icsa-22-349-02
Vulnerability from csaf_cisa
Published
2022-12-15 00:00
Modified
2022-12-15 00:00
Summary
Siemens SCALANCE X-200RNA Switch Devices
Notes
CISA Disclaimer
This CSAF advisory was extracted from unstructured data and may contain inaccuracies. If you notice any errors, please reach out to the designated contact at CISA CSAF: central@cisa.dhs.gov
Legal Notice
All information products included in https://us-cert.cisa.gov/ics are provided "as is" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see https://us-cert.cisa.gov/tlp/.
Risk evaluation
Exploitation of these vulnerabilities could result in a denial-of-service condition, hijacking of web sessions, and the loss of confidential or sensitive information.
Critical infrastructure sectors
Chemical, Critical Manufacturing, Energy, Food and Agriculture, and Water and Wastewater Systems
Countries/areas deployed
Worldwide
Company headquarters location
Germany
Recommended Practices
CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability these vulnerabilities. Specifically, users should:
Recommended Practices
CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.
Recommended Practices
CISA also provides a section for control systems security recommended practices on the ICS webpage at cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.
Recommended Practices
Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.
Recommended Practices
CISA also recommends users take the following measures to protect themselves from social engineering attacks:
Recommended Practices
Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.
Additional Resources
For further inquiries on security vulnerabilities in Siemens products and solutions, please contact the Siemens ProductCERT: https://www.siemens.com/cert/advisories
Exploitability
No known public exploits specifically target these vulnerabilities. These vulnerabilities are exploitable remotely. These vulnerabilities have a low attack complexity.
{ "document": { "acknowledgments": [ { "organization": "Siemens", "summary": "reporting these vulnerabilities to CISA" } ], "category": "csaf_security_advisory", "csaf_version": "2.0", "distribution": { "text": "Disclosure is not limited", "tlp": { "label": "WHITE", "url": "https://us-cert.cisa.gov/tlp/" } }, "lang": "en-US", "notes": [ { "category": "general", "text": "This CSAF advisory was extracted from unstructured data and may contain inaccuracies. If you notice any errors, please reach out to the designated contact at CISA CSAF: central@cisa.dhs.gov", "title": "CISA Disclaimer" }, { "category": "legal_disclaimer", "text": "All information products included in https://us-cert.cisa.gov/ics are provided \"as is\" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see https://us-cert.cisa.gov/tlp/.", "title": "Legal Notice" }, { "category": "summary", "text": "Exploitation of these vulnerabilities could result in a denial-of-service condition, hijacking of web sessions, and the loss of confidential or sensitive information.", "title": "Risk evaluation" }, { "category": "other", "text": " Chemical, Critical Manufacturing, Energy, Food and Agriculture, and Water and Wastewater Systems", "title": "Critical infrastructure sectors" }, { "category": "other", "text": " Worldwide", "title": "Countries/areas deployed" }, { "category": "other", "text": " Germany", "title": "Company headquarters location" }, { "category": "general", "text": "CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability these vulnerabilities. Specifically, users should:", "title": "Recommended Practices" }, { "category": "general", "text": "CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.", "title": "Recommended Practices" }, { "category": "general", "text": "CISA also provides a section for control systems security recommended practices on the ICS webpage at cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.", "title": "Recommended Practices" }, { "category": "general", "text": "Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.", "title": "Recommended Practices" }, { "category": "general", "text": "CISA also recommends users take the following measures to protect themselves from social engineering attacks:", "title": "Recommended Practices" }, { "category": "general", "text": "Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.", "title": "Recommended Practices" }, { "category": "general", "text": "For further inquiries on security vulnerabilities in Siemens products and solutions, please contact the Siemens ProductCERT: https://www.siemens.com/cert/advisories", "title": "Additional Resources" }, { "category": "other", "text": "No known public exploits specifically target these vulnerabilities. These vulnerabilities are exploitable remotely. These vulnerabilities have a low attack complexity.", "title": "Exploitability" } ], "publisher": { "category": "coordinator", "contact_details": "Email: CISAservicedesk@cisa.dhs.gov;\n Toll Free: 1-888-282-0870", "name": "CISA", "namespace": "https://www.cisa.gov/" }, "references": [ { "category": "external", "summary": "SSA-363821: Multiple Vulnerabilities in SCALANCE X-200RNA Switch Devices before V3.2.7 - CSAF Version", "url": "https://cert-portal.siemens.com/productcert/csaf/ssa-363821.json" }, { "category": "self", "summary": "ICS Advisory ICSA-22-349-02 JSON", "url": "https://raw.githubusercontent.com/cisagov/CSAF/develop/csaf_files/OT/white/2022/icsa-22-349-02.json" }, { "category": "self", "summary": "ICS Advisory ICSA-22-349-02 Web Version", "url": "https://www.cisa.gov/news-events/ics-advisories/icsa-22-349-02" }, { "category": "external", "summary": "Recommended Practices", "url": "https://www.cisa.gov/uscert/ncas/tips/ST04-014" }, { "category": "external", "summary": "Recommended Practices", "url": "https://us-cert.cisa.gov/sites/default/files/recommended_practices/NCCIC_ICS-CERT_Defense_in_Depth_2016_S508C.pdf" }, { "category": "external", "summary": "SSA-363821: Multiple Vulnerabilities in SCALANCE X-200RNA Switch Devices before V3.2.7 - PDF Version", "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-363821.pdf" }, { "category": "external", "summary": "SSA-363821: Multiple Vulnerabilities in SCALANCE X-200RNA Switch Devices before V3.2.7 - TXT Version", "url": "https://cert-portal.siemens.com/productcert/txt/ssa-363821.txt" } ], "title": "Siemens SCALANCE X-200RNA Switch Devices", "tracking": { "current_release_date": "2022-12-15T00:00:00.000000Z", "generator": { "engine": { "name": "CISA CSAF Generator", "version": "1.0.0" } }, "id": "ICSA-22-349-02", "initial_release_date": "2022-12-15T00:00:00.000000Z", "revision_history": [ { "date": "2022-12-15T00:00:00.000000Z", "legacy_version": "Initial", "number": "1", "summary": "Publication Date" } ], "status": "final", "version": "1" } }, "product_tree": { "branches": [ { "branches": [ { "branches": [ { "category": "product_version_range", "name": "\u003c V3.2.7", "product": { "name": "SCALANCE X204RNA (HSR) (6GK5204-0BA00-2MB2)", "product_id": "CSAFPID-0001", "product_identification_helper": { "model_numbers": [ "6GK5204-0BA00-2MB2" ] } } } ], "category": "product_name", "name": "SCALANCE X204RNA (HSR) (6GK5204-0BA00-2MB2)" }, { "branches": [ { "category": "product_version_range", "name": "\u003c V3.2.7", "product": { "name": "SCALANCE X204RNA (PRP) (6GK5204-0BA00-2KB2)", "product_id": "CSAFPID-0002", "product_identification_helper": { "model_numbers": [ "6GK5204-0BA00-2KB2" ] } } } ], "category": "product_name", "name": "SCALANCE X204RNA (PRP) (6GK5204-0BA00-2KB2)" }, { "branches": [ { "category": "product_version_range", "name": "\u003c V3.2.7", "product": { "name": "SCALANCE X204RNA EEC (HSR) (6GK5204-0BS00-2NA3)", "product_id": "CSAFPID-0003", "product_identification_helper": { "model_numbers": [ "6GK5204-0BS00-2NA3" ] } } } ], "category": "product_name", "name": "SCALANCE X204RNA EEC (HSR) (6GK5204-0BS00-2NA3)" }, { "branches": [ { "category": "product_version_range", "name": "\u003c V3.2.7", "product": { "name": "SCALANCE X204RNA EEC (PRP) (6GK5204-0BS00-3LA3)", "product_id": "CSAFPID-0004", "product_identification_helper": { "model_numbers": [ "6GK5204-0BS00-3LA3" ] } } } ], "category": "product_name", "name": "SCALANCE X204RNA EEC (PRP) (6GK5204-0BS00-3LA3)" }, { "branches": [ { "category": "product_version_range", "name": "\u003c V3.2.7", "product": { "name": "SCALANCE X204RNA EEC (PRP/HSR) (6GK5204-0BS00-3PA3)", "product_id": "CSAFPID-0005", "product_identification_helper": { "model_numbers": [ "6GK5204-0BS00-3PA3" ] } } } ], "category": "product_name", "name": "SCALANCE X204RNA EEC (PRP/HSR) (6GK5204-0BS00-3PA3)" } ], "category": "vendor", "name": "Siemens" } ] }, "vulnerabilities": [ { "cve": "CVE-2022-46350", "cwe": { "id": "CWE-80", "name": "Improper Neutralization of Script-Related HTML Tags in a Web Page (Basic XSS)" }, "notes": [ { "category": "summary", "text": "The integrated web server could allow Cross-Site Scripting (XSS) attacks if unsuspecting users are tricked into accessing a malicious link. This can be used by an attacker to trigger a malicious request on the affected device.", "title": "Summary" } ], "product_status": { "known_affected": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005" ] }, "references": [ { "category": "external", "summary": "nvd.nist.gov", "url": "https://nvd.nist.gov/vuln/detail/CVE-2022-46350" }, { "category": "external", "summary": "www.first.org", "url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:A/AC:H/PR:N/UI:R/S:C/C:H/I:H/A:H" } ], "remediations": [ { "category": "mitigation", "details": "Restrict access to the affected systems, especially to ports 22/tcp, 80/tcp, 443/tcp and 161/udp to trusted IP addresses only", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005" ] }, { "category": "mitigation", "details": "Disable the SNMP service if not required, and if disabling is supported by the product", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005" ] }, { "category": "mitigation", "details": "Deactivate the web server if not required, and if deactivation is supported by the product", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005" ] }, { "category": "vendor_fix", "details": "Update to V3.2.7 or later version", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005" ], "url": "https://support.industry.siemens.com/cs/ww/en/view/109814809/" }, { "category": "mitigation", "details": "As a general security measure, Siemens strongly recommends to protect network access to devices with appropriate mechanisms. In order to operate the devices in a protected IT environment, Siemens recommends to configure the environment according to Siemens\u0027 operational guidelines for Industrial Security (Download: \nhttps://www.siemens.com/cert/operational-guidelines-industrial-security), and to follow the recommendations in the product manuals.\nAdditional information on Industrial Security by Siemens can be found at: \nhttps://www.siemens.com/industrialsecurity", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005" ] } ], "scores": [ { "cvss_v3": { "baseScore": 7.9, "baseSeverity": "HIGH", "vectorString": "CVSS:3.1/AV:A/AC:H/PR:N/UI:R/S:C/C:H/I:H/A:H/E:P/RL:O/RC:C", "version": "3.1" }, "products": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005" ] } ], "title": "CVE-2022-46350" }, { "cve": "CVE-2022-46351", "cwe": { "id": "CWE-400", "name": "Uncontrolled Resource Consumption" }, "notes": [ { "category": "summary", "text": "Specially crafted PROFINET DCP packets could cause a denial of service condition of affected products on a local Ethernet segment (Layer 2).", "title": "Summary" } ], "product_status": { "known_affected": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005" ] }, "references": [ { "category": "external", "summary": "nvd.nist.gov", "url": "https://nvd.nist.gov/vuln/detail/CVE-2022-46351" }, { "category": "external", "summary": "www.first.org", "url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:A/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H" } ], "remediations": [ { "category": "mitigation", "details": "Restrict access to the affected systems, especially to ports 22/tcp, 80/tcp, 443/tcp and 161/udp to trusted IP addresses only", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005" ] }, { "category": "mitigation", "details": "Disable the SNMP service if not required, and if disabling is supported by the product", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005" ] }, { "category": "mitigation", "details": "Deactivate the web server if not required, and if deactivation is supported by the product", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005" ] }, { "category": "vendor_fix", "details": "Update to V3.2.7 or later version", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005" ], "url": "https://support.industry.siemens.com/cs/ww/en/view/109814809/" }, { "category": "mitigation", "details": "As a general security measure, Siemens strongly recommends to protect network access to devices with appropriate mechanisms. In order to operate the devices in a protected IT environment, Siemens recommends to configure the environment according to Siemens\u0027 operational guidelines for Industrial Security (Download: \nhttps://www.siemens.com/cert/operational-guidelines-industrial-security), and to follow the recommendations in the product manuals.\nAdditional information on Industrial Security by Siemens can be found at: \nhttps://www.siemens.com/industrialsecurity", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005" ] } ], "scores": [ { "cvss_v3": { "baseScore": 6.5, "baseSeverity": "MEDIUM", "vectorString": "CVSS:3.1/AV:A/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H/E:P/RL:O/RC:C", "version": "3.1" }, "products": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005" ] } ], "title": "CVE-2022-46351" }, { "cve": "CVE-2022-46352", "cwe": { "id": "CWE-400", "name": "Uncontrolled Resource Consumption" }, "notes": [ { "category": "summary", "text": "Specially crafted PROFINET DCP packets could cause a denial of service condition of affected products.", "title": "Summary" } ], "product_status": { "known_affected": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005" ] }, "references": [ { "category": "external", "summary": "nvd.nist.gov", "url": "https://nvd.nist.gov/vuln/detail/CVE-2022-46352" }, { "category": "external", "summary": "www.first.org", "url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H" } ], "remediations": [ { "category": "mitigation", "details": "Restrict access to the affected systems, especially to ports 22/tcp, 80/tcp, 443/tcp and 161/udp to trusted IP addresses only", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005" ] }, { "category": "mitigation", "details": "Disable the SNMP service if not required, and if disabling is supported by the product", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005" ] }, { "category": "mitigation", "details": "Deactivate the web server if not required, and if deactivation is supported by the product", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005" ] }, { "category": "vendor_fix", "details": "Update to V3.2.7 or later version", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005" ], "url": "https://support.industry.siemens.com/cs/ww/en/view/109814809/" }, { "category": "mitigation", "details": "As a general security measure, Siemens strongly recommends to protect network access to devices with appropriate mechanisms. In order to operate the devices in a protected IT environment, Siemens recommends to configure the environment according to Siemens\u0027 operational guidelines for Industrial Security (Download: \nhttps://www.siemens.com/cert/operational-guidelines-industrial-security), and to follow the recommendations in the product manuals.\nAdditional information on Industrial Security by Siemens can be found at: \nhttps://www.siemens.com/industrialsecurity", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005" ] } ], "scores": [ { "cvss_v3": { "baseScore": 7.5, "baseSeverity": "HIGH", "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H/E:P/RL:O/RC:C", "version": "3.1" }, "products": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005" ] } ], "title": "CVE-2022-46352" }, { "cve": "CVE-2022-46353", "cwe": { "id": "CWE-330", "name": "Use of Insufficiently Random Values" }, "notes": [ { "category": "summary", "text": "The webserver of affected devices calculates session ids and nonces in an insecure manner. This could allow an unauthenticated remote attacker to brute-force session ids and hijack existing sessions.", "title": "Summary" } ], "product_status": { "known_affected": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005" ] }, "references": [ { "category": "external", "summary": "nvd.nist.gov", "url": "https://nvd.nist.gov/vuln/detail/CVE-2022-46353" }, { "category": "external", "summary": "www.first.org", "url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H" } ], "remediations": [ { "category": "mitigation", "details": "Restrict access to the affected systems, especially to ports 22/tcp, 80/tcp, 443/tcp and 161/udp to trusted IP addresses only", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005" ] }, { "category": "mitigation", "details": "Disable the SNMP service if not required, and if disabling is supported by the product", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005" ] }, { "category": "mitigation", "details": "Deactivate the web server if not required, and if deactivation is supported by the product", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005" ] }, { "category": "vendor_fix", "details": "Update to V3.2.7 or later version", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005" ], "url": "https://support.industry.siemens.com/cs/ww/en/view/109814809/" }, { "category": "mitigation", "details": "As a general security measure, Siemens strongly recommends to protect network access to devices with appropriate mechanisms. In order to operate the devices in a protected IT environment, Siemens recommends to configure the environment according to Siemens\u0027 operational guidelines for Industrial Security (Download: \nhttps://www.siemens.com/cert/operational-guidelines-industrial-security), and to follow the recommendations in the product manuals.\nAdditional information on Industrial Security by Siemens can be found at: \nhttps://www.siemens.com/industrialsecurity", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005" ] } ], "scores": [ { "cvss_v3": { "baseScore": 8.8, "baseSeverity": "HIGH", "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H/E:P/RL:O/RC:C", "version": "3.1" }, "products": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005" ] } ], "title": "CVE-2022-46353" }, { "cve": "CVE-2022-46354", "cwe": { "id": "CWE-284", "name": "Improper Access Control" }, "notes": [ { "category": "summary", "text": "The webserver of an affected device is missing specific security headers. This could allow an remote attacker to extract confidential session information under certain circumstances.", "title": "Summary" } ], "product_status": { "known_affected": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005" ] }, "references": [ { "category": "external", "summary": "nvd.nist.gov", "url": "https://nvd.nist.gov/vuln/detail/CVE-2022-46354" }, { "category": "external", "summary": "www.first.org", "url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:A/AC:H/PR:N/UI:R/S:U/C:L/I:N/A:N" } ], "remediations": [ { "category": "mitigation", "details": "Restrict access to the affected systems, especially to ports 22/tcp, 80/tcp, 443/tcp and 161/udp to trusted IP addresses only", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005" ] }, { "category": "mitigation", "details": "Disable the SNMP service if not required, and if disabling is supported by the product", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005" ] }, { "category": "mitigation", "details": "Deactivate the web server if not required, and if deactivation is supported by the product", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005" ] }, { "category": "vendor_fix", "details": "Update to V3.2.7 or later version", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005" ], "url": "https://support.industry.siemens.com/cs/ww/en/view/109814809/" }, { "category": "mitigation", "details": "As a general security measure, Siemens strongly recommends to protect network access to devices with appropriate mechanisms. In order to operate the devices in a protected IT environment, Siemens recommends to configure the environment according to Siemens\u0027 operational guidelines for Industrial Security (Download: \nhttps://www.siemens.com/cert/operational-guidelines-industrial-security), and to follow the recommendations in the product manuals.\nAdditional information on Industrial Security by Siemens can be found at: \nhttps://www.siemens.com/industrialsecurity", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005" ] } ], "scores": [ { "cvss_v3": { "baseScore": 2.6, "baseSeverity": "LOW", "vectorString": "CVSS:3.1/AV:A/AC:H/PR:N/UI:R/S:U/C:L/I:N/A:N/E:P/RL:O/RC:C", "version": "3.1" }, "products": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005" ] } ], "title": "CVE-2022-46354" }, { "cve": "CVE-2022-46355", "cwe": { "id": "CWE-200", "name": "Exposure of Sensitive Information to an Unauthorized Actor" }, "notes": [ { "category": "summary", "text": "The affected products are vulnerable to an \"Exposure of Sensitive Information to an Unauthorized Actor\" vulnerability by leaking sensitive data in the HTTP Referer.", "title": "Summary" } ], "product_status": { "known_affected": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005" ] }, "references": [ { "category": "external", "summary": "nvd.nist.gov", "url": "https://nvd.nist.gov/vuln/detail/CVE-2022-46355" }, { "category": "external", "summary": "www.first.org", "url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:U/C:H/I:N/A:N" } ], "remediations": [ { "category": "mitigation", "details": "Restrict access to the affected systems, especially to ports 22/tcp, 80/tcp, 443/tcp and 161/udp to trusted IP addresses only", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005" ] }, { "category": "mitigation", "details": "Disable the SNMP service if not required, and if disabling is supported by the product", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005" ] }, { "category": "mitigation", "details": "Deactivate the web server if not required, and if deactivation is supported by the product", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005" ] }, { "category": "vendor_fix", "details": "Update to V3.2.7 or later version", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005" ], "url": "https://support.industry.siemens.com/cs/ww/en/view/109814809/" }, { "category": "mitigation", "details": "As a general security measure, Siemens strongly recommends to protect network access to devices with appropriate mechanisms. In order to operate the devices in a protected IT environment, Siemens recommends to configure the environment according to Siemens\u0027 operational guidelines for Industrial Security (Download: \nhttps://www.siemens.com/cert/operational-guidelines-industrial-security), and to follow the recommendations in the product manuals.\nAdditional information on Industrial Security by Siemens can be found at: \nhttps://www.siemens.com/industrialsecurity", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005" ] } ], "scores": [ { "cvss_v3": { "baseScore": 6.5, "baseSeverity": "MEDIUM", "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:U/C:H/I:N/A:N/E:P/RL:O/RC:C", "version": "3.1" }, "products": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005" ] } ], "title": "CVE-2022-46355" } ] }
Loading...
Loading...
- Seen: The vulnerability was mentioned, discussed, or seen somewhere by the user.
- Confirmed: The vulnerability is confirmed from an analyst perspective.
- Exploited: This vulnerability was exploited and seen by the user reporting the sighting.
- Patched: This vulnerability was successfully patched by the user reporting the sighting.
- Not exploited: This vulnerability was not exploited or seen by the user reporting the sighting.
- Not confirmed: The user expresses doubt about the veracity of the vulnerability.
- Not patched: This vulnerability was not successfully patched by the user reporting the sighting.