icsa-23-166-01
Vulnerability from csaf_cisa
Published
2023-06-15 06:00
Modified
2023-06-15 06:00
Summary
SUBNET PowerSYSTEM Center

Notes

CISA Disclaimer
This CSAF advisory was extracted from unstructured data and may contain inaccuracies. If you notice any errors, please reach out to the designated contact at CISA CSAF: central@cisa.dhs.gov
Legal Notice
All information products included in https://us-cert.cisa.gov/ics are provided "as is" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see https://us-cert.cisa.gov/tlp/.
Risk evaluation
Successful exploitation of these vulnerabilities could allow an attacker to upload malicious scripts or perform a denial-of-service type attack.
Critical infrastructure sectors
Critical Manufacturing
Countries/areas deployed
Worldwide
Company headquarters location
Canada
Recommended Practices
CISA recommends users take defensive measures to minimize the exploitation risk of these vulnerabilities, such as:
Recommended Practices
Minimizing network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet.
Recommended Practices
Locating control system networks and remote devices behind firewalls and isolating them from business networks.
Recommended Practices
When remote access is required, using more secure methods, such as Virtual Private Networks (VPNs). Recognize VPNs may have vulnerabilities, should be updated to the most recent version available, and are only as secure as the connected devices.
Recommended Practices
CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.
Recommended Practices
CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.
Recommended Practices
CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets. Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.
Recommended Practices
Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.
Recommended Practices
CISA also recommends users take the following measures to protect themselves from social engineering attacks:
Recommended Practices
Do not click web links or open attachments in unsolicited email messages.
Recommended Practices
Refer to Recognizing and Avoiding Email Scams for more information on avoiding email scams.
Recommended Practices
Refer to Avoiding Social Engineering and Phishing Attacks for more information on social engineering attacks.
Recommended Practices
No known public exploits specifically target these vulnerabilities.



{
  "document": {
    "acknowledgments": [
      {
        "organization": "SUBNET Solutions",
        "summary": "reporting these vulnerabilities to CISA"
      }
    ],
    "category": "csaf_security_advisory",
    "csaf_version": "2.0",
    "distribution": {
      "text": "Disclosure is not limited",
      "tlp": {
        "label": "WHITE",
        "url": "https://us-cert.cisa.gov/tlp/"
      }
    },
    "lang": "en-US",
    "notes": [
      {
        "category": "general",
        "text": "This CSAF advisory was extracted from unstructured data and may contain inaccuracies. If you notice any errors, please reach out to the designated contact at CISA CSAF: central@cisa.dhs.gov",
        "title": "CISA Disclaimer"
      },
      {
        "category": "legal_disclaimer",
        "text": "All information products included in https://us-cert.cisa.gov/ics are provided \"as is\" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see https://us-cert.cisa.gov/tlp/.",
        "title": "Legal Notice"
      },
      {
        "category": "summary",
        "text": "Successful exploitation of these vulnerabilities could allow an attacker to upload malicious scripts or perform a denial-of-service type attack. ",
        "title": "Risk evaluation"
      },
      {
        "category": "other",
        "text": "Critical Manufacturing",
        "title": "Critical infrastructure sectors"
      },
      {
        "category": "other",
        "text": "Worldwide",
        "title": "Countries/areas deployed"
      },
      {
        "category": "other",
        "text": "Canada",
        "title": "Company headquarters location"
      },
      {
        "category": "general",
        "text": "CISA recommends users take defensive measures to minimize the exploitation risk of these vulnerabilities, such as:",
        "title": "Recommended Practices"
      },
      {
        "category": "general",
        "text": "Minimizing network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet.",
        "title": "Recommended Practices"
      },
      {
        "category": "general",
        "text": "Locating control system networks and remote devices behind firewalls and isolating them from business networks.",
        "title": "Recommended Practices"
      },
      {
        "category": "general",
        "text": "When remote access is required, using more secure methods, such as Virtual Private Networks (VPNs). Recognize VPNs may have vulnerabilities, should be updated to the most recent version available, and are only as secure as the connected devices.",
        "title": "Recommended Practices"
      },
      {
        "category": "general",
        "text": "CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.",
        "title": "Recommended Practices"
      },
      {
        "category": "general",
        "text": "CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.",
        "title": "Recommended Practices"
      },
      {
        "category": "general",
        "text": "CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets. Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.",
        "title": "Recommended Practices"
      },
      {
        "category": "general",
        "text": "Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.",
        "title": "Recommended Practices"
      },
      {
        "category": "general",
        "text": "CISA also recommends users take the following measures to protect themselves from social engineering attacks:",
        "title": "Recommended Practices"
      },
      {
        "category": "general",
        "text": "Do not click web links or open attachments in unsolicited email messages.",
        "title": "Recommended Practices"
      },
      {
        "category": "general",
        "text": "Refer to Recognizing and Avoiding Email Scams for more information on avoiding email scams.",
        "title": "Recommended Practices"
      },
      {
        "category": "general",
        "text": "Refer to Avoiding Social Engineering and Phishing Attacks for more information on social engineering attacks.",
        "title": "Recommended Practices"
      },
      {
        "category": "general",
        "text": "No known public exploits specifically target these vulnerabilities.",
        "title": "Recommended Practices"
      }
    ],
    "publisher": {
      "category": "coordinator",
      "contact_details": "Email: CISAservicedesk@cisa.dhs.gov;\n Toll Free: 1-888-282-0870",
      "name": "CISA",
      "namespace": "https://www.cisa.gov/"
    },
    "references": [
      {
        "category": "self",
        "summary": "ICS Advisory ICSA-23-166-01 JSON",
        "url": "https://raw.githubusercontent.com/cisagov/CSAF/develop/csaf_files/OT/white/2023/icsa-23-166-01.json"
      },
      {
        "category": "self",
        "summary": "ICSA Advisory ICSA-23-166-01 - Web Version",
        "url": "https://www.cisa.gov/news-events/ics-advisories/icsa-23-166-01"
      },
      {
        "category": "external",
        "summary": "Recommended Practices",
        "url": "https://www.cisa.gov/uscert/ics/alerts/ICS-ALERT-10-301-01"
      },
      {
        "category": "external",
        "summary": "Recommended Practices",
        "url": "https://www.cisa.gov/resources-tools/resources/ics-recommended-practices"
      },
      {
        "category": "external",
        "summary": "Recommended Practices",
        "url": "https://www.cisa.gov/sites/default/files/publications/Cybersecurity_Best_Practices_for_Industrial_Control_Systems.pdf"
      },
      {
        "category": "external",
        "summary": "Recommended Practices",
        "url": "https://www.cisa.gov/uscert/sites/default/files/publications/emailscams0905.pdf"
      },
      {
        "category": "external",
        "summary": "Recommended Practices",
        "url": "https://www.cisa.gov/uscert/ncas/tips/ST04-014"
      },
      {
        "category": "external",
        "summary": "Recommended Practices",
        "url": "https://www.cisa.gov/topics/industrial-control-systems"
      },
      {
        "category": "external",
        "summary": "Recommended Practices",
        "url": "https://us-cert.cisa.gov/sites/default/files/recommended_practices/NCCIC_ICS-CERT_Defense_in_Depth_2016_S508C.pdf"
      },
      {
        "category": "external",
        "summary": "Recommended Practices",
        "url": "https://www.cisa.gov/uscert/ics/tips/ICS-TIP-12-146-01B"
      }
    ],
    "title": "SUBNET PowerSYSTEM Center",
    "tracking": {
      "current_release_date": "2023-06-15T06:00:00.000000Z",
      "generator": {
        "engine": {
          "name": "CISA CSAF Generator",
          "version": "1.0.0"
        }
      },
      "id": "ICSA-23-166-01",
      "initial_release_date": "2023-06-15T06:00:00.000000Z",
      "revision_history": [
        {
          "date": "2023-06-15T06:00:00.000000Z",
          "legacy_version": "Initial",
          "number": "1",
          "summary": "Initial Publication"
        }
      ],
      "status": "final",
      "version": "1"
    }
  },
  "product_tree": {
    "branches": [
      {
        "branches": [
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "\u003c=",
                "product": {
                  "name": "PowerSYSTEM Center: \u003c=",
                  "product_id": "CSAFPID-0001"
                }
              }
            ],
            "category": "product_name",
            "name": "PowerSYSTEM Center"
          }
        ],
        "category": "vendor",
        "name": "SUBNET Solutions Inc."
      }
    ]
  },
  "vulnerabilities": [
    {
      "cve": "CVE-2023-32659",
      "cwe": {
        "id": "CWE-79",
        "name": "Improper Neutralization of Input During Web Page Generation (\u0027Cross-site Scripting\u0027)"
      },
      "notes": [
        {
          "category": "summary",
          "text": "SUBNET PowerSYSTEM Center versions 2020 U10 and prior contain a cross-site scripting vulnerability that may allow an attacker to inject malicious code into report header graphic files that could propagate out of the system and reach users who are subscribed to email notifications. ",
          "title": "Vulnerability Summary"
        }
      ],
      "product_status": {
        "known_affected": [
          "CSAFPID-0001"
        ]
      },
      "references": [
        {
          "category": "external",
          "summary": "web.nvd.nist.gov",
          "url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2023-32659"
        },
        {
          "category": "external",
          "summary": "www.first.org",
          "url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:A/AC:L/PR:H/UI:R/S:C/C:H/I:N/A:L"
        }
      ],
      "remediations": [
        {
          "category": "vendor_fix",
          "details": "SUBNET Solutions has fixed these issues by enabling a file integrity check on uploaded images and anti-forgery tokens to prevent replay attacks. The fix was introduced in PowerSYSTEM Center update 12 as well as Update 8+Hotfix (both identified by release number 5.12.2305.10101, which can be located in Settings/Overview/Version).",
          "product_ids": [
            "CSAFPID-0001"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "SUBNET Solutions recommends users to follow the following workarounds:",
          "product_ids": [
            "CSAFPID-0001"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "Users should verify that SVG files do not contain HTML elements or scripts and validate that JPG and PNG files are not SVG files.",
          "product_ids": [
            "CSAFPID-0001"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "Users should verify network security rules to ensure that outbound connections to the internet are not possible.",
          "product_ids": [
            "CSAFPID-0001"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "If the above cannot be performed or notifications are not required, disable email notifications for reports from PowerSYSTEM Center.",
          "product_ids": [
            "CSAFPID-0001"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "Monitor user activity and ensure application control rules only allow preauthorized executables to run.",
          "product_ids": [
            "CSAFPID-0001"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "Deny users to run other executables on client access servers (PowerSYSTEM Center front end access point).",
          "product_ids": [
            "CSAFPID-0001"
          ]
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "baseScore": 6.5,
            "baseSeverity": "MEDIUM",
            "vectorString": "CVSS:3.0/AV:A/AC:L/PR:H/UI:R/S:C/C:H/I:N/A:L",
            "version": "3.0"
          },
          "products": [
            "CSAFPID-0001"
          ]
        }
      ]
    },
    {
      "cve": "CVE-2023-29158",
      "cwe": {
        "id": "CWE-294",
        "name": "Authentication Bypass by Capture-replay"
      },
      "notes": [
        {
          "category": "summary",
          "text": "SUBNET PowerSYSTEM Center versions 2020 U10 and prior are vulnerable to replay attacks which may result in a denial-of-service condition or a loss of data integrity. ",
          "title": "Vulnerability Summary"
        }
      ],
      "product_status": {
        "known_affected": [
          "CSAFPID-0001"
        ]
      },
      "references": [
        {
          "category": "external",
          "summary": "web.nvd.nist.gov",
          "url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2023-29158"
        },
        {
          "category": "external",
          "summary": "www.first.org",
          "url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:A/AC:L/PR:H/UI:N/S:U/C:N/I:H/A:H"
        }
      ],
      "remediations": [
        {
          "category": "vendor_fix",
          "details": "SUBNET Solutions has fixed these issues by enabling a file integrity check on uploaded images and anti-forgery tokens to prevent replay attacks. The fix was introduced in PowerSYSTEM Center update 12 as well as Update 8+Hotfix (both identified by release number 5.12.2305.10101, which can be located in Settings/Overview/Version).",
          "product_ids": [
            "CSAFPID-0001"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "SUBNET Solutions recommends users to follow the following workarounds:",
          "product_ids": [
            "CSAFPID-0001"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "Users should verify that SVG files do not contain HTML elements or scripts and validate that JPG and PNG files are not SVG files.",
          "product_ids": [
            "CSAFPID-0001"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "Users should verify network security rules to ensure that outbound connections to the internet are not possible.",
          "product_ids": [
            "CSAFPID-0001"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "If the above cannot be performed or notifications are not required, disable email notifications for reports from PowerSYSTEM Center.",
          "product_ids": [
            "CSAFPID-0001"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "Monitor user activity and ensure application control rules only allow preauthorized executables to run.",
          "product_ids": [
            "CSAFPID-0001"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "Deny users to run other executables on client access servers (PowerSYSTEM Center front end access point).",
          "product_ids": [
            "CSAFPID-0001"
          ]
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "baseScore": 6.1,
            "baseSeverity": "MEDIUM",
            "vectorString": "CVSS:3.0/AV:A/AC:L/PR:H/UI:N/S:U/C:N/I:H/A:H",
            "version": "3.0"
          },
          "products": [
            "CSAFPID-0001"
          ]
        }
      ]
    }
  ]
}


Log in or create an account to share your comment.




Tags
Taxonomy of the tags.


Loading...

Loading...

Loading...

Sightings

Author Source Type Date

Nomenclature

  • Seen: The vulnerability was mentioned, discussed, or seen somewhere by the user.
  • Confirmed: The vulnerability is confirmed from an analyst perspective.
  • Exploited: This vulnerability was exploited and seen by the user reporting the sighting.
  • Patched: This vulnerability was successfully patched by the user reporting the sighting.
  • Not exploited: This vulnerability was not exploited or seen by the user reporting the sighting.
  • Not confirmed: The user expresses doubt about the veracity of the vulnerability.
  • Not patched: This vulnerability was not successfully patched by the user reporting the sighting.