABB recommendeds users ensure only authorized persons have access to user accounts in System 800xA.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005",
            "CSAFPID-0006",
            "CSAFPID-0007",
            "CSAFPID-0008",
            "CSAFPID-0009"
          ]
        },
        {
          "category": "mitigation",
          "details": "ABB plans to correct these vulnerabilities in future product versions.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005",
            "CSAFPID-0006",
            "CSAFPID-0007",
            "CSAFPID-0008",
            "CSAFPID-0009"
          ]
        },
        {
          "category": "mitigation",
          "details": "For more information, please refer to ABB\u0027s Cybersecurity Advisory.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005",
            "CSAFPID-0006",
            "CSAFPID-0007",
            "CSAFPID-0008",
            "CSAFPID-0009"
          ],
          "url": "https://search.abb.com/library/Download.aspx?DocumentID=2PAA121236\u0026LanguageCode=en\u0026DocumentPartId=\u0026Action=Launch"
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "baseScore": 7.8,
            "baseSeverity": "HIGH",
            "vectorString": "CVSS:3.0/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H",
            "version": "3.0"
          },
          "products": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005",
            "CSAFPID-0006",
            "CSAFPID-0007",
            "CSAFPID-0008",
            "CSAFPID-0009"
          ]
        }
      ]
    },
    {
      "cve": "CVE-2020-8485",
      "cwe": {
        "id": "CWE-276",
        "name": "Incorrect Default Permissions"
      },
      "notes": [
        {
          "category": "summary",
          "text": "The vulnerability is caused by weak access control settings for objects used to exchange information between System 800xA processes on the same machine. An attacker could exploit this vulnerability by injecting garbage data or specially crafted data. An attacker who successfully exploits this vulnerability would be able to manipulate the data to allow reads and writes to the controllers or cause the 800xA for MOD 300 processes to crash.CVE-2020-8485 has been assigned to this vulnerability. A CVSS v3 base score of 7.8 has been calculated; the CVSS vector string is (AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H).",
          "title": "Vulnerability Summary"
        }
      ],
      "product_status": {
        "known_affected": [
          "CSAFPID-0001",
          "CSAFPID-0002",
          "CSAFPID-0003",
          "CSAFPID-0004",
          "CSAFPID-0005",
          "CSAFPID-0006",
          "CSAFPID-0007",
          "CSAFPID-0008",
          "CSAFPID-0009"
        ]
      },
      "references": [
        {
          "category": "external",
          "summary": "web.nvd.nist.gov",
          "url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2020-8485"
        },
        {
          "category": "external",
          "summary": "www.first.org",
          "url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H"
        }
      ],
      "remediations": [
        {
          "category": "mitigation",
          "details": "ABB recommends changing any user account passwords suspected to be known by an unauthorized person. ABB recommends users disable interactive logon (both local and remote) for the service account.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005",
            "CSAFPID-0006",
            "CSAFPID-0007",
            "CSAFPID-0008",
            "CSAFPID-0009"
          ]
        },
        {
          "category": "mitigation",
          "details": "Please note these vulnerabilities can only be exploited by authenticated users. ABB recommendeds users ensure only authorized persons have access to user accounts in System 800xA.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005",
            "CSAFPID-0006",
            "CSAFPID-0007",
            "CSAFPID-0008",
            "CSAFPID-0009"
          ]
        },
        {
          "category": "mitigation",
          "details": "ABB plans to correct these vulnerabilities in future product versions.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005",
            "CSAFPID-0006",
            "CSAFPID-0007",
            "CSAFPID-0008",
            "CSAFPID-0009"
          ]
        },
        {
          "category": "mitigation",
          "details": "For more information, please refer to ABB\u0027s Cybersecurity Advisory.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005",
            "CSAFPID-0006",
            "CSAFPID-0007",
            "CSAFPID-0008",
            "CSAFPID-0009"
          ],
          "url": "https://search.abb.com/library/Download.aspx?DocumentID=2PAA121236\u0026LanguageCode=en\u0026DocumentPartId=\u0026Action=Launch"
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "baseScore": 7.8,
            "baseSeverity": "HIGH",
            "vectorString": "CVSS:3.0/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H",
            "version": "3.0"
          },
          "products": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005",
            "CSAFPID-0006",
            "CSAFPID-0007",
            "CSAFPID-0008",
            "CSAFPID-0009"
          ]
        }
      ]
    },
    {
      "cve": "CVE-2020-8486",
      "cwe": {
        "id": "CWE-276",
        "name": "Incorrect Default Permissions"
      },
      "notes": [
        {
          "category": "summary",
          "text": "The vulnerability is caused by weak access control settings for objects used to exchange information between System 800xA processes on the same machine. An attacker could exploit this vulnerability by injecting garbage data or specially crafted data. An attacker who successfully exploits this vulnerability concerning 800xA RNRP would be able to affect node redundancy handling. The attacked node could perceive other nodes to be unavailable, which will disrupt the communication. When running the system in simulation mode, the simulated clock could be affected.CVE-2020-8486 has been assigned to this vulnerability. A CVSS v3 base score of 6.6 has been calculated; the CVSS vector string is (AV:L/AC:L/PR:L/UI:N/S:U/C:L/I:L/A:H).",
          "title": "Vulnerability Summary"
        }
      ],
      "product_status": {
        "known_affected": [
          "CSAFPID-0001",
          "CSAFPID-0002",
          "CSAFPID-0003",
          "CSAFPID-0004",
          "CSAFPID-0005",
          "CSAFPID-0006",
          "CSAFPID-0007",
          "CSAFPID-0008",
          "CSAFPID-0009"
        ]
      },
      "references": [
        {
          "category": "external",
          "summary": "web.nvd.nist.gov",
          "url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2020-8486"
        },
        {
          "category": "external",
          "summary": "www.first.org",
          "url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:L/AC:L/PR:L/UI:N/S:U/C:L/I:L/A:H"
        }
      ],
      "remediations": [
        {
          "category": "mitigation",
          "details": "ABB recommends changing any user account passwords suspected to be known by an unauthorized person. ABB recommends users disable interactive logon (both local and remote) for the service account.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005",
            "CSAFPID-0006",
            "CSAFPID-0007",
            "CSAFPID-0008",
            "CSAFPID-0009"
          ]
        },
        {
          "category": "mitigation",
          "details": "Please note these vulnerabilities can only be exploited by authenticated users. ABB recommendeds users ensure only authorized persons have access to user accounts in System 800xA.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005",
            "CSAFPID-0006",
            "CSAFPID-0007",
            "CSAFPID-0008",
            "CSAFPID-0009"
          ]
        },
        {
          "category": "mitigation",
          "details": "ABB plans to correct these vulnerabilities in future product versions.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005",
            "CSAFPID-0006",
            "CSAFPID-0007",
            "CSAFPID-0008",
            "CSAFPID-0009"
          ]
        },
        {
          "category": "mitigation",
          "details": "For more information, please refer to ABB\u0027s Cybersecurity Advisory.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005",
            "CSAFPID-0006",
            "CSAFPID-0007",
            "CSAFPID-0008",
            "CSAFPID-0009"
          ],
          "url": "https://search.abb.com/library/Download.aspx?DocumentID=2PAA121236\u0026LanguageCode=en\u0026DocumentPartId=\u0026Action=Launch"
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "baseScore": 6.6,
            "baseSeverity": "MEDIUM",
            "vectorString": "CVSS:3.0/AV:L/AC:L/PR:L/UI:N/S:U/C:L/I:L/A:H",
            "version": "3.0"
          },
          "products": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005",
            "CSAFPID-0006",
            "CSAFPID-0007",
            "CSAFPID-0008",
            "CSAFPID-0009"
          ]
        }
      ]
    },
    {
      "cve": "CVE-2020-8487",
      "cwe": {
        "id": "CWE-276",
        "name": "Incorrect Default Permissions"
      },
      "notes": [
        {
          "category": "summary",
          "text": "The vulnerability is caused by weak access control settings for objects used to exchange information between System 800xA processes on the same machine. An attacker could exploit this vulnerability by injecting garbage data or specially crafted data. An attacker who successfully exploits this vulnerability concerning System 800xA Base would be able to affect node redundancy handling. The attacked node could perceive other nodes to be unavailable, which will disrupt the communication. When running the system in simulation mode, the simulated clock could be affected.CVE-2020-8487 has been assigned to this vulnerability. A CVSS v3 base score of 6.6 has been calculated; the CVSS vector string is (AV:L/AC:L/PR:L/UI:N/S:U/C:L/I:L/A:H).",
          "title": "Vulnerability Summary"
        }
      ],
      "product_status": {
        "known_affected": [
          "CSAFPID-0001",
          "CSAFPID-0002",
          "CSAFPID-0003",
          "CSAFPID-0004",
          "CSAFPID-0005",
          "CSAFPID-0006",
          "CSAFPID-0007",
          "CSAFPID-0008",
          "CSAFPID-0009"
        ]
      },
      "references": [
        {
          "category": "external",
          "summary": "web.nvd.nist.gov",
          "url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2020-8487"
        },
        {
          "category": "external",
          "summary": "www.first.org",
          "url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:L/AC:L/PR:L/UI:N/S:U/C:L/I:L/A:H"
        }
      ],
      "remediations": [
        {
          "category": "mitigation",
          "details": "ABB recommends changing any user account passwords suspected to be known by an unauthorized person. ABB recommends users disable interactive logon (both local and remote) for the service account.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005",
            "CSAFPID-0006",
            "CSAFPID-0007",
            "CSAFPID-0008",
            "CSAFPID-0009"
          ]
        },
        {
          "category": "mitigation",
          "details": "Please note these vulnerabilities can only be exploited by authenticated users. ABB recommendeds users ensure only authorized persons have access to user accounts in System 800xA.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005",
            "CSAFPID-0006",
            "CSAFPID-0007",
            "CSAFPID-0008",
            "CSAFPID-0009"
          ]
        },
        {
          "category": "mitigation",
          "details": "ABB plans to correct these vulnerabilities in future product versions.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005",
            "CSAFPID-0006",
            "CSAFPID-0007",
            "CSAFPID-0008",
            "CSAFPID-0009"
          ]
        },
        {
          "category": "mitigation",
          "details": "For more information, please refer to ABB\u0027s Cybersecurity Advisory.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005",
            "CSAFPID-0006",
            "CSAFPID-0007",
            "CSAFPID-0008",
            "CSAFPID-0009"
          ],
          "url": "https://search.abb.com/library/Download.aspx?DocumentID=2PAA121236\u0026LanguageCode=en\u0026DocumentPartId=\u0026Action=Launch"
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "baseScore": 6.6,
            "baseSeverity": "MEDIUM",
            "vectorString": "CVSS:3.0/AV:L/AC:L/PR:L/UI:N/S:U/C:L/I:L/A:H",
            "version": "3.0"
          },
          "products": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005",
            "CSAFPID-0006",
            "CSAFPID-0007",
            "CSAFPID-0008",
            "CSAFPID-0009"
          ]
        }
      ]
    },
    {
      "cve": "CVE-2020-8488",
      "cwe": {
        "id": "CWE-276",
        "name": "Incorrect Default Permissions"
      },
      "notes": [
        {
          "category": "summary",
          "text": "The vulnerability is caused by weak access control settings for objects used to exchange information between System 800xA processes on the same machine. An attacker could exploit this vulnerability by injecting garbage data or specially crafted data. An attacker who successfully exploits this vulnerability would be able to affect how the UI is updated during batch execution. The compare and printing functionality in batch could also be affected.CVE-2020-8488 has been assigned to this vulnerability. A CVSS v3 base score of 7.8 has been calculated; the CVSS vector string is (AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H).",
          "title": "Vulnerability Summary"
        }
      ],
      "product_status": {
        "known_affected": [
          "CSAFPID-0001",
          "CSAFPID-0002",
          "CSAFPID-0003",
          "CSAFPID-0004",
          "CSAFPID-0005",
          "CSAFPID-0006",
          "CSAFPID-0007",
          "CSAFPID-0008",
          "CSAFPID-0009"
        ]
      },
      "references": [
        {
          "category": "external",
          "summary": "web.nvd.nist.gov",
          "url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2020-8488"
        },
        {
          "category": "external",
          "summary": "www.first.org",
          "url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H"
        }
      ],
      "remediations": [
        {
          "category": "mitigation",
          "details": "ABB recommends changing any user account passwords suspected to be known by an unauthorized person. ABB recommends users disable interactive logon (both local and remote) for the service account.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005",
            "CSAFPID-0006",
            "CSAFPID-0007",
            "CSAFPID-0008",
            "CSAFPID-0009"
          ]
        },
        {
          "category": "mitigation",
          "details": "Please note these vulnerabilities can only be exploited by authenticated users. ABB recommendeds users ensure only authorized persons have access to user accounts in System 800xA.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005",
            "CSAFPID-0006",
            "CSAFPID-0007",
            "CSAFPID-0008",
            "CSAFPID-0009"
          ]
        },
        {
          "category": "mitigation",
          "details": "ABB plans to correct these vulnerabilities in future product versions.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005",
            "CSAFPID-0006",
            "CSAFPID-0007",
            "CSAFPID-0008",
            "CSAFPID-0009"
          ]
        },
        {
          "category": "mitigation",
          "details": "For more information, please refer to ABB\u0027s Cybersecurity Advisory.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005",
            "CSAFPID-0006",
            "CSAFPID-0007",
            "CSAFPID-0008",
            "CSAFPID-0009"
          ],
          "url": "https://search.abb.com/library/Download.aspx?DocumentID=2PAA121236\u0026LanguageCode=en\u0026DocumentPartId=\u0026Action=Launch"
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "baseScore": 7.8,
            "baseSeverity": "HIGH",
            "vectorString": "CVSS:3.0/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H",
            "version": "3.0"
          },
          "products": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005",
            "CSAFPID-0006",
            "CSAFPID-0007",
            "CSAFPID-0008",
            "CSAFPID-0009"
          ]
        }
      ]
    },
    {
      "cve": "CVE-2020-8489",
      "cwe": {
        "id": "CWE-276",
        "name": "Incorrect Default Permissions"
      },
      "notes": [
        {
          "category": "summary",
          "text": "The vulnerability is caused by weak access control settings for objects used to exchange information between System 800xA processes on the same machine. An attacker could exploit this vulnerability by injecting garbage data or specially crafted data. An attacker who successfully exploits this vulnerability would be able to affect the runtime values that are to be stored in the archive. Also, this can make information management history services unavailable to the clients.CVE-2020-8489 has been assigned to this vulnerability. A CVSS v3 base score of 7.8 has been calculated; the CVSS vector string is (AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H).",
          "title": "Vulnerability Summary"
        }
      ],
      "product_status": {
        "known_affected": [
          "CSAFPID-0001",
          "CSAFPID-0002",
          "CSAFPID-0003",
          "CSAFPID-0004",
          "CSAFPID-0005",
          "CSAFPID-0006",
          "CSAFPID-0007",
          "CSAFPID-0008",
          "CSAFPID-0009"
        ]
      },
      "references": [
        {
          "category": "external",
          "summary": "web.nvd.nist.gov",
          "url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2020-8489"
        },
        {
          "category": "external",
          "summary": "www.first.org",
          "url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H"
        }
      ],
      "remediations": [
        {
          "category": "mitigation",
          "details": "ABB recommends changing any user account passwords suspected to be known by an unauthorized person. ABB recommends users disable interactive logon (both local and remote) for the service account.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005",
            "CSAFPID-0006",
            "CSAFPID-0007",
            "CSAFPID-0008",
            "CSAFPID-0009"
          ]
        },
        {
          "category": "mitigation",
          "details": "Please note these vulnerabilities can only be exploited by authenticated users. ABB recommendeds users ensure only authorized persons have access to user accounts in System 800xA.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005",
            "CSAFPID-0006",
            "CSAFPID-0007",
            "CSAFPID-0008",
            "CSAFPID-0009"
          ]
        },
        {
          "category": "mitigation",
          "details": "ABB plans to correct these vulnerabilities in future product versions.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005",
            "CSAFPID-0006",
            "CSAFPID-0007",
            "CSAFPID-0008",
            "CSAFPID-0009"
          ]
        },
        {
          "category": "mitigation",
          "details": "For more information, please refer to ABB\u0027s Cybersecurity Advisory.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005",
            "CSAFPID-0006",
            "CSAFPID-0007",
            "CSAFPID-0008",
            "CSAFPID-0009"
          ],
          "url": "https://search.abb.com/library/Download.aspx?DocumentID=2PAA121236\u0026LanguageCode=en\u0026DocumentPartId=\u0026Action=Launch"
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "baseScore": 7.8,
            "baseSeverity": "HIGH",
            "vectorString": "CVSS:3.0/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H",
            "version": "3.0"
          },
          "products": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005",
            "CSAFPID-0006",
            "CSAFPID-0007",
            "CSAFPID-0008",
            "CSAFPID-0009"
          ]
        }
      ]
    }
  ]
}


Log in or create an account to share your comment.




Tags
Taxonomy of the tags.


Loading…

Loading…

Loading…

Sightings

Author Source Type Date

Nomenclature

  • Seen: The vulnerability was mentioned, discussed, or observed by the user.
  • Confirmed: The vulnerability has been validated from an analyst's perspective.
  • Published Proof of Concept: A public proof of concept is available for this vulnerability.
  • Exploited: The vulnerability was observed as exploited by the user who reported the sighting.
  • Patched: The vulnerability was observed as successfully patched by the user who reported the sighting.
  • Not exploited: The vulnerability was not observed as exploited by the user who reported the sighting.
  • Not confirmed: The user expressed doubt about the validity of the vulnerability.
  • Not patched: The vulnerability was not observed as successfully patched by the user who reported the sighting.


Loading…

Detection rules are retrieved from Rulezet.

Loading…

Loading…