ICSA-22-165-01

Vulnerability from csaf_cisa - Published: 2022-06-14 00:00 - Updated: 2022-06-14 00:00
Summary
Johnson Controls Metasys ADS ADX OAS Servers

Notes

CISA Disclaimer
This CSAF advisory was extracted from unstructured data and may contain inaccuracies. If you notice any errors, please reach out to the designated contact at CISA CSAF: central@cisa.dhs.gov
Legal Notice
All information products included in https://us-cert.cisa.gov/ics are provided "as is" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see https://us-cert.cisa.gov/tlp/.
Risk evaluation
Successful exploitation of these vulnerabilities could allow unauthorized users to compromise passwords and inject malicious code into web interfaces.
Critical infrastructure sectors
Critical Manufacturing
Countries/areas deployed
Worldwide
Company headquarters location
Ireland
Recommended Practices
Johnson Controls also recommends following CISA guidelines for minimizing the risks associated with automation systems, detailed below.
Recommended Practices
CISA recommends users take defensive measures to minimize the risk of exploitation of these vulnerabilities. Specifically, users should:
Recommended Practices
CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures. CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/icsSeveral recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.
Recommended Practices
Additional mitigation guidance and recommended practices are publicly available on the ICS webpage on cisa.gov/icsin the Technical Information Paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies. Organizations observing any suspected malicious activity should follow their established internal procedures and report their findings to CISA for tracking and correlation against other incidents.
Exploitability
No known public exploits specifically target these vulnerabilities.

{
  "document": {
    "acknowledgments": [
      {
        "organization": "Johnson Controls, Inc",
        "summary": "reporting these vulnerabilities to CISA"
      }
    ],
    "category": "csaf_security_advisory",
    "csaf_version": "2.0",
    "distribution": {
      "text": "Disclosure is not limited",
      "tlp": {
        "label": "WHITE",
        "url": "https://us-cert.cisa.gov/tlp/"
      }
    },
    "lang": "en-US",
    "notes": [
      {
        "category": "general",
        "text": "This CSAF advisory was extracted from unstructured data and may contain inaccuracies. If you notice any errors, please reach out to the designated contact at CISA CSAF: central@cisa.dhs.gov",
        "title": "CISA Disclaimer"
      },
      {
        "category": "legal_disclaimer",
        "text": "All information products included in https://us-cert.cisa.gov/ics are provided \"as is\" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see https://us-cert.cisa.gov/tlp/.",
        "title": "Legal Notice"
      },
      {
        "category": "summary",
        "text": "Successful exploitation of these vulnerabilities could allow unauthorized users to compromise passwords and inject malicious code into web interfaces.",
        "title": "Risk evaluation"
      },
      {
        "category": "other",
        "text": "Critical Manufacturing",
        "title": "Critical infrastructure sectors"
      },
      {
        "category": "other",
        "text": "Worldwide",
        "title": "Countries/areas deployed"
      },
      {
        "category": "other",
        "text": "Ireland",
        "title": "Company headquarters location"
      },
      {
        "category": "general",
        "text": "Johnson Controls also recommends following CISA guidelines for minimizing the risks associated with automation systems, detailed below.",
        "title": "Recommended Practices"
      },
      {
        "category": "general",
        "text": "CISA recommends users take defensive measures to minimize the risk of exploitation of these vulnerabilities. Specifically, users should:",
        "title": "Recommended Practices"
      },
      {
        "category": "general",
        "text": "CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.\nCISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/icsSeveral recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.",
        "title": "Recommended Practices"
      },
      {
        "category": "general",
        "text": "Additional mitigation guidance and recommended practices are publicly available on the ICS webpage on cisa.gov/icsin the Technical Information Paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.\nOrganizations observing any suspected malicious activity should follow their established internal procedures and report their findings to CISA for tracking and correlation against other incidents.",
        "title": "Recommended Practices"
      },
      {
        "category": "other",
        "text": "No known public exploits specifically target these vulnerabilities.",
        "title": "Exploitability"
      }
    ],
    "publisher": {
      "category": "coordinator",
      "contact_details": "Email: CISAservicedesk@cisa.dhs.gov;\n Toll Free: 1-888-282-0870",
      "name": "CISA",
      "namespace": "https://www.cisa.gov/"
    },
    "references": [
      {
        "category": "self",
        "summary": "ICS Advisory ICSA-22-165-01 JSON",
        "url": "https://raw.githubusercontent.com/cisagov/CSAF/develop/csaf_files/OT/white/2022/icsa-22-165-01.json"
      },
      {
        "category": "self",
        "summary": "ICS Advisory ICSA-22-165-01 Web Version",
        "url": "https://www.cisa.gov/news-events/ics-advisories/icsa-22-165-01"
      },
      {
        "category": "external",
        "summary": "Recommended Practices",
        "url": "https://www.cisa.gov/uscert/ics/alerts/ICS-ALERT-10-301-01"
      },
      {
        "category": "external",
        "summary": "Recommended Practices",
        "url": "https://www.cisa.gov/uscert/sites/default/files/recommended_practices/NCCIC_ICS-CERT_Defense_in_Depth_2016_S508C.pdf"
      },
      {
        "category": "external",
        "summary": "Recommended Practices",
        "url": "https://www.cisa.gov/uscert/ics/tips/ICS-TIP-12-146-01B"
      }
    ],
    "title": "Johnson Controls Metasys ADS ADX OAS Servers",
    "tracking": {
      "current_release_date": "2022-06-14T00:00:00.000000Z",
      "generator": {
        "engine": {
          "name": "CISA CSAF Generator",
          "version": "1.0.0"
        }
      },
      "id": "ICSA-22-165-01",
      "initial_release_date": "2022-06-14T00:00:00.000000Z",
      "revision_history": [
        {
          "date": "2022-06-14T00:00:00.000000Z",
          "legacy_version": "Initial",
          "number": "1",
          "summary": "ICSA-22-165-01 Johnson Controls Metasys ADS ADX OAS Servers"
        }
      ],
      "status": "final",
      "version": "1"
    }
  },
  "product_tree": {
    "branches": [
      {
        "branches": [
          {
            "branches": [
              {
                "category": "product_version",
                "name": "10 | 11",
                "product": {
                  "name": "All Metasys ADS/ADX/OAS: Versions 10 and 11",
                  "product_id": "CSAFPID-0001"
                }
              }
            ],
            "category": "product_name",
            "name": "All Metasys ADS/ADX/OAS"
          }
        ],
        "category": "vendor",
        "name": "Johnson Controls Inc"
      }
    ]
  },
  "vulnerabilities": [
    {
      "cve": "CVE-2022-21935",
      "cwe": {
        "id": "CWE-620",
        "name": "Unverified Password Change"
      },
      "notes": [
        {
          "category": "summary",
          "text": "The affected products allow passwords to be guessed at a high rate.CVE-2022-21935 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (AV:A/AC:H/PR:N/UI:N/S:U/C:H/I:H/A:H).",
          "title": "Vulnerability Summary"
        }
      ],
      "product_status": {
        "known_affected": [
          "CSAFPID-0001"
        ]
      },
      "references": [
        {
          "category": "external",
          "summary": "web.nvd.nist.gov",
          "url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2022-21935"
        },
        {
          "category": "external",
          "summary": "www.first.org",
          "url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:A/AC:H/PR:N/UI:N/S:U/C:H/I:H/A:H"
        }
      ],
      "remediations": [
        {
          "category": "mitigation",
          "details": "Update Metasys ADS/ADX/OAS Version 10 with patch 10.1.5",
          "product_ids": [
            "CSAFPID-0001"
          ]
        },
        {
          "category": "mitigation",
          "details": "Update Metasys ADS/ADX/OAS Versions 11 with patch 11.0.2",
          "product_ids": [
            "CSAFPID-0001"
          ]
        },
        {
          "category": "mitigation",
          "details": "For more detailed mitigation instructions, please see Johnson Controls Product Security Advisory JCI-PSA-2022-10 v1",
          "product_ids": [
            "CSAFPID-0001"
          ],
          "url": "https://www.johnsoncontrols.com/cyber-solutions/security-advisories"
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "baseScore": 7.5,
            "baseSeverity": "HIGH",
            "vectorString": "CVSS:3.0/AV:A/AC:H/PR:N/UI:N/S:U/C:H/I:H/A:H",
            "version": "3.0"
          },
          "products": [
            "CSAFPID-0001"
          ]
        }
      ]
    },
    {
      "cve": "CVE-2022-21937",
      "cwe": {
        "id": "CWE-79",
        "name": "Improper Neutralization of Input During Web Page Generation (\u0027Cross-site Scripting\u0027)"
      },
      "notes": [
        {
          "category": "summary",
          "text": "It is possible to inject and store malicious code into the web interfaces of the affected products.CVE-2022-21937 has been assigned to this vulnerability. A CVSS v3 base score of 8.7 has been assigned; the CVSS vector string is (AV:N/AC:L/PR:L/UI:R/S:C/C:H/I:H/A:N).",
          "title": "Vulnerability Summary"
        }
      ],
      "product_status": {
        "known_affected": [
          "CSAFPID-0001"
        ]
      },
      "references": [
        {
          "category": "external",
          "summary": "web.nvd.nist.gov",
          "url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2022-21937"
        },
        {
          "category": "external",
          "summary": "www.first.org",
          "url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:L/UI:R/S:C/C:H/I:H/A:N"
        }
      ],
      "remediations": [
        {
          "category": "mitigation",
          "details": "Update Metasys ADS/ADX/OAS Version 10 with patch 10.1.5",
          "product_ids": [
            "CSAFPID-0001"
          ]
        },
        {
          "category": "mitigation",
          "details": "Update Metasys ADS/ADX/OAS Versions 11 with patch 11.0.2",
          "product_ids": [
            "CSAFPID-0001"
          ]
        },
        {
          "category": "mitigation",
          "details": "For more detailed mitigation instructions, please see Johnson Controls Product Security Advisory JCI-PSA-2022-10 v1",
          "product_ids": [
            "CSAFPID-0001"
          ],
          "url": "https://www.johnsoncontrols.com/cyber-solutions/security-advisories"
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "baseScore": 8.7,
            "baseSeverity": "HIGH",
            "vectorString": "CVSS:3.0/AV:N/AC:L/PR:L/UI:R/S:C/C:H/I:H/A:N",
            "version": "3.0"
          },
          "products": [
            "CSAFPID-0001"
          ]
        }
      ]
    },
    {
      "cve": "CVE-2022-21938",
      "cwe": {
        "id": "CWE-79",
        "name": "Improper Neutralization of Input During Web Page Generation (\u0027Cross-site Scripting\u0027)"
      },
      "notes": [
        {
          "category": "summary",
          "text": "It is possible to inject and store malicious code into the Draft Graphics (MUI Graphics) web interfaces of the affected products.CVE-2022-21938 has been assigned to this vulnerability. A CVSS v3 base score of 8.1 has been assigned; the CVSS vector string is (AV:N/AC:L/PR:H/UI:R/S:C/C:H/I:H/A:N).",
          "title": "Vulnerability Summary"
        }
      ],
      "product_status": {
        "known_affected": [
          "CSAFPID-0001"
        ]
      },
      "references": [
        {
          "category": "external",
          "summary": "web.nvd.nist.gov",
          "url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2022-21938"
        },
        {
          "category": "external",
          "summary": "www.first.org",
          "url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:H/UI:R/S:C/C:H/I:H/A:N"
        }
      ],
      "remediations": [
        {
          "category": "mitigation",
          "details": "Update Metasys ADS/ADX/OAS Version 10 with patch 10.1.5",
          "product_ids": [
            "CSAFPID-0001"
          ]
        },
        {
          "category": "mitigation",
          "details": "Update Metasys ADS/ADX/OAS Versions 11 with patch 11.0.2",
          "product_ids": [
            "CSAFPID-0001"
          ]
        },
        {
          "category": "mitigation",
          "details": "For more detailed mitigation instructions, please see Johnson Controls Product Security Advisory JCI-PSA-2022-10 v1",
          "product_ids": [
            "CSAFPID-0001"
          ],
          "url": "https://www.johnsoncontrols.com/cyber-solutions/security-advisories"
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "baseScore": 8.1,
            "baseSeverity": "HIGH",
            "vectorString": "CVSS:3.0/AV:N/AC:L/PR:H/UI:R/S:C/C:H/I:H/A:N",
            "version": "3.0"
          },
          "products": [
            "CSAFPID-0001"
          ]
        }
      ]
    }
  ]
}


Log in or create an account to share your comment.




Tags
Taxonomy of the tags.


Loading…

Loading…

Loading…

Sightings

Author Source Type Date

Nomenclature

  • Seen: The vulnerability was mentioned, discussed, or observed by the user.
  • Confirmed: The vulnerability has been validated from an analyst's perspective.
  • Published Proof of Concept: A public proof of concept is available for this vulnerability.
  • Exploited: The vulnerability was observed as exploited by the user who reported the sighting.
  • Patched: The vulnerability was observed as successfully patched by the user who reported the sighting.
  • Not exploited: The vulnerability was not observed as exploited by the user who reported the sighting.
  • Not confirmed: The user expressed doubt about the validity of the vulnerability.
  • Not patched: The vulnerability was not observed as successfully patched by the user who reported the sighting.


Loading…

Detection rules are retrieved from Rulezet.

Loading…

Loading…