icsa-23-194-06
Vulnerability from csaf_cisa
Published
2023-07-13 00:00
Modified
2023-07-13 00:00
Summary
Honeywell Experion PKS, LX and PlantCruise

Notes

CISA Disclaimer
This CSAF advisory was extracted from unstructured data and may contain inaccuracies. If you notice any errors, please reach out to the designated contact at CISA CSAF: central@cisa.dhs.gov
Legal Notice
All information products included in https://us-cert.cisa.gov/ics are provided "as is" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see https://us-cert.cisa.gov/tlp/.
Risk evaluation
Successful exploitation of these vulnerabilities could cause a denial-of-service condition, allow privilege escalation or allow remote code execution.
Critical infrastructure sectors
Multiple
Countries/areas deployed
Worldwide
Company headquarters location
United States
Recommended Practices
CISA recommends users take defensive measures to minimize the risk of exploitation of these vulnerabilities, such as:
Recommended Practices
Ensure the least-privilege user principle is followed.
Recommended Practices
Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet.
Recommended Practices
Locate control system networks and remote devices behind firewalls and isolating them from business networks.
Recommended Practices
When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize VPN is only as secure as the connected devices.
Recommended Practices
CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.
Recommended Practices
CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.
Recommended Practices
CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.
Recommended Practices
Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.
Recommended Practices
Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.
Recommended Practices
No known public exploits specifically target these vulnerabilities. These vulnerabilities are exploitable remotely. These vulnerabilities have a low attack complexity.



{
  "document": {
    "acknowledgments": [
      {
        "organization": "ARMIS cyber researchers",
        "summary": "reporting these vulnerabilities to Honeywell"
      }
    ],
    "category": "csaf_security_advisory",
    "csaf_version": "2.0",
    "distribution": {
      "text": "Disclosure is not limited",
      "tlp": {
        "label": "WHITE",
        "url": "https://us-cert.cisa.gov/tlp/"
      }
    },
    "lang": "en-US",
    "notes": [
      {
        "category": "general",
        "text": "This CSAF advisory was extracted from unstructured data and may contain inaccuracies. If you notice any errors, please reach out to the designated contact at CISA CSAF: central@cisa.dhs.gov",
        "title": "CISA Disclaimer"
      },
      {
        "category": "legal_disclaimer",
        "text": "All information products included in https://us-cert.cisa.gov/ics are provided \"as is\" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see https://us-cert.cisa.gov/tlp/.",
        "title": "Legal Notice"
      },
      {
        "category": "summary",
        "text": "Successful exploitation of these vulnerabilities could cause a denial-of-service condition, allow privilege escalation or allow remote code execution.",
        "title": "Risk evaluation"
      },
      {
        "category": "other",
        "text": "Multiple",
        "title": "Critical infrastructure sectors"
      },
      {
        "category": "other",
        "text": "Worldwide",
        "title": "Countries/areas deployed"
      },
      {
        "category": "other",
        "text": "United States",
        "title": "Company headquarters location"
      },
      {
        "category": "general",
        "text": "CISA recommends users take defensive measures to minimize the risk of exploitation of these vulnerabilities, such as:",
        "title": "Recommended Practices"
      },
      {
        "category": "general",
        "text": "Ensure the least-privilege user principle is followed.",
        "title": "Recommended Practices"
      },
      {
        "category": "general",
        "text": "Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet.",
        "title": "Recommended Practices"
      },
      {
        "category": "general",
        "text": "Locate control system networks and remote devices behind firewalls and isolating them from business networks.",
        "title": "Recommended Practices"
      },
      {
        "category": "general",
        "text": "When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize VPN is only as secure as the connected devices.",
        "title": "Recommended Practices"
      },
      {
        "category": "general",
        "text": "CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.",
        "title": "Recommended Practices"
      },
      {
        "category": "general",
        "text": "CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.",
        "title": "Recommended Practices"
      },
      {
        "category": "general",
        "text": "CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.",
        "title": "Recommended Practices"
      },
      {
        "category": "general",
        "text": "Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.",
        "title": "Recommended Practices"
      },
      {
        "category": "general",
        "text": "Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.",
        "title": "Recommended Practices"
      },
      {
        "category": "general",
        "text": "No known public exploits specifically target these vulnerabilities. These vulnerabilities are exploitable remotely. These vulnerabilities have a low attack complexity.",
        "title": "Recommended Practices"
      }
    ],
    "publisher": {
      "category": "coordinator",
      "contact_details": "Email: CISAservicedesk@cisa.dhs.gov;\n Toll Free: 1-888-282-0870",
      "name": "CISA",
      "namespace": "https://www.cisa.gov/"
    },
    "references": [
      {
        "category": "self",
        "summary": "ICS Advisory ICSA-23-194-06 JSON",
        "url": "https://raw.githubusercontent.com/cisagov/CSAF/develop/csaf_files/OT/white/2023/icsa-23-194-06.json"
      },
      {
        "category": "self",
        "summary": "ICSA Advisory ICSA-23-194-06 - Web Version",
        "url": "https://www.cisa.gov/news-events/ics-advisories/icsa-23-194-06"
      },
      {
        "category": "external",
        "summary": "Recommended Practices",
        "url": "https://www.cisa.gov/uscert/ics/alerts/ICS-ALERT-10-301-01"
      },
      {
        "category": "external",
        "summary": "Recommended Practices",
        "url": "https://www.cisa.gov/resources-tools/resources/ics-recommended-practices"
      },
      {
        "category": "external",
        "summary": "Recommended Practices",
        "url": "https://www.cisa.gov/sites/default/files/publications/Cybersecurity_Best_Practices_for_Industrial_Control_Systems.pdf"
      },
      {
        "category": "external",
        "summary": "Recommended Practices",
        "url": "https://www.cisa.gov/topics/industrial-control-systems"
      },
      {
        "category": "external",
        "summary": "Recommended Practices",
        "url": "https://us-cert.cisa.gov/sites/default/files/recommended_practices/NCCIC_ICS-CERT_Defense_in_Depth_2016_S508C.pdf"
      },
      {
        "category": "external",
        "summary": "Recommended Practices",
        "url": "https://www.cisa.gov/uscert/ics/tips/ICS-TIP-12-146-01B"
      }
    ],
    "title": "Honeywell Experion PKS, LX and PlantCruise",
    "tracking": {
      "current_release_date": "2023-07-13T00:00:00.000000Z",
      "generator": {
        "engine": {
          "name": "CISA CSAF Generator",
          "version": "1.0.0"
        }
      },
      "id": "ICSA-23-194-06",
      "initial_release_date": "2023-07-13T00:00:00.000000Z",
      "revision_history": [
        {
          "date": "2023-07-13T00:00:00.000000Z",
          "legacy_version": "Initial",
          "number": "1",
          "summary": "Initial Publication"
        }
      ],
      "status": "final",
      "version": "1"
    }
  },
  "product_tree": {
    "branches": [
      {
        "branches": [
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "\u003c R520.2",
                "product": {
                  "name": "Experion PKS: \u003c R520.2",
                  "product_id": "CSAFPID-0001"
                }
              }
            ],
            "category": "product_name",
            "name": "Experion PKS"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "\u003c R520.2",
                "product": {
                  "name": "Experion LX: \u003c R520.2",
                  "product_id": "CSAFPID-0002"
                }
              }
            ],
            "category": "product_name",
            "name": "Experion LX"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "\u003c R520.2",
                "product": {
                  "name": "Experion PlantCruise: \u003c R520.2",
                  "product_id": "CSAFPID-0003"
                }
              }
            ],
            "category": "product_name",
            "name": "Experion PlantCruise"
          }
        ],
        "category": "vendor",
        "name": "Honeywell "
      }
    ]
  },
  "vulnerabilities": [
    {
      "cve": "CVE-2023-23585",
      "cwe": {
        "id": "CWE-122",
        "name": "Heap-based Buffer Overflow"
      },
      "notes": [
        {
          "category": "summary",
          "text": "Experion Server or Console Station could experience a denial-of-service condition due to a heap overflow during the handling of a specially crafted message for a specific configuration operation.",
          "title": "Vulnerability Summary"
        }
      ],
      "product_status": {
        "known_affected": [
          "CSAFPID-0001",
          "CSAFPID-0002",
          "CSAFPID-0003"
        ]
      },
      "references": [
        {
          "category": "external",
          "summary": "web.nvd.nist.gov",
          "url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2023-23585"
        },
        {
          "category": "external",
          "summary": "www.first.org",
          "url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H"
        }
      ],
      "remediations": [
        {
          "category": "mitigation",
          "details": "Honeywell recommends users upgrade Experion Platforms to version R520.2. Download information includes the following:",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "Experion PKS: Update to version R520.2",
          "product_ids": [
            "CSAFPID-0001"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "Experion LX: Update to version R520.2",
          "product_ids": [
            "CSAFPID-0002"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "Experion PlantCruise: Update to version R520.2",
          "product_ids": [
            "CSAFPID-0003"
          ]
        },
        {
          "category": "mitigation",
          "details": "Go to the Honeywell Website and sign in.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ],
          "url": "http://process.honeywell.com/"
        },
        {
          "category": "mitigation",
          "details": "Select \"Support\" at the top of the web page.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        },
        {
          "category": "mitigation",
          "details": "Select \"Product Documents \u0026 Downloads.\"",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "In the given search box, search for: \"Experion PKS R520.2\", \"Experion LX R520.2\" or \"Experion PlantCruise R520.2\" and select the hyperlink for the given Experion platform.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        },
        {
          "category": "mitigation",
          "details": "Honeywell advises users to follow security best practices for Experion platform environments to ensure access is limited to authorized users only. Users should ensure the backup files are maintained in a network location or physical drive with access limited to authorized users only and should not share them.Honeywell Security Notifications are available on the Honeywell website.  For access, users should visit the Honeywell Website and sign in, select the search icon at the top of the web page, and search for \"SN2023-06-22\".",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ],
          "url": "http://process.honeywell.com/"
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "baseScore": 9.8,
            "baseSeverity": "CRITICAL",
            "vectorString": "CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H",
            "version": "3.0"
          },
          "products": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        }
      ]
    },
    {
      "cve": "CVE-2023-25078",
      "cwe": {
        "id": "CWE-121",
        "name": "Stack-based Buffer Overflow"
      },
      "notes": [
        {
          "category": "summary",
          "text": "Experion Server or Console Station could experience a denial-of-service condition or remote code execution  due to a stack overflow during the handling of a specially crafted message for a specific configuration operation.",
          "title": "Vulnerability Summary"
        }
      ],
      "product_status": {
        "known_affected": [
          "CSAFPID-0001",
          "CSAFPID-0002",
          "CSAFPID-0003"
        ]
      },
      "references": [
        {
          "category": "external",
          "summary": "web.nvd.nist.gov",
          "url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2023-25078"
        },
        {
          "category": "external",
          "summary": "www.first.org",
          "url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H"
        }
      ],
      "remediations": [
        {
          "category": "mitigation",
          "details": "Honeywell recommends users upgrade Experion Platforms to version R520.2. Download information includes the following:",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "Experion PKS: Update to version R520.2",
          "product_ids": [
            "CSAFPID-0001"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "Experion LX: Update to version R520.2",
          "product_ids": [
            "CSAFPID-0002"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "Experion PlantCruise: Update to version R520.2",
          "product_ids": [
            "CSAFPID-0003"
          ]
        },
        {
          "category": "mitigation",
          "details": "Go to the Honeywell Website and sign in.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ],
          "url": "http://process.honeywell.com/"
        },
        {
          "category": "mitigation",
          "details": "Select \"Support\" at the top of the web page.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        },
        {
          "category": "mitigation",
          "details": "Select \"Product Documents \u0026 Downloads.\"",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "In the given search box, search for: \"Experion PKS R520.2\", \"Experion LX R520.2\" or \"Experion PlantCruise R520.2\" and select the hyperlink for the given Experion platform.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        },
        {
          "category": "mitigation",
          "details": "Honeywell advises users to follow security best practices for Experion platform environments to ensure access is limited to authorized users only. Users should ensure the backup files are maintained in a network location or physical drive with access limited to authorized users only and should not share them.Honeywell Security Notifications are available on the Honeywell website.  For access, users should visit the Honeywell Website and sign in, select the search icon at the top of the web page, and search for \"SN2023-06-22\".",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ],
          "url": "http://process.honeywell.com/"
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "baseScore": 9.8,
            "baseSeverity": "CRITICAL",
            "vectorString": "CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H",
            "version": "3.0"
          },
          "products": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        }
      ]
    },
    {
      "cve": "CVE-2023-25948",
      "cwe": {
        "id": "CWE-394",
        "name": "Unexpected Status Code or Return Value"
      },
      "notes": [
        {
          "category": "summary",
          "text": "C300 could leak configuration data when an error is generated in response to a specially crafted message.",
          "title": "Vulnerability Summary"
        }
      ],
      "product_status": {
        "known_affected": [
          "CSAFPID-0001",
          "CSAFPID-0002",
          "CSAFPID-0003"
        ]
      },
      "references": [
        {
          "category": "external",
          "summary": "web.nvd.nist.gov",
          "url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2023-25948"
        },
        {
          "category": "external",
          "summary": "www.first.org",
          "url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H"
        }
      ],
      "remediations": [
        {
          "category": "mitigation",
          "details": "Honeywell recommends users upgrade Experion Platforms to version R520.2. Download information includes the following:",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "Experion PKS: Update to version R520.2",
          "product_ids": [
            "CSAFPID-0001"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "Experion LX: Update to version R520.2",
          "product_ids": [
            "CSAFPID-0002"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "Experion PlantCruise: Update to version R520.2",
          "product_ids": [
            "CSAFPID-0003"
          ]
        },
        {
          "category": "mitigation",
          "details": "Go to the Honeywell Website and sign in.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ],
          "url": "http://process.honeywell.com/"
        },
        {
          "category": "mitigation",
          "details": "Select \"Support\" at the top of the web page.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        },
        {
          "category": "mitigation",
          "details": "Select \"Product Documents \u0026 Downloads.\"",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "In the given search box, search for: \"Experion PKS R520.2\", \"Experion LX R520.2\" or \"Experion PlantCruise R520.2\" and select the hyperlink for the given Experion platform.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        },
        {
          "category": "mitigation",
          "details": "Honeywell advises users to follow security best practices for Experion platform environments to ensure access is limited to authorized users only. Users should ensure the backup files are maintained in a network location or physical drive with access limited to authorized users only and should not share them.Honeywell Security Notifications are available on the Honeywell website.  For access, users should visit the Honeywell Website and sign in, select the search icon at the top of the web page, and search for \"SN2023-06-22\".",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ],
          "url": "http://process.honeywell.com/"
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "baseScore": 9.8,
            "baseSeverity": "CRITICAL",
            "vectorString": "CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H",
            "version": "3.0"
          },
          "products": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        }
      ]
    },
    {
      "cve": "CVE-2023-26597",
      "cwe": {
        "id": "CWE-400",
        "name": "Uncontrolled Resource Consumption"
      },
      "notes": [
        {
          "category": "summary",
          "text": "C300 could experience a denial-of-service condition due to a buffer overflow in the handling of a specially crafted message received by the controller.",
          "title": "Vulnerability Summary"
        }
      ],
      "product_status": {
        "known_affected": [
          "CSAFPID-0001",
          "CSAFPID-0002",
          "CSAFPID-0003"
        ]
      },
      "references": [
        {
          "category": "external",
          "summary": "web.nvd.nist.gov",
          "url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2023-26597"
        },
        {
          "category": "external",
          "summary": "www.first.org",
          "url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H"
        }
      ],
      "remediations": [
        {
          "category": "mitigation",
          "details": "Honeywell recommends users upgrade Experion Platforms to version R520.2. Download information includes the following:",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "Experion PKS: Update to version R520.2",
          "product_ids": [
            "CSAFPID-0001"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "Experion LX: Update to version R520.2",
          "product_ids": [
            "CSAFPID-0002"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "Experion PlantCruise: Update to version R520.2",
          "product_ids": [
            "CSAFPID-0003"
          ]
        },
        {
          "category": "mitigation",
          "details": "Go to the Honeywell Website and sign in.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ],
          "url": "http://process.honeywell.com/"
        },
        {
          "category": "mitigation",
          "details": "Select \"Support\" at the top of the web page.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        },
        {
          "category": "mitigation",
          "details": "Select \"Product Documents \u0026 Downloads.\"",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "In the given search box, search for: \"Experion PKS R520.2\", \"Experion LX R520.2\" or \"Experion PlantCruise R520.2\" and select the hyperlink for the given Experion platform.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        },
        {
          "category": "mitigation",
          "details": "Honeywell advises users to follow security best practices for Experion platform environments to ensure access is limited to authorized users only. Users should ensure the backup files are maintained in a network location or physical drive with access limited to authorized users only and should not share them.Honeywell Security Notifications are available on the Honeywell website.  For access, users should visit the Honeywell Website and sign in, select the search icon at the top of the web page, and search for \"SN2023-06-22\".",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ],
          "url": "http://process.honeywell.com/"
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "baseScore": 7.5,
            "baseSeverity": "HIGH",
            "vectorString": "CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H",
            "version": "3.0"
          },
          "products": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        }
      ]
    },
    {
      "cve": "CVE-2023-24480",
      "cwe": {
        "id": "CWE-116",
        "name": "Improper Encoding or Escaping of Output"
      },
      "notes": [
        {
          "category": "summary",
          "text": "C300 could experience a denial-of-service condition due to a stack overflow when decoding a message from the server.",
          "title": "Vulnerability Summary"
        }
      ],
      "product_status": {
        "known_affected": [
          "CSAFPID-0001",
          "CSAFPID-0002",
          "CSAFPID-0003"
        ]
      },
      "references": [
        {
          "category": "external",
          "summary": "web.nvd.nist.gov",
          "url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2023-24480"
        },
        {
          "category": "external",
          "summary": "www.first.org",
          "url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H"
        }
      ],
      "remediations": [
        {
          "category": "mitigation",
          "details": "Honeywell recommends users upgrade Experion Platforms to version R520.2. Download information includes the following:",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "Experion PKS: Update to version R520.2",
          "product_ids": [
            "CSAFPID-0001"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "Experion LX: Update to version R520.2",
          "product_ids": [
            "CSAFPID-0002"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "Experion PlantCruise: Update to version R520.2",
          "product_ids": [
            "CSAFPID-0003"
          ]
        },
        {
          "category": "mitigation",
          "details": "Go to the Honeywell Website and sign in.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ],
          "url": "http://process.honeywell.com/"
        },
        {
          "category": "mitigation",
          "details": "Select \"Support\" at the top of the web page.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        },
        {
          "category": "mitigation",
          "details": "Select \"Product Documents \u0026 Downloads.\"",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "In the given search box, search for: \"Experion PKS R520.2\", \"Experion LX R520.2\" or \"Experion PlantCruise R520.2\" and select the hyperlink for the given Experion platform.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        },
        {
          "category": "mitigation",
          "details": "Honeywell advises users to follow security best practices for Experion platform environments to ensure access is limited to authorized users only. Users should ensure the backup files are maintained in a network location or physical drive with access limited to authorized users only and should not share them.Honeywell Security Notifications are available on the Honeywell website.  For access, users should visit the Honeywell Website and sign in, select the search icon at the top of the web page, and search for \"SN2023-06-22\".",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ],
          "url": "http://process.honeywell.com/"
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "baseScore": 9.8,
            "baseSeverity": "CRITICAL",
            "vectorString": "CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H",
            "version": "3.0"
          },
          "products": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        }
      ]
    },
    {
      "cve": "CVE-2023-25770",
      "cwe": {
        "id": "CWE-502",
        "name": "Deserialization of Untrusted Data"
      },
      "notes": [
        {
          "category": "summary",
          "text": "C300 could experience a denial-of-service condition due to a buffer overflow when an error is generated in response to a specially crafted message.",
          "title": "Vulnerability Summary"
        }
      ],
      "product_status": {
        "known_affected": [
          "CSAFPID-0001",
          "CSAFPID-0002",
          "CSAFPID-0003"
        ]
      },
      "references": [
        {
          "category": "external",
          "summary": "web.nvd.nist.gov",
          "url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2023-25770"
        },
        {
          "category": "external",
          "summary": "www.first.org",
          "url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H"
        }
      ],
      "remediations": [
        {
          "category": "mitigation",
          "details": "Honeywell recommends users upgrade Experion Platforms to version R520.2. Download information includes the following:",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "Experion PKS: Update to version R520.2",
          "product_ids": [
            "CSAFPID-0001"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "Experion LX: Update to version R520.2",
          "product_ids": [
            "CSAFPID-0002"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "Experion PlantCruise: Update to version R520.2",
          "product_ids": [
            "CSAFPID-0003"
          ]
        },
        {
          "category": "mitigation",
          "details": "Go to the Honeywell Website and sign in.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ],
          "url": "http://process.honeywell.com/"
        },
        {
          "category": "mitigation",
          "details": "Select \"Support\" at the top of the web page.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        },
        {
          "category": "mitigation",
          "details": "Select \"Product Documents \u0026 Downloads.\"",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "In the given search box, search for: \"Experion PKS R520.2\", \"Experion LX R520.2\" or \"Experion PlantCruise R520.2\" and select the hyperlink for the given Experion platform.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        },
        {
          "category": "mitigation",
          "details": "Honeywell advises users to follow security best practices for Experion platform environments to ensure access is limited to authorized users only. Users should ensure the backup files are maintained in a network location or physical drive with access limited to authorized users only and should not share them.Honeywell Security Notifications are available on the Honeywell website.  For access, users should visit the Honeywell Website and sign in, select the search icon at the top of the web page, and search for \"SN2023-06-22\".",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ],
          "url": "http://process.honeywell.com/"
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "baseScore": 9.8,
            "baseSeverity": "CRITICAL",
            "vectorString": "CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H",
            "version": "3.0"
          },
          "products": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        }
      ]
    },
    {
      "cve": "CVE-2023-25178",
      "cwe": {
        "id": "CWE-345",
        "name": "Insufficient Verification of Data Authenticity"
      },
      "notes": [
        {
          "category": "summary",
          "text": "C300 may be loaded with malicious firmware which could enable remote code execution.",
          "title": "Vulnerability Summary"
        }
      ],
      "product_status": {
        "known_affected": [
          "CSAFPID-0001",
          "CSAFPID-0002",
          "CSAFPID-0003"
        ]
      },
      "references": [
        {
          "category": "external",
          "summary": "web.nvd.nist.gov",
          "url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2023-25178"
        },
        {
          "category": "external",
          "summary": "www.first.org",
          "url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N"
        }
      ],
      "remediations": [
        {
          "category": "mitigation",
          "details": "Honeywell recommends users upgrade Experion Platforms to version R520.2. Download information includes the following:",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "Experion PKS: Update to version R520.2",
          "product_ids": [
            "CSAFPID-0001"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "Experion LX: Update to version R520.2",
          "product_ids": [
            "CSAFPID-0002"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "Experion PlantCruise: Update to version R520.2",
          "product_ids": [
            "CSAFPID-0003"
          ]
        },
        {
          "category": "mitigation",
          "details": "Go to the Honeywell Website and sign in.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ],
          "url": "http://process.honeywell.com/"
        },
        {
          "category": "mitigation",
          "details": "Select \"Support\" at the top of the web page.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        },
        {
          "category": "mitigation",
          "details": "Select \"Product Documents \u0026 Downloads.\"",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "In the given search box, search for: \"Experion PKS R520.2\", \"Experion LX R520.2\" or \"Experion PlantCruise R520.2\" and select the hyperlink for the given Experion platform.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        },
        {
          "category": "mitigation",
          "details": "Honeywell advises users to follow security best practices for Experion platform environments to ensure access is limited to authorized users only. Users should ensure the backup files are maintained in a network location or physical drive with access limited to authorized users only and should not share them.Honeywell Security Notifications are available on the Honeywell website.  For access, users should visit the Honeywell Website and sign in, select the search icon at the top of the web page, and search for \"SN2023-06-22\".",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ],
          "url": "http://process.honeywell.com/"
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "baseScore": 7.5,
            "baseSeverity": "HIGH",
            "vectorString": "CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N",
            "version": "3.0"
          },
          "products": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        }
      ]
    },
    {
      "cve": "CVE-2023-22435",
      "cwe": {
        "id": "CWE-697",
        "name": "Incorrect Comparison"
      },
      "notes": [
        {
          "category": "summary",
          "text": "Experion Server may experience a denial-of-service condition due to an incorrect comparison when handling a specially crafted message.",
          "title": "Vulnerability Summary"
        }
      ],
      "product_status": {
        "known_affected": [
          "CSAFPID-0001",
          "CSAFPID-0002",
          "CSAFPID-0003"
        ]
      },
      "references": [
        {
          "category": "external",
          "summary": "web.nvd.nist.gov",
          "url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2023-22435"
        },
        {
          "category": "external",
          "summary": "www.first.org",
          "url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H"
        }
      ],
      "remediations": [
        {
          "category": "mitigation",
          "details": "Honeywell recommends users upgrade Experion Platforms to version R520.2. Download information includes the following:",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "Experion PKS: Update to version R520.2",
          "product_ids": [
            "CSAFPID-0001"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "Experion LX: Update to version R520.2",
          "product_ids": [
            "CSAFPID-0002"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "Experion PlantCruise: Update to version R520.2",
          "product_ids": [
            "CSAFPID-0003"
          ]
        },
        {
          "category": "mitigation",
          "details": "Go to the Honeywell Website and sign in.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ],
          "url": "http://process.honeywell.com/"
        },
        {
          "category": "mitigation",
          "details": "Select \"Support\" at the top of the web page.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        },
        {
          "category": "mitigation",
          "details": "Select \"Product Documents \u0026 Downloads.\"",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "In the given search box, search for: \"Experion PKS R520.2\", \"Experion LX R520.2\" or \"Experion PlantCruise R520.2\" and select the hyperlink for the given Experion platform.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        },
        {
          "category": "mitigation",
          "details": "Honeywell advises users to follow security best practices for Experion platform environments to ensure access is limited to authorized users only. Users should ensure the backup files are maintained in a network location or physical drive with access limited to authorized users only and should not share them.Honeywell Security Notifications are available on the Honeywell website.  For access, users should visit the Honeywell Website and sign in, select the search icon at the top of the web page, and search for \"SN2023-06-22\".",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ],
          "url": "http://process.honeywell.com/"
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "baseScore": 9.8,
            "baseSeverity": "CRITICAL",
            "vectorString": "CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H",
            "version": "3.0"
          },
          "products": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        }
      ]
    },
    {
      "cve": "CVE-2023-24474",
      "cwe": {
        "id": "CWE-122",
        "name": "Heap-based Buffer Overflow"
      },
      "notes": [
        {
          "category": "summary",
          "text": "Experion Server may experience a denial-of-service condition due to a heap overflow which could occur when handling a specially crafted message.",
          "title": "Vulnerability Summary"
        }
      ],
      "product_status": {
        "known_affected": [
          "CSAFPID-0001",
          "CSAFPID-0002",
          "CSAFPID-0003"
        ]
      },
      "references": [
        {
          "category": "external",
          "summary": "web.nvd.nist.gov",
          "url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2023-24474"
        },
        {
          "category": "external",
          "summary": "www.first.org",
          "url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H"
        }
      ],
      "remediations": [
        {
          "category": "mitigation",
          "details": "Honeywell recommends users upgrade Experion Platforms to version R520.2. Download information includes the following:",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "Experion PKS: Update to version R520.2",
          "product_ids": [
            "CSAFPID-0001"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "Experion LX: Update to version R520.2",
          "product_ids": [
            "CSAFPID-0002"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "Experion PlantCruise: Update to version R520.2",
          "product_ids": [
            "CSAFPID-0003"
          ]
        },
        {
          "category": "mitigation",
          "details": "Go to the Honeywell Website and sign in.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ],
          "url": "http://process.honeywell.com/"
        },
        {
          "category": "mitigation",
          "details": "Select \"Support\" at the top of the web page.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        },
        {
          "category": "mitigation",
          "details": "Select \"Product Documents \u0026 Downloads.\"",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "In the given search box, search for: \"Experion PKS R520.2\", \"Experion LX R520.2\" or \"Experion PlantCruise R520.2\" and select the hyperlink for the given Experion platform.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        },
        {
          "category": "mitigation",
          "details": "Honeywell advises users to follow security best practices for Experion platform environments to ensure access is limited to authorized users only. Users should ensure the backup files are maintained in a network location or physical drive with access limited to authorized users only and should not share them.Honeywell Security Notifications are available on the Honeywell website.  For access, users should visit the Honeywell Website and sign in, select the search icon at the top of the web page, and search for \"SN2023-06-22\".",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ],
          "url": "http://process.honeywell.com/"
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "baseScore": 9.8,
            "baseSeverity": "CRITICAL",
            "vectorString": "CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H",
            "version": "3.0"
          },
          "products": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        }
      ]
    }
  ]
}


Log in or create an account to share your comment.




Tags
Taxonomy of the tags.


Loading...

Loading...

Loading...

Sightings

Author Source Type Date

Nomenclature

  • Seen: The vulnerability was mentioned, discussed, or seen somewhere by the user.
  • Confirmed: The vulnerability is confirmed from an analyst perspective.
  • Exploited: This vulnerability was exploited and seen by the user reporting the sighting.
  • Patched: This vulnerability was successfully patched by the user reporting the sighting.
  • Not exploited: This vulnerability was not exploited or seen by the user reporting the sighting.
  • Not confirmed: The user expresses doubt about the veracity of the vulnerability.
  • Not patched: This vulnerability was not successfully patched by the user reporting the sighting.